900MHz WAM Connect

The BAPI gateway can be backed up and restored 

locally. This allows you to reset the gateway in the 

rare instance that it would be locked up. It also allows 

you to copy the configuration to a new gateway if you 

chose to replace a gateway, eliminating the need to 

perform a network setup procedure on the gateway. 

BACKUP - LOCAL

1.  Create a folder on your computer or server to 

store and retrieve the backup content. 

2.  Go to the center “Backup” tab and click the “Local” 

icon and then click the “Backup” button (Fig 17). 

This will open the “Select Backup Folder” screen 

(Fig 18). 

3.   Select the local folder that you created in Step #1 

and click “Open” to save the backup to the folder. 

You will receive a “Backup Successful” message 

as shown in Fig 19. 

RESTORE - LOCAL

1.  Go to the “Backup” tab on the WAM Design 

Configuration Screen of the gateway that you 

would like to restore (or the new gateway if 

replacing the gateway) and click the “Restore” 

button. 

2.  Select the backup folder on your local computer or 

network from in the “Select Folder” Screen (Fig 20) 

and click “Open”. You will receive a “Restore 

Successful” confirmation screen (Fig 21) and also a 

request to reboot the system. Click “yes”.

Backup or Restore the Gateway

Fig. 17: 

Backup Tab on the Design Application 

Configuration Screen

Fig. 18: 

Select Backup Folder 

Screen.

Fig. 20: 

Select Restore Folder 

Screen.

Fig. 21: 

Restore 

Successful Message.

Fig. 19: 

Backup 

Successful Message.

Processor:

 AM3358 1GHz ARM® Cortex-A8 Processor 

On-board Flash:

 4GB Rated 

Voltage:

 12 to 42 VDC, 20 to 30 VAC 

Rated Power:

 12 Watt 

RAM:

 1 GB Cache 256KB Power over Ethernet (PoE) Power Requirements 3 watts @ 48 volts

Specifications for the 900MHz WAM Connect

Summary of Contents for 900 MHz WAM Connect

Page 1: ...900 MHz WAM Connect Wireless Gateway Installation and User Guide...

Page 2: ...cations subject to change without notice rev 02 09 21 39021_RCV_900_BACnet_2020 2 of 12 900MHz WAM Connect Table of Contents Mounting and Termination 3 Overview 4 Customer Provided Equipment and Mater...

Page 3: ...tenna connection Hold the gateway up to the plate and secure by twisting 1 4 turn clockwise POWER OPTIONS Direct 24VAC VDC Power Supply Included Power Over Ethernet PoE on board device LED INDICATORS...

Page 4: ...rarily place the gateway and sensors in their desired locations Material Attenuation Loss Brick 3 5 89 mm 3 5 dB Brick 7 178 mm 5 dB Brick 10 5 276 mm 7 dB Concrete 4 102 mm 12 dB Concrete 8 204 mm 23...

Page 5: ...the pull down box of the initial screen Fig 3 If it does not click the red retry arrows to the right of the box The WAM Link dongle should automatically identify itself to WAM Design software 3 Run th...

Page 6: ...stable Firmware Current Firmware Version Power Level Adjust the dBm level of the gateway radio Channel The gateway picks the channels to use There is no need to adjust this Unit Set the unit of measur...

Page 7: ...tion 6 Configure the WAM Tab Configure the options on the WAM Tab as needed Off Turns off the MQTT output WAM Sends the MQTT output to the BAPI WAM System or your own MQTT Broker Local Sends the infor...

Page 8: ...andoff of sensors to the gateway Note that all the sensors have been removed from the right column and are now in the center column These sensors are now handed off or assigned to the gateway that is...

Page 9: ...d them at least 10 apart the system will not recognise them For example if you assign BACnet IDs for three sensors as of 6000 6001 and 6002 the second two sensors will not save on the system because t...

Page 10: ...mple of what the BACnet Objects will look like from the BAPI Gateway using YABE Yet Another BACnet Explorer Notice the Object Instance ID changes based on the type of value being transmitted Fig 13 BA...

Page 11: ...nsor issues Suggestion the Heartbeat should be set to 3 times the transmit interval value to prevent a fault on one or two missed transmissions BACnet Information continued Fig 14 BACnet information f...

Page 12: ...3 Select the local folder that you created in Step 1 and click Open to save the backup to the folder You will receive a Backup Successful message as shown in Fig 19 RESTORE LOCAL 1 Go to the Backup t...

Reviews: