8 Configuration Instructions
8.1 DXM Configuration Software
Download the latest version of all configuration software from
http://www.bannerengineering.com
. For more information on
using the DXM Configuration Software, refer to the instruction manual (p/n
Figure 28. Overview of the configuration software features
USB
Ethernet
DXM Configuration Software
Local Registers
Register
View Utility
System
Settings
Register Mapping
Scheduler
Action Rules
Script Basic
XML Config File
The configuration software configures the DXM by creating an XML file that is transferred to the DXM using a USB or
Ethernet connection. The DXM can also receive the XML configuration file from a Web server using a cellular or Ethernet
connection.
This configuration file governs all aspects of the DXM operation.
The wireless network devices are a separate configurable system. Use the DX80 User Configuration Software to configure
the internal DX80 wireless Gateway and the attached wireless Nodes. Use the MultiHop Configuration Software if the internal
radio is a MultiHop device.
All tools can be connected to the DXM using a USB cable or an Ethernet connection.
8.2 Save and Upload the Configuration File
After making any changes to the configuration, you must save the configuration files to your computer, then upload it to the
device.
Changes to the XML file are not automatically saved. Save your configuration file before exiting the tool and before sending
the XML file to the device to avoid losing data. If you select
DXM
>
Send XML Configuration to DXM
before saving the
configuration file, the software will prompt you to choose between saving the file or continuing without saving the file.
1. Save the XML configuration file to your hard drive by going to the
File
>
Save As
menu.
2. Go to the
DXM
>
Send XML Configuration to DXM
menu.
Figure 29. Status indicator bar
•
If the Application Status indicator is red, close and restart the DXM Configuration Tool, unplug and re-plug in the
cable and reconnect the DXM to the software.
•
If the Application Status indicator is green, the file upload is complete.
•
If the Application Status indicator is yellow, the file transfer is in progress.
The device reboots and begins running the new configuration.
Sure Cross
®
DXM100-Bx and DXM1000-Bx Wireless Controllers
52
www.bannerengineering.com - Tel: + 1 888 373 6767