Installation & Operating Instructions

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

Specifications subject to change without notice.

rev. 02/09/21

39021_RCV_900_BACnet_2020

10 of 12

900MHz WAM Connect

BACnet Information

BAPI BACnet Vendor ID:

 

1069

BACnet Object Instance

Fig 13 is an example of what the BACnet Objects 

will look like from the BAPI Gateway using YABE 

(Yet Another BACnet Explorer).  Notice the Object 

Instance ID changes based on the type of value being 

transmitted.

Fig. 13: 

BACnet Object Instance info using hierarchical 

topology

Continued on next page...

Fig. 12: 

FDR Tab on the Design Application Configuration Screen

Foreign Device Registry (FDR) Information

Fig 12 shows the settings for the 

BACnet FDR (Foreign Device 

Registry) tab. If more information 

is needed for your network FDR 

settings, please discuss it with 

the network administrator for the 

BACnet network in your facility. 

Summary of Contents for 900 MHz WAM Connect

Page 1: ...900 MHz WAM Connect Wireless Gateway Installation and User Guide...

Page 2: ...cations subject to change without notice rev 02 09 21 39021_RCV_900_BACnet_2020 2 of 12 900MHz WAM Connect Table of Contents Mounting and Termination 3 Overview 4 Customer Provided Equipment and Mater...

Page 3: ...tenna connection Hold the gateway up to the plate and secure by twisting 1 4 turn clockwise POWER OPTIONS Direct 24VAC VDC Power Supply Included Power Over Ethernet PoE on board device LED INDICATORS...

Page 4: ...rarily place the gateway and sensors in their desired locations Material Attenuation Loss Brick 3 5 89 mm 3 5 dB Brick 7 178 mm 5 dB Brick 10 5 276 mm 7 dB Concrete 4 102 mm 12 dB Concrete 8 204 mm 23...

Page 5: ...the pull down box of the initial screen Fig 3 If it does not click the red retry arrows to the right of the box The WAM Link dongle should automatically identify itself to WAM Design software 3 Run th...

Page 6: ...stable Firmware Current Firmware Version Power Level Adjust the dBm level of the gateway radio Channel The gateway picks the channels to use There is no need to adjust this Unit Set the unit of measur...

Page 7: ...tion 6 Configure the WAM Tab Configure the options on the WAM Tab as needed Off Turns off the MQTT output WAM Sends the MQTT output to the BAPI WAM System or your own MQTT Broker Local Sends the infor...

Page 8: ...andoff of sensors to the gateway Note that all the sensors have been removed from the right column and are now in the center column These sensors are now handed off or assigned to the gateway that is...

Page 9: ...d them at least 10 apart the system will not recognise them For example if you assign BACnet IDs for three sensors as of 6000 6001 and 6002 the second two sensors will not save on the system because t...

Page 10: ...mple of what the BACnet Objects will look like from the BAPI Gateway using YABE Yet Another BACnet Explorer Notice the Object Instance ID changes based on the type of value being transmitted Fig 13 BA...

Page 11: ...nsor issues Suggestion the Heartbeat should be set to 3 times the transmit interval value to prevent a fault on one or two missed transmissions BACnet Information continued Fig 14 BACnet information f...

Page 12: ...3 Select the local folder that you created in Step 1 and click Open to save the backup to the folder You will receive a Backup Successful message as shown in Fig 19 RESTORE LOCAL 1 Go to the Backup t...