background image

MSC..-1S..E 

Supplement: MINI-SCREEN Models with Selectable Trip/Latch Output

10     

P/N 68980

 

Banner Engineering Corp. • Minneapolis, MN U.S.A.

www.bannerengineering.com  •  Tel: 763.544.3164

If not monitoring MPCEs with the EDM input:
• Verify that a jumper is installed at Mon a and Mon b of TB2.
• Verify that EDM input connections are correct and are not loose.
•  With the jumper wire in place, measure the dc voltage between the jumper wire and COM 

(TB3). The measurement should be approximately 17V dc. If not, replace the controller and/

or see Section 5.3 of the primary manual.

•  If the MINI-SCREEN can not be reset and the “E” error code is still displayed, replace the 

controller card or see Section 5.3 of the primary manual.

Controller Module

Configuration Switches and LED Identification

1 - Floating Blanking
2 - Auto Power-up

Bank

"A"

1 - Floating Blanking
2 - Auto Power-up

Bank

"B"

Diagnostic
LEDs

Red - Blocked/Lockout 

Steady / Flashing

Green - Clear/Blanking
Yellow - Reset/Alignment

Status
LEDs

Diagnostic Indicator LEDs

Controller Module Assembly

Red

Intermittently flashing #4 red
LED indicates presence of
optical or electrical "noise".

Green LED indicator is
always "ON" except when a
CPU failure is detected.

Notes:

Red
Red

1

Binary

Value

2
4

Green

Error No.

ERROR TYPE / Action

1

0

2

3

4

5

6

7

8

*

E

1

2

1
2

4

4

1

2
4

1
2
4

SYSTEM IS O.K.

RELAY SIGNAL ERROR

• Replace Relay Module
• Replace Controller
• Replace Power Supply

KEY INPUT ERROR

• Check Key Position
• Replace Key Switch

CONTROLLER ERROR

• Replace Controller

RECEIVER ERROR

• Check Receiver Cable
• Replace Receiver

EMITTER ERROR

• Check Emitter Cable
• Replace Emitter

COMMUNICATION ERROR

• Check Cable Connections
• Observe Noise Indicator
• Replace Emitter/Receiver

DIP SWITCH ERROR

• Check Switch Settings
• Replace Controller

CPU ERROR

• Replace Controller

* Green LED off

EDM ERROR

• EDM open at reset
• EDM open at 200 ms
• Check EDM wiring
• All red LEDs flashing

See Section 5.2 for further
information about electrical
and optical “noise”.

NOTE: Flashing error 4 LED indicates noisy environment.

Figure 2 Replacement 

Figure 2(s).  Interpretation of diagnostic indicator LEDs, with additional error codes

Summary of Contents for MSC 1S Series

Page 1: ...o include Trip Latch output select switches and the addition of a one channel External Device Monitoring EDM input The primary instruction manual for these control boxes is Banner p n 39022 The inform...

Page 2: ...nstruction manual and Section 3 4 s in this supplement Trip Output Upon power up when the control box is configured for Trip Output the FSD and SSD outputs will automatically close once power is appli...

Page 3: ...ust be jumpered if EDM is not used If the MINI SCREEN is set for No Monitoring the user must ensure that any single failure of the external devices will not result in a hazardous condition and will pr...

Page 4: ...ust be eliminated or reduced to acceptable levels as determined by the user by employing supplemental safeguarding One solution is to combine perimeter guarding with area guarding so that an individua...

Page 5: ...internal lockout condition See Sections 2 2 s 2 10 s and 3 2 1 1 s for Warnings and further information Section 3 5 2 Replacement 3 5 2 s External Device Monitoring and System Power Temporary Connecti...

Page 6: ...ght NOTE See Sections 2 10 s and 3 2 1 1 s on the installation of the Key Reset switch Figure 23 Replacement Figure 23a s Generic Machine Interface MINI SCREEN MSC 1S2E Systems with the MSA RM 1 relay...

Page 7: ...Circuit See Sections 2 10 s and 3 2 1 1 s on the installation of the Key Reset switch Figure 23 Replacement Figure 23b s Generic MaAchine Interface MINI SCREEN MSC 1T3E Systems with the MSA RM 2 relay...

Page 8: ...eplacement 3 5 6 s Auxiliary Relay Output The MSC 1S E controller has an Auxiliary Monitor Relay output See Figure 5 in the primary manual for operating status condition and output status The action o...

Page 9: ...ossible to reset the MINI SCREEN in this condition If the measurement is approximately 0V dc there is likely a closed circuit The problem is likely a slow or sticky MPCE causing the EDM input to close...

Page 10: ...ent Status LEDs Diagnostic Indicator LEDs Controller Module Assembly Red Intermittently flashing 4 red LED indicates presence of optical or electrical noise Green LED indicator is always ON except whe...

Page 11: ...e contacts of the monitored device must be capable of switching 15 to 50V dc at 20 to 100 mA Output Configuration FSD1 FSD2 and SSD Replaces Output Configuration category Relays have forced guided con...

Page 12: ...Banner Engineering Corp warrants its products to be free from defects for one year Banner Engineering Corp will repair or replace free of charge any product of its manufacture found to be defective a...

Reviews: