V
alues listed are with ventilation package disabled
2
Return air temperature °F @ Default airflow (900 CFM) for AC tests and Balanced Climate airflow (650 CFM) for dehumidification tes
ts
3
Below 50°F
, unit requires a factory or field installed low ambient control.
4
Suction pr/- 4 psi, Discharge pr/- 10 psi
DB/WB
2
OD T
emp.
65°F
3
70°F
75°F
80°F
85°F
90°F
95°F
100°F
105°F
Mode
A/C
Dehum
A/C
Dehum
A/C
Dehum
A/C
Dehum
A/C
Dehum
A/C
Dehum
A/C
Dehum
A/C
Dehum
A/C
Dehum
75/62.5 (50% RH)
Total Cooling Btuh
30,600
15,200
29,700
13,000
29,100
10,600
28,100
8,800
27,400
6,800
26,600
4,800
25,800
3,000
25,100
1,200
24,400
Sensible Btuh
22,600
7,200
22,100
5,600
21,800
4,100
21,300
2,500
21,000
900
20,700
(600)
20,500
(2,000)
20,400
(3,500)
20,300
(4,900)
S/T
0.739
0.474
0.744
0.431
0.749
0.387
0.758
0.284
0.766
0.132
0.778
0
0.795
0
0.813
0
0.832
0
Latent Btuh
8,000
8,000
7,600
7,400
7,300
6,500
6,800
6,300
6,400
5,900
5,900
5,400
5,300
5,000
4,700
4,700
4,100
4,300
Lbs. H20/hr
.
7.5
7.5
7.2
7.0
6.9
6.1
6.4
5.9
6.0
5.6
5.6
5.1
5.0
4.7
4.4
4.4
3.9
4.1
Supply Air DB
51.7
65.6
52.0
67.7
52.3
69.6
52.6
71.8
53.0
73.8
53.5
75.8
54.0
77.8
54.6
79.8
55.2
81.7
Supply Air WB
50.5
55.4
50.7
56.4
50.9
57.4
51.3
58.4
51.7
59.4
52.1
60.3
52.5
61.3
53.0
62.2
53.6
63.1
Suction PSIG
4
119
116
120
118
121
120
122
122
123
124
125
126
126
127
127
128
129
130
Discharge PSIG
4
272
242
292
256
312
271
334
286
356
301
380
317
404
333
429
350
456
366
75/64.1 (55% RH)
Total Cooling Btuh
31,400
16,300
30,500
14,100
29,700
11,900
28,900
9,900
28,100
7,900
27,400
5,900
26,600
4,100
25,900
2,300
25,200
500
Sensible Btuh
21,400
6,400
20,900
4,900
20,400
3,300
20,000
1,700
19,700
200
19,400
(1,300)
19,300
(2,800)
19,100
(4,200)
19,100
(5,700)
S/T
0.682
0.39
0.685
0.35
0.687
0.28
0.692
0.17
0.701
0.03
0.708
0
0.726
0
0.737
0
0.758
0
Latent Btuh
10,000
9,900
9,600
9,200
9,300
8,600
8,900
8,200
8,400
7,700
8,000
7,200
7,300
6,900
6,800
6,500
6,100
6,200
Lbs. H20/hr
.
9.4
9.3
9.1
8.7
8.8
8.1
8.4
7.7
7.9
7.3
7.5
6.8
6.9
6.5
6.4
6.1
5.8
5.8
Supply Air DB
53.0
66.6
53.2
68.6
53.5
70.7
53.9
72.7
54.3
74.8
54.7
76.8
55.3
78.8
55.8
80.7
56.5
82.7
Supply Air WB
51.9
56.4
52.1
57.5
52.4
58.5
52.7
59.5
53.1
60.5
53.5
61.4
54.0
62.4
54.5
63.3
55.0
64.2
Suction PSIG
4
123
119
124
121
125
123
126
125
127
127
128
129
130
130
131
131
132
133
Discharge PSIG
4
274
245
294
259
314
274
336
289
358
304
382
320
406
336
431
352
458
369
75/65.5 (60% RH)
Total Cooling Btuh
32,100
17,300
31,300
15,100
30,700
12,800
29,700
10,900
28,900
8,900
28,200
7,000
27,400
5,100
26,700
3,300
26,000
1,600
Sensible Btuh
20,100
5,700
19,600
4,100
19,300
2,600
18,800
1,000
18,500
(500)
18,200
(2,000)
18,000
(3,500)
17,900
(5,000)
17,800
(6,400)
S/T
0.626
0.329
0.626
0.272
0.629
0.203
0.633
0.092
0.640
0
0.645
0
0.657
0
0.670
0
0.685
0
Latent Btuh
12,000
11,600
11,700
11,000
11,400
10,200
10,900
9,900
10,400
9,400
10,000
9,000
9,400
8,600
8,800
8,300
8,200
8,000
Lbs. H20/hr
.
11.3
10.9
11.0
10.4
10.8
9.6
10.3
9.3
9.8
8.9
9.4
8.5
8.9
8.1
8.3
7.8
7.7
7.5
Supply Air DB
54.3
67.6
54.5
69.6
54.8
71.6
55.1
73.7
55.5
75.7
56.0
77.7
56.5
79.7
57.1
81.7
57.8
83.7
Supply Air WB
53.3
57.5
53.5
58.5
53.7
59.6
54.1
60.6
54.5
61.5
54.9
62.5
55.4
63.4
55.9
64.4
56.4
65.3
Suction PSIG4
126
122
127
124
128
126
129
128
131
130
132
132
133
133
134
134
136
136
Discharge PSIG4
276
248
296
262
316
277
338
292
360
307
384
323
408
339
434
355
460
372
75/66.7 (65% RH)
Total Cooling Btuh
32,900
18,400
32,100
16,200
31,500
13,800
30,500
12,000
29,700
10,000
29,000
8,100
28,200
6,200
27,500
4,400
26,800
2,700
Sensible Btuh
18,900
5,000
18,400
3,400
18,000
1,900
17,500
300
17,200
(1,300)
16,900
(2,800)
16,700
(4,300)
16,600
(5,700)
16,500
(7,100)
S/T
0.574
0.27
0.573
0.21
0.571
0.14
0.574
0.03
0.579
0
0.583
0
0.592
0
0.604
0
0.616
0
Latent Btuh
14,000
13,400
13,700
12,800
13,500
11,900
13,000
11,700
12,500
11,300
12,100
10,900
11,500
10,500
10,900
10,100
10,300
9,800
Lbs. H20/hr
.
13.2
12.6
12.9
12.1
12.7
11.2
12.3
11.0
11.8
10.7
11.4
10.3
10.8
9.9
10.3
9.5
9.7
9.2
Supply Air DB
55.5
68.5
55.8
70.6
56.1
72.5
56.4
74.7
56.8
76.7
57.2
78.7
57.8
80.7
58.4
82.7
59.0
84.6
Supply Air WB
54.7
58.6
55.0
59.6
55.1
60.6
55.6
61.6
55.9
62.6
56.3
63.6
56.8
64.5
57.3
65.4
57.9
66.3
Suction PSIG
4
130
125
131
127
131
129
133
131
134
133
135
135
137
136
138
137
139
139
Discharge PSIG
4
279
251
298
265
318
279
340
294
362
310
386
325
410
341
436
358
462
375
75/68
(70% RH)
Total Cooling Btuh
33,700
19,500
32,900
17,300
32,200
14,900
31,300
13,100
30,500
11,100
29,700
9,200
29,000
7,300
28,300
5,500
27,600
3,800
Sensible Btuh
17,600
4,200
17,100
2,600
16,800
1,200
16,300
(500)
15,900
(2,000)
15,700
(3,500)
15,500
(5,000)
15,400
(6,400)
15,300
(7,900)
S/T
0.522
0.215
0.520
0.150
0.522
0.081
0.521
0
0.521
0
0.529
0
0.534
0
0.544
0
0.554
0
Latent Btuh
16,100
15,300
15,800
14,700
15,400
13,700
15,000
13,600
14,600
13,100
14,000
12,700
13,500
12,300
12,900
11,900
12,300
11,700
Lbs. H20/hr
.
15.2
14.4
14.9
13.9
14.5
12.9
14.2
12.8
13.8
12.4
13.2
12.0
12.7
11.6
12.2
11.2
11.6
11.0
Supply Air DB
56.8
69.5
57.0
71.6
57.4
73.5
57.6
75.7
58.0
77.7
58.5
79.7
59.0
81.7
59.6
83.6
60.3
85.6
Supply Air WB
56.2
59.7
56.4
60.7
56.6
61.7
57.0
62.7
57.3
63.7
57.8
64.6
58.2
65.6
58.7
66.5
59.3
67.4
Suction PSIG
4
133
128
134
130
135
132
136
134
138
136
139
138
140
139
141
140
143
141
Discharge PSIG
4
281
253
300
268
321
282
342
297
365
312
388
328
412
344
438
361
464
378
80/68.3 (55% RH)
Total Cooling Btuh
34,100
17,200
33,300
15,000
32,600
12,600
31,700
10,800
30,900
8,800
30,100
6,800
29,400
5,000
28,700
3,200
28,000
1,400
Sensible Btuh
22,100
7,600
21,600
6,000
21,300
4,600
20,800
2,900
20,400
1,400
20,200
(100)
20,000
(1,600)
19,800
(3,100)
19,800
(4,500)
S/T
0.648
0.44
0.649
0.40
0.653
0.37
0.656
0.27
0.660
0.16
0.671
0
0.680
0
0.690
0
0.707
0
Latent Btuh
12,000
9,600
11,700
9,000
11,300
8,000
10,900
7,900
10,500
7,400
9,900
6,900
9,400
6,600
8,900
6,300
8,200
5,900
Lbs. H20/hr
.
11.3
9.1
11.0
8.5
10.7
7.5
10.3
7.5
9.9
7.0
9.3
6.5
8.9
6.2
8.4
5.9
7.7
5.6
Supply Air DB
57.5
70.0
57.8
72.1
58.1
74.1
58.4
76.2
58.8
78.2
59.3
80.2
59.8
82.2
60.4
84.2
61.0
86.2
Supply Air WB
56.5
60.9
56.7
61.9
56.9
62.9
57.3
63.9
57.7
64.9
58.1
65.9
58.5
66.8
59.0
67.7
59.6
68.6
Suction PSIG
4
135
129
136
131
137
133
138
135
140
137
141
138
142
140
144
141
145
142
Discharge PSIG
4
282
238
301
252
322
267
343
282
366
297
389
313
413
329
439
345
465
362
Q30H4D Cooling and Dehumidification Application Data