background image

Manual 2100-719 

Page 

25 of 25

Motor

Motor OK when

R > 100k ohm

ECM 2.0

Only remove
Hex Head Bolts

Connector Orientation

Between 4 and 8 o'clock

Drip Loop

Back of

Control

Figure 5

Winding Test

Figure 4

Note:              
Use the shorter 
bolts and 
alignment pin 
supplied when 
replacing an 
ECM 2.0 
control.

Figure 3

ECM 
2.3/2.5

Power Connector
(5-pin)

Control Connector
(16-pin)

Hex-head Screws

Motor Connector
(3-pin)

Motor Connector
(3-pin)

Control Disassembly

Drip Loop

Push until

Latch Seats
Over Ramp

From Motor

Circuit

Board

 

Figure 10

Figure 11

Figure 12

TROUBLESHOOTING  GE  ECM

 MOTORS CONT’D.

Replacing ECM Control Module

To replace the control module for the GE variable-speed indoor blower motor 
you need to take the following steps:
 

1.  You MUST have the correct replacement module.  The controls are 

factory programmed for specific operating modes.  Even though they look 

alike, different modules may have completely different functionality.

USING THE WRONG CONTROL MODULE VOIDS ALL PRODUCT 
WARRANTIES AND MAY PRODUCE UNEXPECTED RESULTS.

 

2.  Begin by removing AC power from the furnace or air handler being 

serviced.  

DO NOT WORK ON THE MOTOR WITH AC POWER 

APPLIED.  

To avoid electric shock from the motor’s capacitors, disconnect 

power and wait at least 5 minutes before opening motor.

 

3.  It is usually not necessary to remove the motor from the blower 

assembly.  However, it is recommended that the whole blower assembly, 
with the motor, be removed from the furnace/air handler.  (Follow the 
manufacturer’s procedures).  Unplug the two cable connectors to the motor.  
There are latches on each connector.  

DO NOT PULL ON THE WIRES.  

The plugs remove easily when properly released.

 

4.  Locate the two standard ¼" hex head bolts at the rear of the control 

housing (at the back end of the control opposite the shaft end).  

Refer to 

Figure 10.  

Remove these two bolts from the motor and control assembly 

while holding the motor in a way that will prevent the motor or control 
from falling when the bolts are removed.  If an ECM2.0 control is being 
replaced (recognized by an aluminum casting rather that a deep-drawn 
black steel can housing the electronics), remove only the hex-head bolts.  

DO NOT REMOVE THE TORX-HEAD SCREWS.

 

5.  The control module is now free of mechanical attachment to the 

motor endshield but is still connected by a plug and three wires inside 
the control.  Carefully rotate the control to gain access to the plug at 

the control end of the wires.  With thumb and forefinger, reach the latch 

holding the plug to the control and release it by squeezing the latch tab 
and the opposite side of the connector plug and gently pulling the plug 
out of the connector socket in the control.  

DO NOT PULL ON THE 

WIRES.  GRIP THE PLUG ONLY.

 

6.  The control module is now completely detached from the motor.  

Verify with a standard ohmmeter that the resistance from each motor 
lead (in the motor plug just removed) to the motor shell is >100K ohms.  

Refer to Figure 11.  

(Measure to unpainted motor end plate.)  If any motor 

lead fails this test, do not proceed to install the control module.  

THE 

MOTOR IS DEFECTIVE AND MUST BE REPLACED.

  Installing 

the new control module will cause it to fail also.

 

7.  Verify that the replacement control is correct for your application.  

Refer to the manufacturer's authorized replacement list.  

USING THE 

WRONG CONTROL WILL RESULT IN IMPROPER OR NO 
BLOWER OPERATION.

  Orient the control module so that the 3-wire 

motor plug can be inserted into the socket in the control.  Carefully insert 
the plug and press it into the socket until it latches.  

A SLIGHT CLICK 

WILL BE HEARD WHEN PROPERLY INSERTED.

  Finish installing 

the replacement control per one of the three following paragraphs, 8a, 8b or 8c.

 8a. 

IF REPLACING AN ECM 2.0 CONTROL

 (control in cast 

aluminum can with air vents on the back of the can) 

WITH AN ECM 

2.3 CONTROL

 (control containing black potting for water protection in 

black deep-drawn steel case with no vents in the bottom of the can), locate 
the two through-bolts and plastic tab that are packed with the replacement 
control.  Insert the plastic tab into the slot at the perimeter of the open end 
of the can so that the pin is located on the inside of the perimeter of the 
can.  Rotate the can so that the tab inserts into the tab locator hole in the 
endshield of the motor.  Using the two through-bolts provided with the 
replacement control, reattach the can to the motor.

THE TWO THROUGH-BOLTS PROVIDED WITH THE 
REPLACEMENT ECM 2.3 CONTROL ARE SHORTER THAN 
THE BOLTS ORIGINALLY REMOVED FROM THE ECM 2.0 
CONTROL AND MUST BE USED IF SECURE ATTACHMENT OF 
THE CONTROL TO THE MOTOR IS TO BE ACHIEVED.
DO NOT OVERTIGHTEN THE BOLTS.

 

 8b. 

IF REPLACING AN ECM 2.3 CONTROL

 

WITH AN ECM 2.3 

CONTROL

, the plastic tab and shorter through-bolts are not needed.  The 

control can be oriented in two positions 180° apart.  

MAKE SURE THE 

ORIENTATION YOU SELECT FOR REPLACING THE CONTROL 
ASSURES THE CONTROL'S CABLE CONNECTORS WILL 
BE LOCATED DOWNWARD IN THE APPLICATION SO THAT 
WATER CANNOT RUN DOWN THE CABLES AND INTO THE 
CONTROL.

  Simply orient the new control to the motor's endshield, insert 

bolts, and tighten.  

DO NOT OVERTIGHTEN THE BOLTS.

 

8c. 

IF REPLACING AN ECM 2.0 CONTROL WITH AN ECM 2.0 

CONTROL (It is recommended that ECM 2.3 controls be used for all 
replacements), 

the new control must be attached to the motor using through 

bolts identical to those removed with the original control.  

DO NOT 

OVERTIGHTEN THE BOLTS.

 

9.  Reinstall the blower/motor assembly into the HVAC equipment.  

Follow the manufacturer's suggested procedures.

 

10. Plug the 16-pin control plug into the motor.  The plug is keyed.  

Make sure the connector is properly seated and latched.

 

11. Plug the 5-pin power connector into the motor.  Even though the 

plug is keyed, 

OBSERVE THE PROPER ORIENTATION.  DO NOT 

FORCE THE CONNECTOR.

  It plugs in very easily when properly 

oriented.  

REVERSING THIS PLUG WILL CAUSE IMMEDIATE 

FAILURE OF THE CONTROL MODULE.

 12. 

Final installation check.  Make sure the motor is installed as follows:

 

 

a. Unit is as far INTO the blower housing as possible.

 

 

b. Belly bands are not on the control module or covering vent holes.

 

 

c. Motor connectors should be oriented between the 4 o’clock and 8  

      o’clock positions when the blower is positioned in its final    

 

 

  location and orientation.

 

 

d. Add a drip loop to the cables so that water cannot enter the motor  

 

 

  by draining down the cables.  

Refer to Figure 12.

The installation is now complete.  Reapply the AC power to the HVAC 
equipment and verify that the new motor control module is working 
properly.  Follow the manufacturer's procedures for disposition of the old 
control module.

Summary of Contents for C24H2-A

Page 1: ...ION INSTRUCTIONS C24H2 A C24H2 B C30H2 A C30H2 B C30H2 C C36H1 A C36H1 B C36H1 C C42H1 A C42H1 B C42H1 C Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 719 Supersedes NEW...

Page 2: ...H 22 Table 7 Indoor Blower Performance 23 Getting Other Information and Publications 3 Wall Mount General Information Wall Mount Model Nomenclature 4 Shipping Damage 4 General 4 Duct Work 5 Filters 5...

Page 3: ...nter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditionin...

Page 4: ...o methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Cond...

Page 5: ...is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum velocity of 400 fpm NOTE If no return air duc...

Page 6: ...rs on the lag bolts 7 Secure rain flashing to wall and caulk across entire length of top See Figures 3A 3B 8 For additional mounting rigidity the return air and supply air frames or collars can be dri...

Page 7: ...s of Basic Unit for Architectural Installation Requirements Nominal MODEL WIDTH W DEPTH D HEIGHT H SUPPLY RETURN A B C B E F G I J K L M N O P Q R S T C24H2 C30H2 38 200 17 125 70 563 7 88 27 88 13 88...

Page 8: ...LEARANCE ON ALL RAIN FLASHING COMBUSTIBLE MATERIALS DUCT TOP FLASHING AT TIME OF INSTALLATION 1 4 MIN CLEARANCE FROM REQUIRED DIMENSIONS TO MAINTAIN OPENING ENTIRE LENGTH OF TOP MATERIALS NOTES OF CAU...

Page 9: ...URE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MOUNTING FLANGES AND UNDER TOP FLASHING...

Page 10: ...This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible...

Page 11: ...R FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR...

Page 12: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Page 13: ...cess panel straight out This tab will now line up with the slot in the door When shut a padlock may be placed through the hole in the tab preventing entry See Start Up section for important informatio...

Page 14: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Page 15: ...However reverse operation for over one hour may have a negative impact on the bearing due to oil pump out NOTE If compressor is allowed to run in reverse rotation for several minutes the compressor s...

Page 16: ...ump control will place the system in the defrost mode During the defrost mode the refrigerant cycle switches back to the cooling cycle the outdoor motor stops electric heaters are energized and hot ga...

Page 17: ...res the control will then monitor the low pressure switch input normally to make sure that the switch is closed during Y operation High Pressure Switch Operation The control has a built in lockout sys...

Page 18: ...RV C and B C 1 Check control circuit wiring 2 Replace heat pump control Reversing valve solenoid coil defective Check for open or shorted coil Replace solenoid coil Unit will not go into defrost heati...

Page 19: ...36 29157 74 10762 112 4464 1 88139 37 28355 75 10501 113 4367 0 85371 38 27577 76 10247 114 4274 1 82699 39 26823 77 10000 115 4182 2 80121 40 26092 78 9760 116 4093 3 77632 41 25383 79 9526 117 4006...

Page 20: ...th this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this information sho...

Page 21: ...GH SIDE 133 302 133 321 133 341 134 365 136 391 137 418 138 449 141 481 143 516 146 553 80 DB 67 WB LOW SIDE HIGH SIDE 142 310 142 329 142 350 143 374 145 401 146 429 148 460 151 493 153 529 156 567 8...

Page 22: ...60 1 1 22 30 10 10 A04 1 42 50 8 10 AS8 1 48 50 8 10 AF8 1 or 2 63 70 6 8 22 42 30 45 10 8 10 10 C24H2 B0Z 230 208 60 3 1 15 20 12 12 B06 1 33 35 8 10 B09 1 42 45 8 10 C30H2 A0Z 230 208 60 1 1 23 30 1...

Page 23: ...hese units are equipped with a variable speed ECM indoor motor that automatically adjusts itself to maintain approximately the same rate of indoor airflow in both heating cooling dry wet coil conditio...

Page 24: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check...

Page 25: ...is correct for your application Refer to the manufacturer s authorized replacement list USING THE WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION Orient the control module so that the 3 w...

Reviews: