background image

Installation & Operating Instructions

BAPI-Stat 4 Sensor, w/Display, Button Setpoint, Fan or System Mode Control

BA/BS4M  Temperature Sensor

Specifications subject to change without notice.

rev. 01/18/16

25188_ins_BS4M

1 of 8

Product Identification and Overview

Fig. 1:

  BAPI-Stat 4M 

with optional Setpoint, 

Override, Fan and Mode 

Control.

The BAPI-Stat 4M room temperature sensor 

features a large format LCD and pushbutton 

setpoint adjustment. Additonal options include 

pushbutton override, fan speed and mode 

adjustments. 
The setpoint is available as a resistance or 

voltage output.  The override is a momentary 

closure signal that can be configured in parallel 

with the sensor or setpoint, or as a separate 

momentary or latching contact output. A 3.5mm 

(1/8”), RJ11 or RJ22 communication jack can 

also be mounted in the unit’s base to provide 

direct access to the network.

Mounting

JUNCTION BOX

1.   Pull the wire through the wall and out of the junction box, leaving about 6 inches free.
2.   Pull the wire through the hole in the base plate.
3.   Secure the base to the box using the #6-32 x 1/2 inch mounting screw provided.
4.   Terminate the unit according to the guidelines in the 

Termination 

section.

5.   Attach Cover by latching it to the top of the base, rotating the cover down 

and snapping it into place.

6.   Secure the cover by backing out the lock-down screws using a 1/16” Allen 

wrench until they are flush with the bottom of the cover.

DRYWALL MOUNTING

1.   Place the base plate against the wall where you want to mount the sensor.
2.   Using a pencil, mark out the two mounting holes and the area where the 

wires will come through the wall.

3.   Drill two 3/16” holes in the center of each marked mounting hole. Insert a 

drywall anchor into each hole.

4.  Drill one 1/2” hole in the middle of the marked wiring area.
5.   Pull the wire through the wall and out the 1/2” hole, leaving about 6” free.
6.   Pull the wire through the hole in the base plate.
7.   Secure the base to the drywall anchors using the #6 x 1 inch mounting screws provided.
8.   Terminate the unit according to the guidelines in the 

Termination 

section.

9.   Attach Cover by latching it to the top of the base, rotating the cover down and snapping it into place. Secure the cover 

by backing out the lock-down screws using a 1/16” Allen wrench until they are flush with the bottom of the cover.

NOTE: 

In a wall-mount application, the mixing of room air and air from within the wall cavity can lead to erroneous 

readings, condensation, and premature failure of the sensor. To prevent this condition, plug the conduit hole with 

insulation in the junction box.

Fig. 5:

 Mounting hardware is provided 

for both J-Box and drywall installation 

(J-Box installation shown)

Fig. 2:

 2 Button Unit

Fig. 3:

 3 Button Unit

Note: 

 BAPI-Stat 4M shown with 

five buttons. Two, three or five 

buttons may be present. See “Front 

Panel & Control” section.

Fig. 4:

 5 Button Unit

Summary of Contents for BAPI-Stat 4M

Page 1: ... lock down screws using a 1 16 Allen wrench until they are flush with the bottom of the cover DRYWALL MOUNTING 1 Place the base plate against the wall where you want to mount the sensor 2 Using a pencil mark out the two mounting holes and the area where the wires will come through the wall 3 Drill two 3 16 holes in the center of each marked mounting hole Insert a drywall anchor into each hole 4 Dr...

Page 2: ...der voltage SET1 is SET2 is If the unit is a common ground configuration CG see Grounding Note below OVR1 OVR2 Override output Dry contact The contact can be ordered as a momentary shunt across the sensor N or as a momentary shunt across the setpoint P or as a separate momentary contact J or as a separate latching contact L If the unit is a common ground configuration CG see Grounding Note below R...

Page 3: ...hermistor 7 32KΩ 43 7 F 3 65Ω 105 2 F Test and Balance Switch S1 NORM Sensor operates normally LOW Sets the sensor value low HIGH Sets the sensor value high On the Test and Balance Switch the NORM position allows the real sensor to be monitored The HIGH position forces the output to a very hot reading and the LOW position forces a very cold reading see Table below Optional Fan Speed and System Mod...

Page 4: ...shows a fully featured sensor NUMERICAL DISPLAY The default display shows current temperature When the up down buttons are pushed then the display will show and adjust the current setpoint and hold the display for 3 to 4 seconds The unit can also be set up to display setpoint only or for setpoint lockout See Optional Technicians Adjustments section BAPI MAN ICON The BAPI Man Icon shows the status ...

Page 5: ... Override S5 Up Adjust and S6 Down Adjust See Fig 14 After adjustment place the board back into the cover and insert the center mounting screw Do not over tighten MODE MENUS The setup mode consists of menu pages P1 through P6 for configuring the sensor The following adjustments can be done with the program jumper J16 installed P1 Temperature offset Adjust Up or Down 5 to 5 in 0 1 increments P2 Set...

Page 6: ...d when there is a ground signal to the EXT OVR terminal of the unit For Option 9 the BAPI Man Icon stays filled or solid when the relay is closed and hollow when the relay is open For Option 10 the BAPI Man Icon is disabled but the ON or OFF Dot on the display is controlled by the EXT OVR terminal When there is a ground signal at the EXT OVR terminal the ON dot is lit Otherwise the OFF and hollow ...

Page 7: ...ly Check that the resistance across the override output is less than 5Ω when the override is pushed Fan Mode not correct Make sure that the fan mode output is correct Remove the fan mode output wire and check the output for the correct resistance See the product label for your specific range and compare it to the resistance chart at the bottom of page 3 Don t forget to reconnect the wire When the ...

Page 8: ...uts Dry contact 24V 1mA Occupied EXT OVR Grounded Unoccupied EXT OVR Open to Ground Display LCD Overall 2 W x 1 1 H Temp Setpoint Occupied LCD 3 5 Digits 0 6 H Occ Unocc BAPI Man Icon Filled in man is occupied Display Limits 1 0º 0 5 and 0 1 F C increments Setpoints in 1º steps Range 40 to 185 F 40 to 85 C Display Setup Temp Setpoint Temp only or Setpoint only ºF or ºC Optional Fan Speed System Mo...

Reviews: