Manual 2100-742A
Page
42 of 54
Model
Rated ESP*
Maximum ESP*
Vent*
Rated CFM*
Balanced Climate
CFM*
Q24H4
0.10
0.6
825
825
600
Q30H4
0.10
0.6
900
900
650
Q36H4
0.15
0.6
1100
1125
825
* These units are equipped with a variable speed (ECM) indoor motor that automatically adjusts itself to maintain
approximately the same rate of indoor airflow in both heating and cooling, dry and wet coil conditions and at
both 230/208 or 460 volts.
TABLE 13
Indoor Blower Performance
These electric heaters are available in 230/208V units only.
These electric heaters are available in 480V units only.
Nominal
KW
At 240V
At 208V
At 480V
At 460V
KW
1-Ph
Amps
3-Ph
Amps BTUH
KW
1-Ph
Amps
3-Ph
Amps BTUH
KW
3-Ph
Amps BTUH
KW
3-Ph
Amps BTUH
5.0
5.0
20.8
17,065
3.75
18.0
12,799
6.0
6.0
14.4
20,478
4.50
12.5
15,359
6.0
7.2
20,478
5.52
6.9
18,840
9.0
9.0
21.7
30,717
6.75
18.7
23,038
9.0
10.8
30,717
8.28
10.4
28,260
10.0
10.0
41.7
34,130
7.50
36.1
25,598
15.0
15.0
62.5
36.1
51,195 11.25
54.1
31.2
38,396
15.0
18.0
51,195 13.80
17.3
47,099
TABLE 15
Electric Heat
TABLE 14
Maximum ESP of Operation
Electric Heat Only
Values shown are for units equipped with
standard 1" throwaway filter or 1" washable
filter.
Derate ESP by .15 for 2" pleated filters.
Model
Q24,30,36H4
Outlet
Top
Speed
Rated
-A0Z
-A05
-A10
-A15
.50
.50
.50
.50
-B0Z
-B06
-B09
-B15
.50
.50
.50
.50
-C0Z
-C06
-C09
-C15
.50
.50
.50
.50