background image

Installation and Operating Instructions

CO

2

 Room Sensor in the BAPI-Stat 3 Enclosure 

with Common Ground Configuration

Specifications subject to change without notice.

26141_ins_room_CO2

6 of 6

rev. 04/27/18

The CO

2

 outputs may be field configured for 0 

to 5 VDC or 0 to 10 VDC outputs at any time.  

Set the jumpers on J16 as shown in Figs 12 

and 13.  
The humidity outputs may be field configured 

for 0 to 5, 1 to 5, 0 to 10 or 2 to 10 VDC outputs 

at any time.  Set the jumpers on J16 as shown 

in Figs 14 and 15. 

Note:

 The jumpers on the pins not being 

described are omitted for clarity on the figures 

at right.

Output Selection

Diagnostics

Possible Problems: 

Possible Solutions:

General troubleshooting   Determine that the input is set up correctly in the controller's and building automation software.
 

 Check wiring at the sensor and controller for proper connections. If there is corrosion, clean off 

the corrosion, re-strip the interconnecting wire and reapply the connection.  In extreme cases, 

replace the controller, interconnecting wire and/or sensor.

 

 Label the terminals that the interconnecting wires are connected to at the sensor end and the 

controller end.  Disconnect the interconnecting wires from the controller and the sensor.  With 

the interconnecting wires separated at both ends measure the resistance from wire-to-wire with 

a multimeter.  The meter should read greater than 10 Meg-ohms, open or OL depending on the 

meter you have.  Short the interconnecting wires together at one end.  Go to the other end and 

measure the resistance from wire-to-wire with a multimeter.  The meter should read less than 10 

ohms (22 gauge or larger, 250 feet or less).  If either test fails, replace the wire.

 

 Check power supply/controller voltage supply for proper voltage (see specifications)

Incorrect CO

2

 

 Wait 15 minutes after a power interruption.

  

Check all software parameters

  

Determine if the sensor is exposed to an external environment different from the room (conduit draft)

 

If the sensor is reading consistently high, make sure that the power supply to the unit can provide 

240mA. A low power situation will cause high CO

2

 readings.

 

Note: If the CO

2

 sensor has consistently given high PPM readings for over 5 days, it will take up 

to 14 days for the readings to return to normal.

Incorrect Humidity 

 Check all software parameters

  

If available, check the sensor against a calibrated instrument such as a hygrometer

  

Determine if the sensor is exposed to an external environment different from the room (conduit draft)

Incorrect Temperature    Check the wires at the sensor and controller for proper connections.
 

Check the Temperature Output of the unit. Disconnect the temperature sensor’s wire (Terminals 

TP+ & TP-) and measure the temperature sensor’s resistance across the sensor output pins with 

an ohmmeter.  Put the ohmmeter’s black lead on Terminal TP- and the red lead on Terminal TP+.  

Compare the temperature sensor’s resistance to the appropriate temperature sensor table on the 

BAPI website. (Go to www.bapihvac.com; click on “Resource Library” and “Sensor Specs”, then 

click on the sensor type you have.)  If the measured resistance differs from the temperature table 

by more than 5%, call BAPI technical support.  

  

Determine if the sensor is exposed to an external environment different from the room (conduit or 

wall cavity draft)

Fig. 14: 

CO

2

 Output 

0 to 5 VDC

Fig. 15: 

CO

2

 

Output 0 to 

10 VDC

Fig. 16: %

RH 

Output 0 to 5 

or 1 to 5 VDC

Fig. 17: %

RH 

Output 0 to 10 

or 2 to 10 VDC

Reviews: