background image

MSC..-1S..E 

Supplement: MINI-SCREEN Models with Selectable Trip/Latch Output

 

 

P/N 68980     

9 

Banner Engineering Corp. • Minneapolis, MN U.S.A.

www.bannerengineering.com  •  Tel: 763.544.3164

Section .1 Addition

.1(s) Troubleshooting Lockout Conditions

An additional error code will indicate if the EDM input requirements have not been satisfied. 

See Figure 24(s).
An EDM error will be caused by:
•  An open EDM input when the MINI-SCREEN controller tries to close its FSD outputs. The 

EDM input must be closed before the system is reset (whether manually or automatically).

•  The EDM input being slow to close (i.e., more than 200 ms) once the MINI-SCREEN opens 

its FSD outputs and issues a stop command to the machine.

Troubleshooting an EDM Error (Flashing # or “E”)

If monitoring MPCEs with EDM input:
•  Flashing # (lockout condition): measure the dc voltage across Mon a and Mon b at TB4 

with a voltmeter.

  -  If the measurement is approximately 32V dc, there is likely an open circuit caused by a 

broken wire, a loose connection, or an MPCE that failed in an energized condition (e.g., a 

welded relay contact of a forced-guided relay). It should not be possible to reset the MINI-

SCREEN in this condition.

  -  If the measurement is approximately 0V dc, there is likely a closed circuit. The problem is 

likely a slow or sticky MPCE, causing the EDM input to close 200 ms after the FSDs open. 

The symptoms may include an intermittent lockout that allows the MINI-SCREEN to be 

reset.

  -  If the measurement is between the two values (0 to 32V dc), a connection or a contact may 

have become resistive. Depending on the severity, this may result in intermittent operation.

To troubleshoot further:

1. Remove power from the machine and from the MINI-SCREEN system.
2. Disconnect FSD1, FSD2, and the SSD output.
3. Remove existing wiring from EDM input at Mon a and Mon b, and replace with a jumper.
4. Apply power to the MINI-SCREEN system only.
   If the MINI-SCREEN can be reset, the fault is probably in either the external wiring 

associated with the N.C. contacts of the MPCEs or in the MPCEs themselves. One or both 

of the MPCEs could be at fault; typically both MPCEs should be replaced in this situation. 

Possible MPCE failures include slow or sluggish reacting, sticky contacts, contact weld, or 

other faults that cause inconsistent or slow response.

   If the MINI-SCREEN can not be reset and the “E” error code is still displayed, replace the 

controller card or see Section 5.3 of the primary manual.

Summary of Contents for MSC 1S Series

Page 1: ...o include Trip Latch output select switches and the addition of a one channel External Device Monitoring EDM input The primary instruction manual for these control boxes is Banner p n 39022 The inform...

Page 2: ...nstruction manual and Section 3 4 s in this supplement Trip Output Upon power up when the control box is configured for Trip Output the FSD and SSD outputs will automatically close once power is appli...

Page 3: ...ust be jumpered if EDM is not used If the MINI SCREEN is set for No Monitoring the user must ensure that any single failure of the external devices will not result in a hazardous condition and will pr...

Page 4: ...ust be eliminated or reduced to acceptable levels as determined by the user by employing supplemental safeguarding One solution is to combine perimeter guarding with area guarding so that an individua...

Page 5: ...internal lockout condition See Sections 2 2 s 2 10 s and 3 2 1 1 s for Warnings and further information Section 3 5 2 Replacement 3 5 2 s External Device Monitoring and System Power Temporary Connecti...

Page 6: ...ght NOTE See Sections 2 10 s and 3 2 1 1 s on the installation of the Key Reset switch Figure 23 Replacement Figure 23a s Generic Machine Interface MINI SCREEN MSC 1S2E Systems with the MSA RM 1 relay...

Page 7: ...Circuit See Sections 2 10 s and 3 2 1 1 s on the installation of the Key Reset switch Figure 23 Replacement Figure 23b s Generic MaAchine Interface MINI SCREEN MSC 1T3E Systems with the MSA RM 2 relay...

Page 8: ...eplacement 3 5 6 s Auxiliary Relay Output The MSC 1S E controller has an Auxiliary Monitor Relay output See Figure 5 in the primary manual for operating status condition and output status The action o...

Page 9: ...ossible to reset the MINI SCREEN in this condition If the measurement is approximately 0V dc there is likely a closed circuit The problem is likely a slow or sticky MPCE causing the EDM input to close...

Page 10: ...ent Status LEDs Diagnostic Indicator LEDs Controller Module Assembly Red Intermittently flashing 4 red LED indicates presence of optical or electrical noise Green LED indicator is always ON except whe...

Page 11: ...e contacts of the monitored device must be capable of switching 15 to 50V dc at 20 to 100 mA Output Configuration FSD1 FSD2 and SSD Replaces Output Configuration category Relays have forced guided con...

Page 12: ...Banner Engineering Corp warrants its products to be free from defects for one year Banner Engineering Corp will repair or replace free of charge any product of its manufacture found to be defective a...

Reviews: