DIP Switch Settings

Switches

Device Settings

1

2

Rotary dial address mode

OFF*

Extended address mode

ON

Analog Configuration

OFF*

Discrete Configuration

ON

* Default configuration
Address Mode
The SureCross wireless devices may use one of two types of addressing modes: rotary dial addressing or extended addressing. In
rotary dial address mode, the left rotary dial establishes the network ID and the right rotary dial sets the device ID. The wireless network
is restricted to a maximum of 16 devices.
Extended address mode uses a security code to "bind" Nodes to a specific Gateway. Bound Nodes can only send and receive informa-
tion from the Gateway to which they are bound. In extended address mode, wireless networks may contain up to 48 radio devices. For
more information on extended address mode, refer to the SureCross

 Wireless I/O Network product manual.

The device ships in rotary dial address mode by default, with the DIP switch in the OFF position. To use extended address mode, change
the DIP switch to the ON position.
Analog or Discrete Configuration
Select between an analog configuration or a discrete configuration using the DIP switch specified in the table. The default switch settings
for this device are all in the OFF position.

Analog Configuration - Switch 2 OFF (10V Boost Models)

For analog configuration, DIP switch 2 is in the OFF position (factory default). Analog configuration has analog IN 1 linked to switch
power 1 (SP1) and is programmable using switches four through eight. Sample and report rates for analog input 2 are listed in the specifi-
cations. Discrete inputs 1 and 2 are also active in this configuration and the input types are defined using switch 3.

Analog Configuration, Switch 2 OFF

DIP Switches

Descriptions

3

4

5

6

7

8

Discrete Input Sinking (NPN)

OFF*

Discrete Input Sourcing (PNP)

ON

Warm-up Time 10 milliseconds

OFF*

OFF*

Warm-up Time 62.5 milliseconds

OFF

ON

Warm-up Time 125 milliseconds

ON

OFF

Warm-up Time 2 seconds

ON

ON

Sample/Report Rate 1 second

OFF*

OFF*

OFF*

Sample/Report Rate 2 seconds

OFF

OFF

ON

Sample/Report Rate 4 seconds

OFF

ON

OFF

Sample/Report Rate 16 seconds

OFF

ON

ON

Sample/Report Rate 64 seconds

ON

OFF

OFF

Sample/Report Rate 5 minutes

ON

OFF

ON

Sample/Report Rate 15 minutes

ON

ON

OFF

Modbus or UCT configured (overrides DIP switches)

ON

ON

ON

Analog IN 2, Discrete 1, and Discrete 2 are not powered from switched power terminals. In this configuration, SP2 is disabled. If you need
SP2, contact the factory.

SureCross DX99 FlexPower Node (Polycarbonate Housing)

 

 

P/N 142496 Rev. F

www.bannerengineering.com - tel: 763-544-3164

3

Summary of Contents for SureCross DX99 FlexPower Series

Page 1: ...nstalled in accordance with the National Electrical Code the Canadian Electrical Code or applicable local codes regulations Model 0 to 20 mA Frequency Boost Voltage Inputs and Outputs DX99N9X2S2N0M2X0...

Page 2: ...all your wireless sensor network components If installation instructions are not included in this datasheet refer to the product manual for detailed installation instructions For additional informatio...

Page 3: ...ch settings for this device are all in the OFF position Analog Configuration Switch 2 OFF 10V Boost Models For analog configuration DIP switch 2 is in the OFF position factory default Analog configura...

Page 4: ...minutes ON OFF ON Sample Report Rate 30 minutes ON ON OFF Modbus or UCT configured overrides DIP switches ON ON ON Analog IN 2 Discrete 1 and Discrete 2 are not powered from switched power terminals...

Page 5: ...lexPower applications setting the report rate to a slower rate extends the battery life Warm Up Time The warm up time defines how long the device must power up the sensor before a stable sensor readin...

Page 6: ...LCD remains on for an additional minute after the radio enters storage mode After a device has entered storage mode you must wait one minute before waking it During normal operation the SureCross rad...

Page 7: ...t Rates 1 second 16 seconds Accuracy 0 25 of full scale 0 01 per C Resolution 12 bit Ratings IEC IP67 NEMA 4x Operating Conditions Operating Temperature 40 to 70 C Operating Humidity 95 max relative n...

Page 8: ...ineering Corp if the destination country is not on this list Violating Warnings The manufacturer does not take responsibility for the violation of any warning listed in this document Make no modificat...

Reviews:

Related manuals for SureCross DX99 FlexPower Series