24595_ins_BAPI_4_room_humidity

Installation & Operating Instructions

BAPI-Stat 4 Room Humidity Sensor (BA/

B4

-H200 Series)

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

rev. 12/15/17

Specifications subject to change without notice.

4 of 5

Optional Communications Jack Wiring

Male Jack shown for clarity

Fig 7:

 C35L Communications Jack

C35L Front

C35L Back

C11L/C22L Front

C11L/C22L Back

Fig 8:

 C11L/C22L Communications Jack

The display indicates temperature in degrees Fahrenheit or Celsius, relative humidity in %RH, temperature setpoint in 

degrees Fahrenheit or Celsius.  Temperatures and relative humidity can be displayed in a rotating manner, see the Optional 

Technician Adjustments section.  The BAPI Man icon indicates that the override button has been pushed.

Temperature:

 When temperature is displayed, the INSIDE icon as well as the appropriate units icon are illuminated.  

Relative Humidity:

 When relative humidity is displayed, the INSIDE icon as well as %RH are illuminated.

Setpoint Slidepot: 

When the temperature setpoint is active (see technician adjustments), moving the slidepot enough to 

change the setpoint by one degree will display the setpoint on display units. 

Override Button: 

When the override button is pressed, the Override or BAPI-Man Icon 

 will display on display units.  A 

dry resistance of less than 15 ohms appears across the override output (OVR1 to OVR2).  Latching the Icon (to make it re-

main lit on the display when the unit is in override) requires that a digital output on your controller be used to connect terminal 

EXT-OVR to power supply ground.

Signifies Space Temperature 

or Humidity Being Displayed

Signifies Temperature Setpoint 

Display or Setpoint Adjustment

Display Units

0.6 inch Display

BAPI Man Icon

Fig 9:

 Optional Display

User Operation

Comm Jack Pin

Wire Color

1

Not Connected

2

Black

3

Red

4

Yellow

5

Green

6

Not Connected

C11L/C22L Wiring

Summary of Contents for BA-H200 Series

Page 1: ... by backing out the lock down screws using a 1 16 Allen wrench until they are flush with the bottom of the cover DRYWALL MOUNTING 1 Place the base plate against the wall where you want to mount the sensor 2 Using a pencil mark out the two mounting holes and the area where the wires will come through the wall 3 Drill two 3 16 holes in the center of each marked mounting hole Insert a drywall anchor ...

Page 2: ...dependent 4 to 20 mA Output Unit Termination Terminal Function OVR1 OVR2 Override Output Dry Contact Switch If unit is a common CG model see Note below SET1 SET2 Setpoint Output If unit is a common CG model see Note below SEN1 SEN2 Sensor Output Resistive Output Semiconductor SEN1 SEN2 If unit is a common CG model see Note below EXT OVR Allows remote control of the LCD indicator for occupancy and ...

Page 3: ... in the 4 to 20mA position The 0 to 10 VDC jumper is used for the 2 to 10 VDC signal if an H212 or H312 was ordered Parameter Page Designator Adjustment Temperature Offset P0 5 in 0 1 increments A high accuracy reference is recommended Humidity Offset P1 5 in 0 1 increments or R34 When R34 is selected humidity offset is set by turning potentiometer R34 See Fig 5 below Display Units P2 F or C Displ...

Page 4: ...n temperature is displayed the INSIDE icon as well as the appropriate units icon are illuminated Relative Humidity When relative humidity is displayed the INSIDE icon as well as RH are illuminated Setpoint Slidepot When the temperature setpoint is active see technician adjustments moving the slidepot enough to change the setpoint by one degree will display the setpoint on display units Override Bu...

Page 5: ...ferent from the room conduit draft Incorrect Temperature Determine that the temperature sensor s wires are connected to the correct controller input terminals and check the wires at the sensor and controller for proper connections Determine if the sensor is exposed to an external environment different from the room conduit draft Measure the physical temperature at the sensor s location using an ac...

Reviews: