background image

Manual 2100-719 

Page 

13 of 25

WIRING  –  MAIN POWER

Refer to the unit rating plate for wire sizing information 
and maximum fuse or “HACR” type circuit breaker 
size.  Each outdoor unit is marked with a “Minimum 

Circuit Ampacity”.  This means that the field wiring 

used must be sized to carry that amount of current. 
Depending on the installed KW of electric heat, there 

may be two field power circuits required.  If this is the 

case, the unit serial plate will so indicate.  All models 
are suitable only for connection with copper wire. Each 
unit and/or wiring diagram will be marked “Use Copper 
Conductors Only”.  These instructions 

must be 

adhered 

to.  Refer to the National Electrical Code (NEC) for 
complete current carrying capacity data on the various 
insulation grades of wiring material.  All wiring must 
conform to NEC and all local codes.

The electrical data lists fuse and wire sizes (75°C 
copper) for all models including the most commonly 

used heater sizes.  Also shown are the number of field 

power circuits required for the various models with 
heaters.

The unit rating plate lists a “Maximum Time Delay 
Relay Fuse” or “HACR” type circuit breaker that is to 
be used with the equipment.  The correct size must be 
used for proper circuit protection and also to assure that 
there will be no nuisance tripping due to the momentary 
high starting current of the compressor motor.

The disconnect access door on this unit may be locked 
to prevent unauthorized access to the disconnect.  To 
convert for the locking capability, bend the tab located 
in the bottom left-hand corner of the disconnect 
opening under the disconnect access panel straight 
out.  This tab will now line up with the slot in the door.  
When shut, a padlock may be placed through the hole 
in the tab preventing entry.

See “Start Up” section for important information on 
three phase scroll compressor start ups.

See Table 6 for Electrical Specifications.

WIRING  –  LOW VOLTAGE WIRING 

230/208V, 1 phase and 3 phase units are equipped with 
dual primary voltage transformers.  All equipment 
leaves the factory wired on 240V tap.  For 208V 
operation, reconnect from 240V to 208V tap.  The 
acceptable operating voltage range for the 240 and 
208V taps are:

 

TAP RANGE

 

240 

253 – 216

 

208 

220 – 187

NOTE:  The voltage should be measured at the field 

power connection point in the unit and while 
the unit is operating at full load (maximum 
amperage operating condition).

For wiring size and connections, refer to Wiring 
Manual 2100-554.

OPTIONAL OUTDOOR THERMOSTAT 
APPLICATIONS

Since most equipment at the time of manufacture is not 

designated for any specific destination of the country 

and are installed in areas not approaching the lower 
outdoor temperature range, outdoor thermostats are not 
factory installed as standard equipment, but are offered 

as an option.  See Specification Sheet for outdoor 

thermostat options.  They may vary according to the 
thermostat used to control the unit.  There are also 
different applications for applying outdoor thermostats.  
The set point of either type of outdoor thermostat 
application is variable with geographic region and 
sizing of the heating equipment to the individual 
structure.  Utilization of the heating Application Data, 
and the heat loss calculation of the building are useful 
in determining the correct set points.

NOTE: The additional LAB (low ambient bypass) relay 
is required to prevent heater operation during low 
temperature cooling operation.

Summary of Contents for C24H2-A

Page 1: ...ION INSTRUCTIONS C24H2 A C24H2 B C30H2 A C30H2 B C30H2 C C36H1 A C36H1 B C36H1 C C42H1 A C42H1 B C42H1 C Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 719 Supersedes NEW...

Page 2: ...H 22 Table 7 Indoor Blower Performance 23 Getting Other Information and Publications 3 Wall Mount General Information Wall Mount Model Nomenclature 4 Shipping Damage 4 General 4 Duct Work 5 Filters 5...

Page 3: ...nter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditionin...

Page 4: ...o methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Cond...

Page 5: ...is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum velocity of 400 fpm NOTE If no return air duc...

Page 6: ...rs on the lag bolts 7 Secure rain flashing to wall and caulk across entire length of top See Figures 3A 3B 8 For additional mounting rigidity the return air and supply air frames or collars can be dri...

Page 7: ...s of Basic Unit for Architectural Installation Requirements Nominal MODEL WIDTH W DEPTH D HEIGHT H SUPPLY RETURN A B C B E F G I J K L M N O P Q R S T C24H2 C30H2 38 200 17 125 70 563 7 88 27 88 13 88...

Page 8: ...LEARANCE ON ALL RAIN FLASHING COMBUSTIBLE MATERIALS DUCT TOP FLASHING AT TIME OF INSTALLATION 1 4 MIN CLEARANCE FROM REQUIRED DIMENSIONS TO MAINTAIN OPENING ENTIRE LENGTH OF TOP MATERIALS NOTES OF CAU...

Page 9: ...URE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MOUNTING FLANGES AND UNDER TOP FLASHING...

Page 10: ...This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible...

Page 11: ...R FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR...

Page 12: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Page 13: ...cess panel straight out This tab will now line up with the slot in the door When shut a padlock may be placed through the hole in the tab preventing entry See Start Up section for important informatio...

Page 14: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Page 15: ...However reverse operation for over one hour may have a negative impact on the bearing due to oil pump out NOTE If compressor is allowed to run in reverse rotation for several minutes the compressor s...

Page 16: ...ump control will place the system in the defrost mode During the defrost mode the refrigerant cycle switches back to the cooling cycle the outdoor motor stops electric heaters are energized and hot ga...

Page 17: ...res the control will then monitor the low pressure switch input normally to make sure that the switch is closed during Y operation High Pressure Switch Operation The control has a built in lockout sys...

Page 18: ...RV C and B C 1 Check control circuit wiring 2 Replace heat pump control Reversing valve solenoid coil defective Check for open or shorted coil Replace solenoid coil Unit will not go into defrost heati...

Page 19: ...36 29157 74 10762 112 4464 1 88139 37 28355 75 10501 113 4367 0 85371 38 27577 76 10247 114 4274 1 82699 39 26823 77 10000 115 4182 2 80121 40 26092 78 9760 116 4093 3 77632 41 25383 79 9526 117 4006...

Page 20: ...th this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this information sho...

Page 21: ...GH SIDE 133 302 133 321 133 341 134 365 136 391 137 418 138 449 141 481 143 516 146 553 80 DB 67 WB LOW SIDE HIGH SIDE 142 310 142 329 142 350 143 374 145 401 146 429 148 460 151 493 153 529 156 567 8...

Page 22: ...60 1 1 22 30 10 10 A04 1 42 50 8 10 AS8 1 48 50 8 10 AF8 1 or 2 63 70 6 8 22 42 30 45 10 8 10 10 C24H2 B0Z 230 208 60 3 1 15 20 12 12 B06 1 33 35 8 10 B09 1 42 45 8 10 C30H2 A0Z 230 208 60 1 1 23 30 1...

Page 23: ...hese units are equipped with a variable speed ECM indoor motor that automatically adjusts itself to maintain approximately the same rate of indoor airflow in both heating cooling dry wet coil conditio...

Page 24: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check...

Page 25: ...is correct for your application Refer to the manufacturer s authorized replacement list USING THE WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION Orient the control module so that the 3 w...

Reviews: