background image

Installation and Operating Instructions

CO

2

 Room Sensor in the BAPI-Stat 3 Enclosure 

with Common Ground Configuration

Specifications subject to change without notice.

26141_ins_room_CO2

4 of 6

rev. 04/27/18

Wire Color

Ground

Black

Tip

White

Ring

Red

Table 1: C35 Wiring

Comm Jack Pin

Wire Color

1

Not Connected

2

Black

3

Red

4

Yellow

5

Green

6

Not Connected

Table 2: C11 Wiring

  

Optional Communications Jack Wiring

Fig. 5: 

Communication Jack Locations

C11

C35

C35 

Communication 

Jack

(Male jack 

shown for clarity)

C11 

Communication 

Jack

  

User Operation

The display indicates CO

2

 in PPM, temperature in °F or °C, 

%RH, temperature setpoint in degrees °F or °C and override 

using the BAPI Man icon.  The three triangle icons are used 

with the –ARW option to show CO

2

 levels.

The main display indicates the numeric value of the quantity 

being displayed.  The minor display indicates the engineering 

units of the value, such as PPM, °F, °C or %RH.

Temperature Setpoint Slidepot:

 Moving the slidepot enough 

to change the setpoint by one degree will display the setpoint 

on the main LCD display if equipped with display.  The setpoint 

display will hold for five seconds after moving the slide pot.

Override Button:

 When the override button is pressed on 

display units, the BAPI Man icon will display.  A dry resistance 

of less than 1 ohm appears from the override output (OVR) to 

the Ground terminal (GND).  Latching the Icon to show that 

the system is in override requires that a dry contact on your 

controller be used to connect terminal EXT to ground.

Optional CO

2

 Level Indication via Arrow or 3-Color LED

CO

2

 level indication is available via a black arrow on the display 

or a three-color LED on the logo plate with green for good, 

yellow for fair and red for poor.

  Optional Test and Balance Switch (SW1)

Sensor Type

Low Temp

High Temp

1000   RTD

1.02K (41.2°F)

1.15K (101.5°F)

3000   Thermistor

7.87K (39.8°F)

1.50K (106.8°F)

10K-2 Thermistor

30.1K (34.9°F)

4.75K (109.1°F)

10K-3 Thermistor

26.7K (35.9°F)

5.11K (108.4°F)

10K-3(11K) Thermistor

7.32K (43.7°F)

3.65K (105.2°F)

BAPI Man 

Icon

Fig. 6: 

CO

2

 Unit Indicators 

(Shown above with all 

optional indicators) 

Arrow 

Indicators 

& Legend

LED

Indicator 

& Legend

Note:

 Both 

indicators are 

not available 

together

“ON” Icon

Reviews: