Installation and Operating Instructions
CO
2
Room Sensor in the BAPI-Stat 3 Enclosure
with Common Ground Configuration
Specifications subject to change without notice.
26141_ins_room_CO2
4 of 6
rev. 04/27/18
Wire Color
Ground
Black
Tip
White
Ring
Red
Table 1: C35 Wiring
Comm Jack Pin
Wire Color
1
Not Connected
2
Black
3
Red
4
Yellow
5
Green
6
Not Connected
Table 2: C11 Wiring
Optional Communications Jack Wiring
Fig. 5:
Communication Jack Locations
C11
C35
C35
Communication
Jack
(Male jack
shown for clarity)
C11
Communication
Jack
User Operation
The display indicates CO
2
in PPM, temperature in °F or °C,
%RH, temperature setpoint in degrees °F or °C and override
using the BAPI Man icon. The three triangle icons are used
with the –ARW option to show CO
2
levels.
The main display indicates the numeric value of the quantity
being displayed. The minor display indicates the engineering
units of the value, such as PPM, °F, °C or %RH.
Temperature Setpoint Slidepot:
Moving the slidepot enough
to change the setpoint by one degree will display the setpoint
on the main LCD display if equipped with display. The setpoint
display will hold for five seconds after moving the slide pot.
Override Button:
When the override button is pressed on
display units, the BAPI Man icon will display. A dry resistance
of less than 1 ohm appears from the override output (OVR) to
the Ground terminal (GND). Latching the Icon to show that
the system is in override requires that a dry contact on your
controller be used to connect terminal EXT to ground.
Optional CO
2
Level Indication via Arrow or 3-Color LED
CO
2
level indication is available via a black arrow on the display
or a three-color LED on the logo plate with green for good,
yellow for fair and red for poor.
Optional Test and Balance Switch (SW1)
Sensor Type
Low Temp
High Temp
1000 RTD
1.02K (41.2°F)
1.15K (101.5°F)
3000 Thermistor
7.87K (39.8°F)
1.50K (106.8°F)
10K-2 Thermistor
30.1K (34.9°F)
4.75K (109.1°F)
10K-3 Thermistor
26.7K (35.9°F)
5.11K (108.4°F)
10K-3(11K) Thermistor
7.32K (43.7°F)
3.65K (105.2°F)
BAPI Man
Icon
Fig. 6:
CO
2
Unit Indicators
(Shown above with all
optional indicators)
Arrow
Indicators
& Legend
LED
Indicator
& Legend
Note:
Both
indicators are
not available
together
“ON” Icon