The network address settings from the LCD menu have the highest priority and override settings in the XML configuration
file. To use the parameter settings from the XML configuration file or use DHCP, execute the
Reset
under
System Config
>
Ethernet
or use the LCD display to set the IP Address, Gateway Address, and Subnet Mask to 255.255.255.255. Reboot the
DXM after changing the Ethernet parameters.
The Ethernet cable should be attached before powering up the DXM.
7.5.4 Provision Cell
If the DXM has a cellular modem installed, the modem must be provisioned on the network. This menu provisions the cellular
modem on the network. For step by step directions, see
on p. 37.
7.5.5 DXM Modbus ID
Use the secondary Modbus RS-485 port when the DXM is connected to a Modbus RTU network as a Modbus slave device.
Set the Modbus ID for the secondary RS-485 port using the LCD display menu
System Config
>
DXM Modbus ID
.
7.5.6 LCD Contrast
Use the
LCD Contrast
option to adjust the LCD contrast. Adjust the starting number lower to decrease the display contrast.
The factory default is 28. Do not set a number less than 15 or the display may not be bright enough to see to change back.
7.5.7 Reset
Use the
Restart
menu to force the main processor to restart. This does not affect the other boards in the system.