background image

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

Specifications subject to change without notice.

1 of 4

Installation & Operating Instructions

rev. 08/21/17

28173_ins_CO2_Duct

CO

2

 Duct and Rough Service Sensor

The BAPI CO

2

 Duct Sensor is an accurate and reliable way 

of incorporating demand controlled ventilation. It measures 

CO

2

 in ranges of 0 to 2,000, 0 to 5,000, 0 to 10,000 and 0 

to 50,000 ppm with a field selectable output of 0 to 5 or 0 to 

10 VDC.
The Single Beam (ACD) unit has been optimized for 

periodically unoccupied areas and features automatic 

background calibration over a long time period to reduce 

drift. The Dual Channel (DCD) “24/7” unit has been 

optimized for continuously occupied areas and features a 

3-point calibration process. 

Barometric pressure changes from altitude or weather 

can affect CO

2

 sensors, even putting them outside of their 

specified accuracy. The BAPI unit has a built-in Barometric 

pressure sensor that continuously compensates the output 

for accurate readings despite the weather or altitude.
The Duct unit samples duct air using an aspiration tube. 

The Rough Service unit features a ventilated BAPI-Box and 

is ideal for areas such as outdoor air plenums, equipment 

rooms, attics, green houses and warehouses. Optional 

indication of the CO

2

 level as “Good, Fair or Poor” is 

available as a 3-color LED for 0 to 2,000 ppm range units. 

 Identification and Overview

Fig. 1: 

Duct CO

2

 Sensor

Three-color 

LED

Fig. 2: 

Rough Service CO

2

 Sensor

 Specifications

Power:

 

12 to 24 VDC, 240mA

18 to 24 VAC, 12 VA Peak

CO

2

 Sensing Elements:

Single Beam Non-Dispersive Infrared (NDIR)

or Dual Channel NDIR for “24/7” Model

Selectable Output:

0 to 5 VDC or 0 to 10 VDC

Termination: 

3 Terminals, 16 to 22 AWG

Wiring: 

2 Pair

Operating Environment:

32 to 122°F (0 to 50°C)

0 to 95%RH non-condensing

Enclosure Material:

Polycarbonate, UL94 V-O

CO

2

 Detection Range:

 

0 to 2,000, 0 to 5,000, 0 to 10,000 and 0 to 50,000 ppm 

Start-Up Time:

 10 Minutes

Response Time:

Less Than 5 Minutes (after Start-Up Time)

CO

2

 Accuracy:

 

(Automatic Background Calib. Single Channel Model)

400 to 1,250 ppm: ±30ppm or 3% of reading, 

 

 

      whichever is greater

1,250 to 2,000 ppm: ±5% of r 30ppm

CO

2

 Accuracy:

 

(“24/7” Dual Channel Model)

75ppm or 10% of reading (whichever is greater)

CO

2

 Drift Stability (DCD “24/7” Units):

<5% of full scale over life of product.

Optional 3-Color LED 

(0 to 2,000 ppm range only):

Good, Green < 1,000 PPM CO

2

Fair, Orange = 1,000 to 1,500 PPM CO

2

Poor, Red > 1,500 PPM CO

2

 

Certifications:

 RoHS

Warranty Period:

 

5 Years from manufacture date