Banner RP-LS42F LE Series Instruction Manual Download Page 4

Figure 4. Individual Tension Springs

Ls

L

Spring Breakage

Protection Cable

min

RP-LS42F-25xx/-38xx

RP-LS42F-75xx

Tensioning

Spring

RPA-S5-1

RPA-S3-1

Lmin

185 mm

201 mm

Ls

300 mm

300 mm

Spring Rating

2.5

3.5

Figure 5. Tension Spring Assembly

L

Ø

D

min

L

M12

30

max

RP-LS42F-25xx/-38xx

RP-LS42F-75xx

Tensioning

Spring

Assembly

RPA-S6-1

RPA-S4-1

Lmin

362 mm

465 mm

Lmax

466 mm

635 mm

ØD

42 mm

50 mm

5. Route the rope using pulleys (recommended) or eye bolts at each support point (securely/rigidly mounted) as described in 

Figure 6 

on p. 4.

Important: 

Always use a pulley when changing the direction of the rope or routing the rope around a

corner, regardless of the angle. Minimize friction at all supports and change of direction; do not run rope
through conduit or other tubing.

Figure 6. Assembly of Rope and Hardware

Max. Length

Force to actuate must

not exceed 200 N (45 lbf)

400 mm (16 in.) max.

for actuation of switch

Max. Length

2-5 m

2-5 m

Lg = 200 mm to 400 mm

Lg = 200 mm
to 400 mm

La = 150 mm to 300 mm

La = 150 mm to 300 mm

The distance between 

the ring and the 

turnbuckle should be 

as short as possible.

6. For models 

RP-LS42F-..L with ring connection

:

a) Adjust the Turnbuckle (RP-TA1-1) to a median position (to allow for adjustment in both directions).
b) Attach the prepared turnbuckle to the rope using a thimble/clamp loop. Keep the rope’s PVC cover intact along its

complete length, except where it attaches to the clamps.

c) Assemble the Turnbuckle (RP-TA1-1) and the second thimble/clamp loop to attach the connection link between the

turnbuckle and the ring of the switch, as shown 

Figure 6 

on p. 4. Hardware kit RPAK-C2SBP-1 can be used for the

connection link.

d) Check the rope for proper routing for the complete length.
e) Assemble the third thimble/clamp on the ring of the switch.
f) Pull the connection link cable so that the approximate tension is achieved, and tighten the clamp to hold the rope firmly

in place.

g) Make sure the cut ends on the rope do not present a hazard (cutting, scraping, snagging, etc.). Electrical/plastic tape or

plastic tubing can be used to cover any sharp ends of the rope.

7. For models 

RP-LS42F-..LF with integral turnbuckle

:

These models have their own integral turnbuckle and clamp to tension the rope and to hold it in place. This innovative
design provides for quick and easy rope fixing and tensioning, and requires no external turnbuckle, nor any additional clamp
at the switch end of the rope. To install the rope, as shown in 

Figure 7 

on p. 5:

 

 

Rope Pull Emergency Stop Switches

4

www.bannerengineering.com - Tel: + 1 888 373 6767

P/N 67709 Rev. C

Summary of Contents for RP-LS42F LE Series

Page 1: ...22 34 42 13 21 33 41 Run 14 22 34 42 13 21 33 41 Pull Break Note This symbol for a positive opening safety contact IEC 60947 5 1 is used in the switching diagram to identify the point in actuator tra...

Page 2: ...cable pull The rope or cable pull as well as any flags or markers must be colored RED The rope or cable pull must have the capability to react to a force in any direction This requires a spring at the...

Page 3: ...mbly RPA S4 1 or RPA S6 1 eye bolt to an anchor that is solid and stationary and can withstand the constant tension and pull of the rope Do not exceed the maximum length for the specific switch 3 For...

Page 4: ...edian position to allow for adjustment in both directions b Attach the prepared turnbuckle to the rope using a thimble clamp loop Keep the rope s PVC cover intact along its complete length except wher...

Page 5: ...e accomplished by pulling excess rope through the clamp until the tension indicator is approximately centered and then re tightening the clamp It is recommended that tensioning be accomplished at a me...

Page 6: ...s to the terminals 1 Insert the screwdriver blade flat 2 5 mm into the slot next to the desired wiring terminal 2 Twist the screwdriver blade 45 in the slot to open the terminal jaws insert the wire 6...

Page 7: ...series Never connect the contacts of multiple switches in parallel Individually actuate engage each device then release or re arm and reset the safety module This allows the module to check each switc...

Page 8: ...Type gG Recommend external fusing or overload protection B10d 1 x 105 cycles at DC 13 24 V Ie2 0 1 A Mechanical Life 1 x 105 switching cycles maximum according to IEC 60947 5 5 Wire Connections 8 x ca...

Page 9: ...ion 130 mm 5 in flying lead wires 1 each 30 27 M20 X 1 5 SI K30LRXX7P 1 RED indication 1 each SI K30LYRX7P 2 YELLOW RED indication 1 each Cable Gland Model Size For Cable Diameter Dimensions Used With...

Page 10: ...8 ft 3 mm steel wire rope with 0 5 mm red PVC jacket unterminated RPA C2 20 20 m 65 6 ft RPA C2 40 40 m 131 2 ft RPA C2 50 50 m 164 0 ft RPA C2 80 80 m 262 4 ft Model Quantity Description Thimble RPA...

Page 11: ...Turnbuckle Each RPAK C2SBP 1 0 5 m 1 5 ft 2 2 RPAK CH2 10 10 m 32 8 ft 4 4 3 RPAK CHP2 10 4 4 3 3 RPAK CH2 10 TA 4 4 3 1 RPAK CHP2 10 TA 4 4 3 3 1 RPAK CH2 20 20 m 65 6 ft 4 4 6 RPAK CHP2 20 4 4 6 6...

Page 12: ...IVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED INCLUDING WITHOUT LIMITATION ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE AND WHETHER ARISING UNDER COURSE OF...

Reviews: