background image

LED 1

LED 2

Node Status

 (flashing green)

Radio Link Ok

 (flashing red)

 (flashing red)

Device Error

 (flashing red, 1 per 3 sec)

No Radio Link

Modbus Register Table

I/O

Modbus Holding Register

I/O Type

I/O Range

Holding Register Represen-
tation

Terminal Block

Labels

Gateway

Any Node

Min.

Max.

Min. (Dec.)

Max. (Dec.)

1

1

1 + (Node# × 16)

Discrete IN 1

0

1

0

1

DI1

2

2

2 + (Node# × 16)

Discrete IN 2

0

1

0

1

DI2

3

3

3 + (Node# × 16)

Analog IN 1 (mA or V)

0.0

20.0 or 10.0

0

65535

A1+

4

4

4 + (Node# × 16)

Analog IN 2 (mA or V)

0.0

20.0 or 10.0

0

65535

A2+

...

7

7

7 + (Node# × 16)

Reserved

8

8

8 + (Node# × 16)

Device Message

...

15

15

15 + (Node# × 16)

Control Message

16

16

16 + (Node# × 16)

Reserved

Storage Mode and Sleep Mode

While in storage mode, the radio does not operate. All SureCross

®

 radios powered from an integrated battery ship from the factory in

storage mode to conserve the battery. To wake the device, press and hold button 1 for five seconds. To put any FlexPower

®

 or integra-

ted battery SureCross radio into storage mode, press and hold button 1 for five seconds. The radio is in storage mode when the LEDs
stop blinking, but in some models, the LCD remains on for an additional minute after the radio enters storage mode. After a device has
entered storage mode, you must wait one minute before waking it.
During normal operation, the SureCross radio devices enter sleep mode after 15 minutes of operation. The radio continues to function,
but the LCD goes blank. To wake the device, press any button.

Specifications

Radio

General

Range

900 MHz: Up to 4.8 kilometers (3 miles)
2.4 GHz: Up to 3.2 kilometers (2 miles)

Transmit Power

900 MHz: 21 dBm (150 mW) conducted
2.4 GHz: 18 dBm (65 mW) conducted, less than or equal to
20 dBm (100 mW) EIRP

900 MHz Compliance (150 mW Radios)

FCC ID TGUDX80 - This device complies with FCC Part 15,
Subpart C, 15.247
IC: 7044A-DX8009

Power

Requirements: 3.6V dc low power option (from the DX81H
Battery Supply Module)
Consumption: Application dependant

Housing

Polycarbonate housing and rotary dial cover; polyester la-
bels; EDPM rubber cover gasket; nitrile rubber, non-sulphur
cured button covers
Weight: 0.26 kg (0.57 lbs)
Mounting: #10 or M5 (SS M5 hardware included)
Max. Tightening Torque: 0.56 N·m (5 lbf·in)

Antenna Connection

Ext. Reverse Polarity SMA, 50 Ohms
Max Tightening Torque: 0.45 N·m (4 lbf·in)

 

 

SureCross DX99 FlexPower Node (Polycarbonate Housing)

6

www.bannerengineering.com - tel: 763-544-3164

P/N 142496 Rev. F

Summary of Contents for SureCross DX99 FlexPower Series

Page 1: ...nstalled in accordance with the National Electrical Code the Canadian Electrical Code or applicable local codes regulations Model 0 to 20 mA Frequency Boost Voltage Inputs and Outputs DX99N9X2S2N0M2X0...

Page 2: ...all your wireless sensor network components If installation instructions are not included in this datasheet refer to the product manual for detailed installation instructions For additional informatio...

Page 3: ...ch settings for this device are all in the OFF position Analog Configuration Switch 2 OFF 10V Boost Models For analog configuration DIP switch 2 is in the OFF position factory default Analog configura...

Page 4: ...minutes ON OFF ON Sample Report Rate 30 minutes ON ON OFF Modbus or UCT configured overrides DIP switches ON ON ON Analog IN 2 Discrete 1 and Discrete 2 are not powered from switched power terminals...

Page 5: ...lexPower applications setting the report rate to a slower rate extends the battery life Warm Up Time The warm up time defines how long the device must power up the sensor before a stable sensor readin...

Page 6: ...LCD remains on for an additional minute after the radio enters storage mode After a device has entered storage mode you must wait one minute before waking it During normal operation the SureCross rad...

Page 7: ...t Rates 1 second 16 seconds Accuracy 0 25 of full scale 0 01 per C Resolution 12 bit Ratings IEC IP67 NEMA 4x Operating Conditions Operating Temperature 40 to 70 C Operating Humidity 95 max relative n...

Page 8: ...ineering Corp if the destination country is not on this list Violating Warnings The manufacturer does not take responsibility for the violation of any warning listed in this document Make no modificat...

Reviews:

Related manuals for SureCross DX99 FlexPower Series