Manual 2100-614I
Page
15 of 43
Log In Page
1. Type “Admin” for user name and “Bard” for
password. These are case sensitive. Hit “Log In”.
The System Status Page will appear.
System Status Page
The System Status Page shows:
1. The overall HVAC status of:
a. Active cooling or heating stages or
dehumidification mode (requires humidity
sensor)
b. Active controller outputs (blower, cooling Stage
1 or 2, heating) to each air conditioner
c. Which unit is the Lead unit
d. Power loss or refrigerant lockout for each air
conditioner
e. If economizers are used if on or off (
NOTE:
older style EIFM economizers require a simple
relay kit for this feature to work, Bard Part
Number 8620-221)
2. General status of:
a. Dehumidification Active or not
b. Backup Generator Active or not (if tied to
generator run controls to inhibit lag unit
operation during generator run)
c. Alarm board connected or not
d. Controller system Locked or Unlocked
e. Comfort mode Active or not
3. Temperatures:
a. Average temperature (if more than one sensor
used, if not will read same as Local sensor)
b. Local sensor at controller
c. Remote 1 or Remote 2 if connected
4. General Alarm Status:
a. Fire/Smoke, Clear or Alarm
b. Low Temp, Clear or Alarm
c. High Temp #1, Clear or Alarm
d. High Temp #2, Clear or Alarm
e. Controller Failure, Clear or Alarm
Click the “IP Setup” button on the left side of the
page.
NOTE:
If the remote user is on a different subnet
than the CB5000, it is recommended that Static IP
Addressing be used rather than DHCP.
MC4000 HVAC Monitor / Controller
MC4000 HVAC Monitor / Controller
MC4000 HVAC Monitor / Controller