background image

MSC..-1S..E 

Supplement: MINI-SCREEN Models with Selectable Trip/Latch Output

8     

P/N 68980

 

Banner Engineering Corp. • Minneapolis, MN U.S.A.

www.bannerengineering.com  •  Tel: 763.544.3164

Section 3.. Replacement

3..(s) External Device Monitoring

Permanent Connection

After the initial checkout of Section 3.5.3 has been successfully completed, remove the EDM 

bypass circuit, installed in Section 3.5.2(s). Then connect the External Device Monitoring 

(EDM) input to the closed monitoring contacts of the MPCEs. Refer to the NOTICE Regarding 

MPCE Monitoring Hookup, at right

.

TB2 provides connection terminals for the External Device Monitoring input (Mon a and 

Mon b), and is located at the upper left corner of the control box. External device monitoring 

must be wired in one of two configurations: one-channel monitoring, or no monitoring; see 

Section 2.8(s).
After power is connected to the MINI-SCREEN System and the output relay contacts are 

connected to the machine to be guarded, the operation of the MINI-SCREEN System with the 

guarded machine must be verified before the combined System may be put into service. To 

do this, a Qualified Person must perform the Commissioning Checkout Procedure described in 

Section 6.2 of the primary instruction manual.

Section 3.. Replacement

3..(s) Auxiliary Relay Output

The MSC..-1S..E controller has an Auxiliary Monitor Relay output. See Figure 5 in the primary 

manual for operating status condition and output status. 
The action of the Auxiliary Monitor Relay contact “follows” the action of output relays FSD1 

and FSD2 in either Trip mode or Latch mode. The Auxiliary Monitor Relay contact is a 

light-duty contact used for control functions that are not safety-related. A typical use is to 

communicate with a programmable logic controller (PLC). The switching capacity of the 

Auxiliary Monitor Relay is 125V ac or dc max., 500 mA max. Connection to the Auxiliary 

Monitor Relay contact is made at wiring barrier TB4.

Section 3.. Addition

3..(s) Accessory Connections at Terminal Strip TB2

NOTE:  The “Remote Test Input” has been replaced by the External Device Monitoring input. 

See Section 2.8 of the primary manual and Section 2.8(s).

NOTICE Regarding MPCE 

Monitoring Hookup

It is strongly recommended that one normally 
closed, forced-guided, monitoring contact of 
each MPCE be wired as MPCE monitor (as 
shown in Figure 23 of the primary manual). If 
this is done, proper operation of the MPCEs 
will be verified. MPCE monitoring contacts 
must be used in order to maintain control 
reliability.

WARNING . . . 

No EDM

If the application does not require external 
device monitoring, the EDM input must be 
jumpered. It is the user’s responsibility 
to ensure that this does not create a 
hazardous situation.

Summary of Contents for MSC 1S Series

Page 1: ...o include Trip Latch output select switches and the addition of a one channel External Device Monitoring EDM input The primary instruction manual for these control boxes is Banner p n 39022 The inform...

Page 2: ...nstruction manual and Section 3 4 s in this supplement Trip Output Upon power up when the control box is configured for Trip Output the FSD and SSD outputs will automatically close once power is appli...

Page 3: ...ust be jumpered if EDM is not used If the MINI SCREEN is set for No Monitoring the user must ensure that any single failure of the external devices will not result in a hazardous condition and will pr...

Page 4: ...ust be eliminated or reduced to acceptable levels as determined by the user by employing supplemental safeguarding One solution is to combine perimeter guarding with area guarding so that an individua...

Page 5: ...internal lockout condition See Sections 2 2 s 2 10 s and 3 2 1 1 s for Warnings and further information Section 3 5 2 Replacement 3 5 2 s External Device Monitoring and System Power Temporary Connecti...

Page 6: ...ght NOTE See Sections 2 10 s and 3 2 1 1 s on the installation of the Key Reset switch Figure 23 Replacement Figure 23a s Generic Machine Interface MINI SCREEN MSC 1S2E Systems with the MSA RM 1 relay...

Page 7: ...Circuit See Sections 2 10 s and 3 2 1 1 s on the installation of the Key Reset switch Figure 23 Replacement Figure 23b s Generic MaAchine Interface MINI SCREEN MSC 1T3E Systems with the MSA RM 2 relay...

Page 8: ...eplacement 3 5 6 s Auxiliary Relay Output The MSC 1S E controller has an Auxiliary Monitor Relay output See Figure 5 in the primary manual for operating status condition and output status The action o...

Page 9: ...ossible to reset the MINI SCREEN in this condition If the measurement is approximately 0V dc there is likely a closed circuit The problem is likely a slow or sticky MPCE causing the EDM input to close...

Page 10: ...ent Status LEDs Diagnostic Indicator LEDs Controller Module Assembly Red Intermittently flashing 4 red LED indicates presence of optical or electrical noise Green LED indicator is always ON except whe...

Page 11: ...e contacts of the monitored device must be capable of switching 15 to 50V dc at 20 to 100 mA Output Configuration FSD1 FSD2 and SSD Replaces Output Configuration category Relays have forced guided con...

Page 12: ...Banner Engineering Corp warrants its products to be free from defects for one year Banner Engineering Corp will repair or replace free of charge any product of its manufacture found to be defective a...

Reviews: