background image

24595_ins_BAPI_4_room_humidity

Installation & Operating Instructions

BAPI-Stat 4 Room Humidity Sensor (BA/

B4

-H200 Series)

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

rev. 12/15/17

Specifications subject to change without notice.

Diagnostics

5 of 5

Possible Problems: 

Possible Solutions:

General troubleshooting  • Determine that the input is set up correctly in the controller's and building automation 

software.

 

 • Check wiring at the sensor and controller for proper connections.

 

 • Check for corrosion at either the controller or the sensor. Clean off the corrosion, re-strip the 

interconnecting wire and reapply the connection.  In extreme cases, replace the controller, 

interconnecting wire and/or sensor.

 

• Label the terminals that the interconnecting wires are connected to at the sensor end and the 

controller end.  Disconnect the interconnecting wires from the controller and the sensor.  With 

the interconnecting wires separated at both ends measure the resistance from wire-to-wire 

with a multimeter.  The meter should read greater than 10 Meg-ohms, open or OL depending 

on the meter you have.  Short the interconnecting wires together at one end.  Go to the other 

end and measure the resistance from wire-to-wire with a multimeter.  The meter should read 

less than 10 ohms (22 gauge or larger, 250 feet or less).  If either test fails, replace the wire.

Incorrect Humidity 

• Check power supply/controller voltage supply

 

 • Disconnect sensor and check power wires for proper voltage (see specifications page)

 

 • Check all software parameters

 

• If available, check the sensor against a calibrated instrument such as a hygrometer

  

• Determine if the sensor is exposed to an external environment different from the room 

(conduit draft)

Incorrect Temperature  

• Determine that the temperature sensor's wires are connected to the correct controller input 

terminals, and check the wires at the sensor and controller for proper connections.

 

• Determine if the sensor is exposed to an external environment different from the room 

(conduit draft)

 

• Measure the physical temperature at the sensor's location using an accurate temperature 

standard. Disconnect the temperature sensor's wires (Terminals SEN1 & SEN2) and 

measure the temperature sensor's resistance across the output pins. Put the ohmmeter black 

lead on SEN2 and the red lead on SEN1. Compare the temperature sensor's resistance to 

the appropriate Sensor Resistance Table on the BAPI website (See below).  If the measured 

resistance varies from the table by more than 5%, call BAPI technical support.

 

How to Find The Temperature Sensor Resistance Table

Find BAPI's web site at www.bapihvac.com; click on “Resource Library” and “Sensor Specs” 

and then click on the sensor type you have.

Specifications

Power: 

15 to 35 VDC for 4 to 20 mA Output

10 to 40 VDC or 12 to 24 VAC for 0 to 5 VDC Output

15 to 40 VDC or 15 to 28 VAC for 0 to 10 or 2 to 10 VDC Output

(AC Power requires a separate pair of shielded wires)

Power Consumption:

20 mA max. for 4 to 20 mA Output

4 mA max. for 0 to 5 VDC and 0 to 10 or 2 to 10 VDC Output

0.1 VA max. for 0 to 5 VDC and 0 to 10 or 2 to 10 VDC Output

Sensing Elements:

Temperature - Thermistor, RTD or Semiconductor

±0.3°C (±0.54°F) @ 20 to 40°C (68 to 104°F)
Humidity - Capacitive Polymer

±2%RH @ 25°C (77°F), 20 to 80%RH

Wiring:

 2 to 6 pair of 16 to 22 AWG

Field Calibration: 

Potentiometer (R34), ±5% in 0.1% 

increments

 

(Units are factory calibrated)

Terminals:

 Cage clamp, 16 to 22 AWG

Mounting: 

2”x4” J-box or drywall - screws provided

Environmental Operation Range:

Temperature: 32 to 122 °F (0 to 50 °C)

Humidity: 0 to 95%, non-condensing

Material & Rating:

 ABS Plastic, UL 94, V-0

Agency: 

RoHS, CE*

*Units with passive Thermistors 20KΩ and smaller are 

CE compliant.

Summary of Contents for BA-H200 Series

Page 1: ... by backing out the lock down screws using a 1 16 Allen wrench until they are flush with the bottom of the cover DRYWALL MOUNTING 1 Place the base plate against the wall where you want to mount the sensor 2 Using a pencil mark out the two mounting holes and the area where the wires will come through the wall 3 Drill two 3 16 holes in the center of each marked mounting hole Insert a drywall anchor ...

Page 2: ...dependent 4 to 20 mA Output Unit Termination Terminal Function OVR1 OVR2 Override Output Dry Contact Switch If unit is a common CG model see Note below SET1 SET2 Setpoint Output If unit is a common CG model see Note below SEN1 SEN2 Sensor Output Resistive Output Semiconductor SEN1 SEN2 If unit is a common CG model see Note below EXT OVR Allows remote control of the LCD indicator for occupancy and ...

Page 3: ... in the 4 to 20mA position The 0 to 10 VDC jumper is used for the 2 to 10 VDC signal if an H212 or H312 was ordered Parameter Page Designator Adjustment Temperature Offset P0 5 in 0 1 increments A high accuracy reference is recommended Humidity Offset P1 5 in 0 1 increments or R34 When R34 is selected humidity offset is set by turning potentiometer R34 See Fig 5 below Display Units P2 F or C Displ...

Page 4: ...n temperature is displayed the INSIDE icon as well as the appropriate units icon are illuminated Relative Humidity When relative humidity is displayed the INSIDE icon as well as RH are illuminated Setpoint Slidepot When the temperature setpoint is active see technician adjustments moving the slidepot enough to change the setpoint by one degree will display the setpoint on display units Override Bu...

Page 5: ...ferent from the room conduit draft Incorrect Temperature Determine that the temperature sensor s wires are connected to the correct controller input terminals and check the wires at the sensor and controller for proper connections Determine if the sensor is exposed to an external environment different from the room conduit draft Measure the physical temperature at the sensor s location using an ac...

Reviews: