Banner RP-LS42F LE Series Instruction Manual Download Page 3

A tensioning spring is required to ensure compliance with direction-independent actuation of the wire rope and must be

installed on the load bearing structure (for example, machine frame, wall, etc.)

Temperature affects rope tension. The wire rope expands (lengthens) when temperature increases, and contracts (shrinks)

when temperature decreases. Significant temperature variations require frequent checks of the tension adjustment

Do not exceed the maximum specified total wire rope length. This length may be reduced due to temperature variations as

described in 

Figure 3 

on p. 3

Figure 3. Maximum Temperature Variation by Length (Steel Rope/Wire)

Span L max. in meters [m]

Max. temperature 

variation in  

Celsius (C)

and (Farenheit (F))

± 40°C (± 72°F)

± 35°C (± 63°F)

± 30°C (± 54°F)

± 25°C (± 45°F)

± 20°C (± 36°F)

± 15°C (± 27°F)

± 10°C (± 18°F)

± 5°C (± 9°F)

± 3.5°C (± 6.3°F)

WARNING:

Properly install the device

Failure to follow the installation instructions can result in ineffective or non-operation of the Banner

device, which could create an unsafe condition resulting in serious injury or death.

Follow all installation instructions.

Installation Procedure

1. Mount the switch securely on a solid, stationary surface that can accommodate the forces of pulling the rope.

See 

Dimensions

 on p. 9 for the mounting hole pattern (4 x M5, Max. torque = 2 Nm).

2. At the opposite end of the rope span, fasten an individual eye bolt (such as RPA-EB1-1) or the Tensioning Spring Assembly

(RPA-S4-1 or RPA-S6-1) eye bolt to an anchor that is solid and stationary, and can withstand the constant tension and pull
of the rope. Do not exceed the maximum length for the specific switch.

3. For applications using an 

Individual Tensioning Spring

 (RPA-S5-1 or RPA-S3-1), assemble the Spring Breakage

Protection Cable (such as RPAK-C2SBP-1) and the thimble/clamp loop at the end of the rope, as shown in 

Figure 4 

on p.

4. Keep the rope’s PVC cover intact along its complete length, except where it attaches to the clamps at either end. Use
Tensioning Spring RPA-S5-1 for the 25 m and the 38 m switches in straight line applications and RPA-S3-1 for 75 m
applications or in any application in which the direction changes.

4. For applications using a 

Tensioning Spring Assembly

 (such as RPA-S4-1 or RPA-S6-1), install the rope using the

following steps.
See 

Figure 5 

on p. 4 and 

Figure 7 

on p. 5.

a) Strip away a minimum of 100 mm to 150 mm (4 in to 6 in) of the red rope sheathing. Additional length of red sheathing

maybe required to be removed depending on total slack in the rope.

b) Using a 4 mm hex wrench, loosen the set screw on the switch fitting.
c) Insert the cable into the center hole in the clamp, pull the excess rope through, and loop the rope back through the

clamp.

d) Pull the cut end of the rope out from the side hole until there is no excess rope in the clamp.
e) Make sure that no red sheathing is within the clamping mechanism.
f) Using the 4 mm hex wrench, tighten the set screw on the switch fitting.

Rope Pull Emergency Stop Switches

 

 

P/N 67709 Rev. C

www.bannerengineering.com - Tel: + 1 888 373 6767

3

Summary of Contents for RP-LS42F LE Series

Page 1: ...22 34 42 13 21 33 41 Run 14 22 34 42 13 21 33 41 Pull Break Note This symbol for a positive opening safety contact IEC 60947 5 1 is used in the switching diagram to identify the point in actuator tra...

Page 2: ...cable pull The rope or cable pull as well as any flags or markers must be colored RED The rope or cable pull must have the capability to react to a force in any direction This requires a spring at the...

Page 3: ...mbly RPA S4 1 or RPA S6 1 eye bolt to an anchor that is solid and stationary and can withstand the constant tension and pull of the rope Do not exceed the maximum length for the specific switch 3 For...

Page 4: ...edian position to allow for adjustment in both directions b Attach the prepared turnbuckle to the rope using a thimble clamp loop Keep the rope s PVC cover intact along its complete length except wher...

Page 5: ...e accomplished by pulling excess rope through the clamp until the tension indicator is approximately centered and then re tightening the clamp It is recommended that tensioning be accomplished at a me...

Page 6: ...s to the terminals 1 Insert the screwdriver blade flat 2 5 mm into the slot next to the desired wiring terminal 2 Twist the screwdriver blade 45 in the slot to open the terminal jaws insert the wire 6...

Page 7: ...series Never connect the contacts of multiple switches in parallel Individually actuate engage each device then release or re arm and reset the safety module This allows the module to check each switc...

Page 8: ...Type gG Recommend external fusing or overload protection B10d 1 x 105 cycles at DC 13 24 V Ie2 0 1 A Mechanical Life 1 x 105 switching cycles maximum according to IEC 60947 5 5 Wire Connections 8 x ca...

Page 9: ...ion 130 mm 5 in flying lead wires 1 each 30 27 M20 X 1 5 SI K30LRXX7P 1 RED indication 1 each SI K30LYRX7P 2 YELLOW RED indication 1 each Cable Gland Model Size For Cable Diameter Dimensions Used With...

Page 10: ...8 ft 3 mm steel wire rope with 0 5 mm red PVC jacket unterminated RPA C2 20 20 m 65 6 ft RPA C2 40 40 m 131 2 ft RPA C2 50 50 m 164 0 ft RPA C2 80 80 m 262 4 ft Model Quantity Description Thimble RPA...

Page 11: ...Turnbuckle Each RPAK C2SBP 1 0 5 m 1 5 ft 2 2 RPAK CH2 10 10 m 32 8 ft 4 4 3 RPAK CHP2 10 4 4 3 3 RPAK CH2 10 TA 4 4 3 1 RPAK CHP2 10 TA 4 4 3 3 1 RPAK CH2 20 20 m 65 6 ft 4 4 6 RPAK CHP2 20 4 4 6 6...

Page 12: ...IVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED INCLUDING WITHOUT LIMITATION ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE AND WHETHER ARISING UNDER COURSE OF...

Reviews: