Banner RP-LS42F LE Series Instruction Manual Download Page 7

Figure 13. Safety Contacts at 21/22 and 41/42

41

42

33

34

13
14
21
22

CH2 (N.C.)

CH1 (N.C.)

To ensure the highest level of reliability (Control Reliable or Category 4, for example), wire the positively-driven safety contacts

(terminals 21/22 and 41/42) in a dual channel hookup to a safety module (for example, ES-FA-9AA), safety controller (for example,

XS/SC26 or SC10-2roe), or the safety related part of the machine control that complies with the required level of safety performance.
Two functions of the safety module or safety controller are:

1. To provide a means of monitoring the contacts of both safety switches for contact failure, and to prevent the machine from

restarting if either switch fails.

2. To provide a reset routine after re-arming/resetting the rope pull switch (returning the safety contacts to their closed

position). This prevents the controlled machinery from restarting by simply resetting the switch. This necessary reset

function is required by ANSI B11.0 and NFPA 79 machine safety standards.

WARNING:

Ensure the safety circuit integrity

The safety circuit integrity level is affected by the design and installation of the safety devices and the

means of interfacing with those devices.

Perform a risk assessment to determine the appropriate safety circuit integrity level or category to

ensure the expected risk reduction is achieved and all applicable regulations and standards are in

compliance (see ANSI B11.0 and ANSI B11.19, ISO 12100 and ISO13849-1 or the applicable

standards).

WARNING:

Connect two or more devices to the same safety module (controller) in series

Connecting devices in parallel defeats the switch contact monitoring ability of the module and creates an

unsafe condition that could result in serious injury or death.

Failure to test each device individually in this manner could result in undetected faults and create an

unsafe condition that could result in serious injury or death.

Connect the contacts of the corresponding pole of each switch in series. Never connect the contacts of

multiple switches in parallel. Individually actuate (engage) each device, then release (or re-arm) and

reset the safety module. This allows the module to check each switch and its wiring to detect faults.

Perform this check during the prescribed checkouts.

Maintenance/Checkout

At switch installation or replacement and at machine set up, a Designated Person

3

 must test each switch for proper machine

shutdown response and check the switch(es) and installation for proper operation, physical damage, mounting (looseness), and

excessive environmental contamination. This must also take place on a periodic schedule determined by the user, based on the

severity of the operating environment and the frequency of switch actuations. This is generally determined by a risk assessment,

such as the one contained in ANSI B11.0. Adjust, repair, or replace components as needed. If inspection reveals contamination on

the switch, thoroughly clean the switch and eliminate the cause of the contamination. Replace the switch and/or appropriate

components when any parts or assemblies are damaged, broken, deformed, or badly worn; or if the electrical/mechanical

specifications (for the environment and operating conditions) have been exceeded. Always test the control system for proper

functioning under machine control conditions after performing maintenance, replacing the switch, or replacing any component of the

switch.
Additional items that should be included in the checkout and/or regularly scheduled maintenance of a rope pull system:

Check for proper rope tension and adjust as needed

Verify free operation (no binding) of the rope and proper tripping when the rope is pulled

Periodically lubricate the pulleys and other moving parts associated with the rope

Repair any loose or damaged hardware, worn/frayed rope (cable), missing red rope sheathing or flags/markers (if used)

Remove or clean off any contamination and eliminate its cause

3

A Designated Person is identified in writing by the employer as being appropriately trained to perform a specified checkout procedure.

Rope Pull Emergency Stop Switches

 

 

P/N 67709 Rev. C

www.bannerengineering.com - Tel: + 1 888 373 6767

7

Summary of Contents for RP-LS42F LE Series

Page 1: ...22 34 42 13 21 33 41 Run 14 22 34 42 13 21 33 41 Pull Break Note This symbol for a positive opening safety contact IEC 60947 5 1 is used in the switching diagram to identify the point in actuator tra...

Page 2: ...cable pull The rope or cable pull as well as any flags or markers must be colored RED The rope or cable pull must have the capability to react to a force in any direction This requires a spring at the...

Page 3: ...mbly RPA S4 1 or RPA S6 1 eye bolt to an anchor that is solid and stationary and can withstand the constant tension and pull of the rope Do not exceed the maximum length for the specific switch 3 For...

Page 4: ...edian position to allow for adjustment in both directions b Attach the prepared turnbuckle to the rope using a thimble clamp loop Keep the rope s PVC cover intact along its complete length except wher...

Page 5: ...e accomplished by pulling excess rope through the clamp until the tension indicator is approximately centered and then re tightening the clamp It is recommended that tensioning be accomplished at a me...

Page 6: ...s to the terminals 1 Insert the screwdriver blade flat 2 5 mm into the slot next to the desired wiring terminal 2 Twist the screwdriver blade 45 in the slot to open the terminal jaws insert the wire 6...

Page 7: ...series Never connect the contacts of multiple switches in parallel Individually actuate engage each device then release or re arm and reset the safety module This allows the module to check each switc...

Page 8: ...Type gG Recommend external fusing or overload protection B10d 1 x 105 cycles at DC 13 24 V Ie2 0 1 A Mechanical Life 1 x 105 switching cycles maximum according to IEC 60947 5 5 Wire Connections 8 x ca...

Page 9: ...ion 130 mm 5 in flying lead wires 1 each 30 27 M20 X 1 5 SI K30LRXX7P 1 RED indication 1 each SI K30LYRX7P 2 YELLOW RED indication 1 each Cable Gland Model Size For Cable Diameter Dimensions Used With...

Page 10: ...8 ft 3 mm steel wire rope with 0 5 mm red PVC jacket unterminated RPA C2 20 20 m 65 6 ft RPA C2 40 40 m 131 2 ft RPA C2 50 50 m 164 0 ft RPA C2 80 80 m 262 4 ft Model Quantity Description Thimble RPA...

Page 11: ...Turnbuckle Each RPAK C2SBP 1 0 5 m 1 5 ft 2 2 RPAK CH2 10 10 m 32 8 ft 4 4 3 RPAK CHP2 10 4 4 3 3 RPAK CH2 10 TA 4 4 3 1 RPAK CHP2 10 TA 4 4 3 3 1 RPAK CH2 20 20 m 65 6 ft 4 4 6 RPAK CHP2 20 4 4 6 6...

Page 12: ...IVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED INCLUDING WITHOUT LIMITATION ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE AND WHETHER ARISING UNDER COURSE OF...

Reviews: