CO

2

 Duct and Rough Service Sensor

 

Termination

BAPI recommends using twisted pair of at least 22AWG and sealant filled connectors for all wire connections. Larger 

gauge wire may be required for long runs. All wiring must comply with the National Electric Code (NEC) and local 

codes. Do NOT run this device’s wiring in the same conduit as AC power wiring.  BAPI’s tests show that fluctuating 

and inaccurate signal levels are possible when AC power wiring is present in the same conduit as the signal lines.

The CO

2

 outputs may 

be field configured for 

0 to 5 VDC or 0 to 10 

VDC outputs at any 

time.  Set the jumpers 

on J3 as shown in 

Figures 7 and 8.  

Fig. 7:

 J3 set for 0 

to 10 VDC output

Fig. 8:

 J3 set for 0 

to 5 VDC output

Terminal 

Function

PWR

 ............... 12 to 24 VDC, 240mA

 

18 to 24 VAC, 12 VA Peak

GND

 ................ To controller Ground [GND or Common] 

OUT

 ................ Voltage Output, CO

2

 Signal

 

0 to 5 or 0 to 10 VDC, Referenced to GND

Note: Unit is not ready for operation until the 10 minute start-up time has elapsed.

Note: For proper operation, the 

jumper on calibration connector J2 

must be connected to one leg.

Fig. 6:

 Circuit Board

BAPI recommends wiring the product with power disconnected.  Proper supply voltage, polarity, and 

wiring connections are important to a successful installation.  Not observing these recommendations may 

damage the product and will void the warranty.

VC350A or VC350A-EZ 

Voltage Converter

(VC350A shown below)

CO

2

 Sensor

POWERING WITH A BAPI VC350A 

VOLTAGE CONVERTER

The CO

2

 unit requires 240mA of current 

to operate correctly. If this is more 

current than can be provided by the 

controller power output, then the unit 

can be powered by a BAPI VC350A or 

VC350A-EZ Voltage Converter.

Fig. 9: 

Powering with 

a BAPI VC350A 