6. Press UP or DOWN buttons to enter appropriate
heating setpoint. Press ENTER button to save new
heating setpoint.
7. Follow the steps provided above to adjust cooling
and heating setback temperatures, dehum setpoint
and span, and CO
2
setpoint and span of control in
parts per million (if available).
8. Press LEFT button to return to the home screen.
NOTE:
The controller will not allow heating/cooling
setpoints to contradict one another, or to be
within a degree of conflicting operation.
NOTE:
Any system startup with indoor ambient
temperatures lower than 56°F or above 86°F,
or humidity higher than 65%, will experience
an internal Low Temperature or High
Temperature alarm. This will not affect normal
operation and can be cleared easily.
Bard CompleteStat should be operational at this point.
For further controller enhancement or operation detail,
please consult the latest edition of
CompleteStat
Advanced Programming & Features 2100-685
.