The User Configuration Tool (UCT) offers an easy way to link I/O points in your wire-
less network, view I/O register values graphically, and set system communication pa-
rameters when a host system is not part of the wireless network.
The UCT requires a special USB to RS-485 (model number BWA-UCT-900 for 1 Watt
radios, BWA-HW-006 can be used for all other radios) converter cable to pass infor-
mation between your computer and the Gateway. Download the most recent revi-
sions of the UCT software from Banner Engineering's website: 

http://www.banneren-

gineering.com/wireless

.

Setting Up Your Wireless Network

To set up and install your wireless network, follow these steps.

Disconnect the power from your SureCross devices.

1. Configure the DIP switches of all devices.
2. Connect the sensors to the SureCross devices.
3. Apply power to all devices.
4. Form the wireless network by binding the Nodes to the Gateway. If the binding instructions are not included in the datasheet, refer to

the product manual for binding instructions.

5. Observe the LED behavior to verify the devices are communicating with each other.
6. Conduct a site survey between the Gateway and Nodes. If the site survey instructions are not included in this datasheet, refer to the

product manual for detailed site survey instructions.

7. Install your wireless sensor network components. If installation instructions are not included in this datasheet, refer to the product

manual for detailed installation instructions.

For additional information, including installation and setup, weatherproofing, device menu maps, troubleshooting, and a list of accesso-
ries, refer to one of the following product manuals.

• SureCross Wireless I/O Network Manual: 

132607

• Web Configurator Manual (used with "Pro" and DX83 models): 

134421

• Host Configuration Manual 

132114

Configuring the DIP Switches

Before making any changes to the DIP switch positions, disconnect the power. DIP switch changes will not be recognized if power isn't
cycled to the device.

Accessing the Internal DIP Switches

To access the internal DIP switches, follow these steps:

1. Unscrew the four screws that mount the cover to the bottom housing.
2. Remove the cover from the housing without damaging the ribbon cable or the pins the cable plugs into.
3. Gently unplug the ribbon cable from the board mounted into the bottom housing.
4. Remove the black cover plate from the bottom of the device's cover.

The DIP switches are located behind the rotary dials.

After making the necessary changes to the DIP switches, place the black cover plate back into position and
gently push into place. Plug the ribbon cable in after verifying that the blocked hole lines up with the missing
pin. Mount the cover back onto the housing.

 

 

SureCross DX99 FlexPower Node (Polycarbonate Housing)

2

www.bannerengineering.com - tel: 763-544-3164

P/N 142496 Rev. F

Summary of Contents for SureCross DX99 FlexPower Series

Page 1: ...nstalled in accordance with the National Electrical Code the Canadian Electrical Code or applicable local codes regulations Model 0 to 20 mA Frequency Boost Voltage Inputs and Outputs DX99N9X2S2N0M2X0...

Page 2: ...all your wireless sensor network components If installation instructions are not included in this datasheet refer to the product manual for detailed installation instructions For additional informatio...

Page 3: ...ch settings for this device are all in the OFF position Analog Configuration Switch 2 OFF 10V Boost Models For analog configuration DIP switch 2 is in the OFF position factory default Analog configura...

Page 4: ...minutes ON OFF ON Sample Report Rate 30 minutes ON ON OFF Modbus or UCT configured overrides DIP switches ON ON ON Analog IN 2 Discrete 1 and Discrete 2 are not powered from switched power terminals...

Page 5: ...lexPower applications setting the report rate to a slower rate extends the battery life Warm Up Time The warm up time defines how long the device must power up the sensor before a stable sensor readin...

Page 6: ...LCD remains on for an additional minute after the radio enters storage mode After a device has entered storage mode you must wait one minute before waking it During normal operation the SureCross rad...

Page 7: ...t Rates 1 second 16 seconds Accuracy 0 25 of full scale 0 01 per C Resolution 12 bit Ratings IEC IP67 NEMA 4x Operating Conditions Operating Temperature 40 to 70 C Operating Humidity 95 max relative n...

Page 8: ...ineering Corp if the destination country is not on this list Violating Warnings The manufacturer does not take responsibility for the violation of any warning listed in this document Make no modificat...

Reviews:

Related manuals for SureCross DX99 FlexPower Series