Installation and Operating Instructions

CO

2

 Room Sensor in the BAPI-Stat 3 Enclosure 

with Common Ground Configuration

Specifications subject to change without notice.

26141_ins_room_CO2

3 of 6

rev. 04/27/18

Terminal  Function

OVR

 ............. Override Output (Dry Contact Switch).  When 

Override switch is pushed this terminal is connected 

to the GND terminal.

SET

.............. Setpoint output.  Referenced to GND terminal.

EXT

.............. External occupied LCD indicator is activated by logic 

LOW or ground at this terminal, referenced to the 

GND terminal.

TP+ & TP-

 ... Temperature Sensor Output (Resistive Output). 

When a jumper is on J16, TP- is connected to the 

GND terminal. When the jumper is off of J16, the 

temperature sensor is floating.

 

(Semiconductor TP+ = +, TP- = -)

CO

/ VOC

 .... Voltage output CO2 Signal (0 to 2,000 ppm) 

referenced to the GND terminal.

RH

 ............... Voltage output Humidity Signal  referenced to the 

GND terminal.

GND

 ............. To controller Ground [GND or Common]

PWR

 ............ Power, referenced to GND

 

9 to 35 VDC @ 240mA

 

(9 to 24 VDC recommended) for 0 to 5 VDC Outputs 

 

15 to 35 VDC @ 240mA

 

(15 to 24 VDC recommended) for 0 to 10 VDC Outputs 

Termination

Note: Unit is not ready for 

operation until the 10 minute 

start-up time has elapsed.

Fig. 3: 

Circuit Board

Note: For proper operation, the 

jumper on PRG connector of J19 

must be connected by only one leg.

BAPI recommends using twisted pair of at least 22AWG and sealant filled connectors for all wire connections. Larger 

gauge wire may be required for long runs. All wiring must comply with the National Electric Code (NEC) and local codes. 

Do NOT run this device’s wiring in the same conduit as AC power wiring.  BAPI’s tests show fluctuating and inaccurate 

signals are possible when AC power wiring is in the same conduit as the signal lines.  If you are experiencing any of these 

difficulties, please contact your BAPI representative

.

BAPI recommends wiring the product with power disconnected. Proper supply voltage, polarity and wiring 

connections are important to a successful installation.  Not observing these recommendations may damage the 

product and void the warranty.

VC350A or VC350A-EZ 

Voltage Converter

(VC350A shown below)

CO

2

 Sensor

POWERING WITH A BAPI VC350A 

VOLTAGE CONVERTER

The CO

2

 unit requires 240mA of current 

to operate correctly. If this is more 

current than can be provided by the 

controller power output, then the unit 

can be powered by a BAPI VC350A or 

VC350A-EZ Voltage Converter.

Fig. 4: 

Powering with 

a BAPI VC350A 