If COMP LOCKOUT was chosen during the heat 
strip configuration process, an optional outdoor 
air temperature sensor will have to be installed/
configured to specifically set the temperature at which 
the compressor will no longer be allowed to operate. 
Refer to the latest version of 

CompleteStat Controller 

Advanced Programming & Features 2100-685

 to 

configure the outdoor air temperature sensor.

 

To install Bard 8403-061 Outdoor Air Temperature 
Sensor, attach the leads to terminals “OAT” and 
“GND”. To set the compressor outdoor air temperature 
limits from the home screen:

1. Press 

RIGHT button to access Main Menu screen.

2. Press 

DOWN button to scroll to TECHNICIAN. 

Press ENTER button.

3.  In the TECHNICIAN menu screen, press UP or 

DOWN button to scroll to LIMITS. Press ENTER 
button.

4.  Press DOWN button to scroll to COMP OAT CLG 

LOW. Press ENTER button.

5.  Press UP or DOWN button to select outdoor air 

temperature for compressor lockout (factory default 
0ºF). Press ENTER to save choice.

6.  Press LEFT button to return to TECHNICIAN menu.

Ventilation, Fan and Humidity Setup

1.  In the  TECHNICIAN menu screen, press ENTER 

button to enter the APPLICATION menu. 

2.  Press DOWN button to scroll to ADDITIONAL 

SETUP. Press ENTER button.

3.  Press DOWN button to scroll to VENTILATION. 

Press ENTER button.

4.  Press UP or DOWN button to choose from the 

available economizer options:

 

•  NONE = No economizer, or standard vent 

package (ERV/CRV/MFAD). This is the factory 
default.

 

•  EN/DIS = Economizer in system

5.  Press ENTER button to select/save appropriate 

economizer option.

6.  Press LEFT button to go back to ADDITIONAL 

SETUP.

7.  The indoor blower can be set for ON or AUTO 

in either occupied or unoccupied conditions.

 

To 

access or change blower settings, press DOWN 
button to scroll to FAN. Press ENTER button to 
enter FAN SETUP (see Figure 9). 

8.  Press DOWN button to scroll through selections; 

adjust as necessary.

 

•  Speeds: Constant speed (nonadjustable)

FAN SETUP

SPEEDS: 

CONSTANT SPEED

OFF DELAY (SECS): 0

UNOCC: AUTO

OCC: AUTO

FIGURE 9

Fan Setup (Heat Pump)

 

•  Off Delay: “0” = System fan will run for 

specified time after call ends; 0-600 seconds 
in 30-second increments.

 • Unocc: “ON” = System fan will run continuously 

during all operational modes; “AUTO” = System 
fan will operate during call for cooling or 
heating, but will cycle off when no compressor 
or no heating is needed (factory default).

 

•  Occ: “ON” = System fan will run continuously 

during all operational modes; “AUTO” = 
System fan will operate during call for 
cooling or heating, but will cycle off when no 
compressor or no heating is needed (factory 
default).

9.  Press ENTER button to save changes to FAN 

SETUP selections.

10. Press LEFT button to go back to ADDITIONAL 

SETUP.

11. Press DOWN button to scroll to HUMIDITY. Press 

ENTER button to enter HUMIDITY SETUP.

12. Press ENTER button again to choose 

DEHUMIDIFICATION (see Figure 10).

13. Press ENTER button again to highlight current 

dehum choice (default is ENABLE).

14. Press UP or DOWN button to toggle ENABLE/

DISABLE. Press ENTER button to select/save 
choice.

15. Press DOWN button to scroll through additional 

DEHUMIDIFICATION screen choices:

 • ALLOW HTG DEHUM = Allows 

dehumidification in heating as well as cooling:  
YES/NO (default is YES).

 • DEHUM SETPT = Relative Humidity (RH) 

setpoint: 45% RH to 80% RH, 1% increments 
(default is 60%RH).

 

•  DEHUM SPAN = Amount of RH% removal 

allowed past setpoint: 5% to 10%, 1% 
increments (default is 5%RH).

16. Press ENTER button to save changes. 

Summary of Contents for CompleteStat CS9B-THOA

Page 1: ...ATION OPERATION QUICK START GUIDE Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 684 Supersedes NEW Date 3 20 18 CompleteStatTM Controller Models CS9B THOA CS9B THOCA CS9...

Page 2: ...o Economizer 16 WD 2 Conventional 1H 1C or 2H 1C with Honeywell W7220 JADETM Control Economizer with or without Dehumidification 17 WD 3 Conventional 1H 2C or 2H 2C with Honeywell W7220 JADETM Control...

Page 3: ...n the bottom and top of the controller clockwise inward until they clear the cover Remove base plate from controller INSTALLATION 3 Route control wiring through base plate 4 With the embossed UP arrow...

Page 4: ...Setback 15 Heat Setback 16 Standby Time Minutes 17 Motion Sensing Daily Schedule 18 Date 19 Time 20 Occupied Minimum Cooling 21 Occupied Maximum Cooling 22 Unoccupied Minimum Cooling 23 Unoccupied Max...

Page 5: ...onds factory default is 120 seconds See page 14 in the latest version of CompleteStat Controller Advanced Programming Features 2100 685 for information on adjusting the inactivity setting NOTE If the...

Page 6: ...No economizer or standard vent package ERV CRV MFAD EN DIS Economizer in system FAN SETUP SPEEDS CONSTANT SPEED OFF DELAY SECS 0 UNOCC AUTO OCC AUTO FIGURE 5 Fan Setup Air Conditioner 3 Press ENTER b...

Page 7: ...8 8 Press UP or DOWN button to scroll through AUX HEAT screen choices W O LOCKOUT Auxiliary heat will activate regardless of compressor operation or outdoor air temperature factory default If W O LOCK...

Page 8: ...IONAL SETUP 7 The indoor blower can be set for ON or AUTO in either occupied or unoccupied conditions To access or change blower settings press DOWN button to scroll to FAN Press ENTER button to enter...

Page 9: ...EM ENABLE options use UP or DOWN buttons to scroll through choices AUTO factory default System is in Auto Changeover mode HVAC system will cycle heating and cooling automatically to stay within preset...

Page 10: ...The controller will not allow heating cooling setpoints to contradict one another or to be within a degree of conflicting operation NOTE Any system startup with indoor ambient temperatures lower than...

Page 11: ...r Output 24VAC SPST Relay SC Not Used 24VAC Hot O B Reversing Valve Output 24VAC SPST Relay G Indoor Blower Output 24VAC SPST Relay IN9 Not Used ROS Remote Occupancy Sensor Input Dry Contact Input to...

Page 12: ...tioning or through constant fan operation Operation G Y O Y1 Y2 W1 E W2 O B D A Fan Only X 1st Stage Cooling Economizer X X 2nd Stage Cooling X X X 3rd Stage Cooling if employed X X X X 1st Stage Heat...

Page 13: ...at must be configured for a heat pump application see Auxiliary Electric Heat Setup on page 7 Operation G Y O Y1 Y2 W1 E W2 O B D A Fan Only X 1st Stage Cooling X X 1st Stage Heating X X X X2 2nd Stag...

Page 14: ...ectric Heat Setup on page 7 Operation G Y O Y1 Y2 W1 E W2 O B D A Fan Only X 1st Stage Cooling X X X 2nd Stage Cooling X X X 3rd Stage Cooling X X X X 1st Stage Heating X X X X2 2nd Stage Heating X X...

Page 15: ...Factory T or W Economizer w JADE W7220 Control On Off 8 Gas Electric THOA THOCA A C 1H 1C None 1 Stage A C with Gas Heat CRV ERV MFAD On Off 9 Gas Electric THOA THOCA A C 1H 2C None 2 Stage A C with G...

Page 16: ...es and jumpers Factory installed wires and jumpers Wire for dehumidification units only 1 Remove jumper for 2 stage heat 15kW or more 3 Wire only for 2 stage cooling if available 4 W A2 units use D te...

Page 17: ...installed wires and jumpers Factory installed wires and jumpers Wire for dehumidification units only 1 Remove jumper for 2 stage heat 15kW or more 3 CompleteStat programmed for damper economizer Enabl...

Page 18: ...Factory installed wires and jumpers 1 Remove jumper for 2 stage heat 15kW or more 3 CompleteStat programmed for damper economizer Enable Disable 4 Field installed wire nut 1 2 3 3 4 CompleteStatTM WIR...

Page 19: ...alled wire nut on 9 EER W A2 A1 units For W AA units consult unit installation instructions 2 Field installed wires and jumpers Factory installed wires and jumpers Wire for dehumidification units only...

Page 20: ...wires and jumpers 1 Field installed wire nut 3 CompleteStat programmed for damper economizer Enable Disable 4 CH S Series heat pumps use DH dehumidification terminal CompleteStatTM WIRING DIAGRAM 8 G...

Page 21: ...ump Series with No Ventilation Wire for dehumidification units only 2 Field installed wires and jumpers Factory installed wires and jumpers 1 W G Series uses A terminal for ventilation 3 Wire not used...

Page 22: ...RAM 11 I TEC 2 Stage Heat Pump Series with CRV Ventilation Package Wire for dehumidification units only 2 Field installed wires and jumpers Factory installed wires and jumpers 1 Wire not needed if aux...

Page 23: ...ith ERV Ventilation Package and 8403 067 CO2 Detector Fully Modulating Wire for dehumidification units only 2 Field installed wires and jumpers Factory installed wires and jumpers 1 Wire not needed if...

Page 24: ...on Field installed wires and jumpers Factory installed wires and jumpers Q Series with factory installed thermostat had no terminal board and were wired directly from Plug 4 Use provided colors to wir...

Page 25: ...StatTM WIRING DIAGRAM 15 QW S Series 2 Stage Heat Pump with or without Dehumidification and Ventilation WIRING DIAGRAM 16 C H Heat Pump 2 Stage with Honeywell W7220 JadeTM Control Economizer with or w...

Reviews: