Manual 2100-708A 

Page 

3 of 17

GENERAL INFORMATION 

Unpacking

Upon receipt of the equipment be sure to compare the 
model number found on the shipping label with the 
accessory identification information on the ordering and 
shipping document to verify that the correct accessory 
has been shipped.
Inspect the carton housing of each economizer as it is 
received, and before signing the freight bill, verify that 
all items have been received and that there is no visible 
damage (check parts list below). Note any shortages or 
damage on all copies of the freight bill. The receiving 
party must contact the last carrier immediately, 
preferably in writing, requesting inspection by the 
carrier’s agent. Concealed damage not discovered until 
after loading must be reported to the carrier within 15 
days of its receipt. 

General

The economizer should only be installed by a trained 
heating and air conditioning technician. These 
instructions serve as a guide to the technician installing 
the economizer package. They are not intended as a 
step-by-step procedure with which the mechanically 
inclined owner can install the package.
The economizer is shipped in one carton which 
contains the electrical harness, miscellaneous hardware 
and installation instructions.
Economizer kit includes:
(1) ECON-NC5 ventilator
(1) 910-2017 sensor assembly
(1) 3000-1627 wire assembly
(2) 7003-084 mist filters
(1) 7003-083 exhaust bug screen
(2) 1913-002-0808 8-1/2" foam strips
(4) 1913-002-0708 7-1/2" foam strips
(2) 539-405 intake sealing frames
(2) 543-223 lower block off plates
(12) #10-16x1/2 screws
(4) #8-18x3/8 pan head screws
(1) 2100-708 installation instructions

Economizer Features

•  One piece construction.
•  Exhaust air damper – built in with positive closed 

position. Provides exhaust air capability to prevent 
pressurization of tight buildings.

•  Actuator motor – 24 volt, power open, spring return 

with built in torque limiting switch.

Description

ECON-NC economizers are designed to be used 
with the wall mount series air conditioners and 
heat pumps, shown in Table 1, equipped with low 
ambient controls and field-installed controller. They 
are electromechanical economizer systems designed 
to provide “free” cooling where the outdoor air 
temperature is cool enough to provide the needed 
cooling without running the compressor, or in addition 
to the compressor. 
When cooling is required, the system automatically 
takes advantage of cold outdoor air when available and 
uses it for first stage cooling. This then reduces the 
need to run the air conditioning compressor providing 
lower operating costs and increasing the service life 
of the equipment. If the outdoor air temperature is 
too warm to be sufficient for cooling, the dry bulb 
outdoor air temperature sensor detects the condition 
and should automatically close the outdoor air intake/
exhaust damper, open the return air damper and switch 
to compressor-only operation.

Models

When installed in the models listed on the front page, 
the ECON-NC5 provides built-in exhaust provisions.  
When the damper blade opens to bring fresh air in, the 
damper also opens an exhaust relief. The exhaust air 
will flow into the condenser section of the unit. The 
condenser fan will help draw exhaust air out when it 
is operating with compressor in cooling or heat pump 
mode.

Economizer with Exhaust Model Nomenclature

ECON –  NC 

Chassis Size

5

 – 5  Ton Models

Economizer

NC – 

No Control

Summary of Contents for ECON-NC5

Page 1: ...ac com Manual 2100 708A Supersedes 2100 708 Date 9 16 19 Full Flow Economizer with Exhaust for Building Applications To Be Used with Field Installed DDC Controls Model ECON NC5 For Use with Bard Singl...

Page 2: ...l Economizer 7 Figure 14 Control Plug Centered in Plug Access Opening 7 Figure 15 Connect Economizer Power Plug to Control Panel Plug 7 Figure 16 Release the Exhaust Blade 8 Figure 17 Exhaust Blade an...

Page 3: ...s 1 2100 708 installation instructions Economizer Features One piece construction Exhaust air damper built in with positive closed position Provides exhaust air capability to prevent pressurization of...

Page 4: ...shock hazard Disconnect remote electrical power supply or supplies before servicing Failure to do so could result in electric shock or death WARNING Cut hazard Wear gloves to avoid contact with sharp...

Page 5: ...hrough side intake openings and discard see Figure 5 Blank Off Plate FIGURE 4 Remove Blank Off Plates Both Sides FIGURE 5 Remove Exhaust Blank Off Plate Remove both air filters and the low voltage inn...

Page 6: ...ing and into the wire channel see Figure 11 Plug the wires into the 3000 1627 wire harness that plugs into the 12 pin low voltage connector Route the sensor wires over the top of the outdoor fan motor...

Page 7: ...n page 5 and slide in until flush with the side of the wall mount Economizer can be installed from either side FIGURE 13 Install Economizer When the economizer is fully installed the control plug shou...

Page 8: ...lade FIGURE 17 Exhaust Blade and Latch Bend the two 2 sheet metal tabs in the condenser partition up to hold the bottom of the mist eliminator in place Install 7003 084 mist filters on both sides see...

Page 9: ...y air duct static pressure drop 3 Indoor blower motor speed 4 Damper blade open position setting Refer to the appropriate graph on pages 14 and 15 to determine the blade setting Bend the two 2 sheet m...

Page 10: ...uring scheduled occupied periods Must be configured for multi stage for Y1 output to be active 1st stage cooling For dehumidification must be configured for No Economizer for YO D to be active for hum...

Page 11: ...tat if optional CO2 controller is used control optional for ECON only see vent instruction manuals 0 10 VDC modulating C02 control signal for modulating ventilation 6 8 7 Do not add these wires if set...

Page 12: ...l for modulating ventilation control Optional for ECON Only See vent installation manual 6 For vent operation add jumper if optional CO2 controller is not used Vent will run while blower is energized...

Page 13: ...tional for ECON Only See vent installation manual 6 For vent operation add jumper if optional CO2 controller is not used Vent will run while blower is energized For ECON CRV V an additional wire chang...

Page 14: ...Manual 2100 708A Page 14 of 17 GRAPH 1 W42AC ECON E WD Ventilation Delivery GRAPH 2 W48AC ECON E WD Ventilation Delivery...

Page 15: ...Manual 2100 708A Page 15 of 17 GRAPH 3 W60AC ECON E WD Ventilation Delivery GRAPH 4 W72AC ECON E WD Ventilation Delivery...

Page 16: ...Manual 2100 708A Page 16 of 17 FIGURE 26 Call for Compressor or Fan Only with Ventilation Off FIGURE 25 Call for Ventilation With or Without Compressor Operation...

Page 17: ...E 0 10V DC INPUT SIGNAL RED WHITE 10K OHM BLACK THERMISTOR 10K OD SENSOR ORANGE 12 PIN 10K OHM THERMISTOR RED VENT PLUG 24V INPUT SIGNAL NO CONTROL ECONOMIZER WIRING DIAGRAM OD TEMP PURPLE 10K OD BROW...