How hysteresis affects the output on/off points when if the sensor is configured with mode = Swtch_|- and SPtRef configured
as Backgrnd
On
Off
Near
Far
Setpoint
Hysteresis
Signal
Output
Setpoint Mode Example:
Mode = Swtch
SPtRef = Backgrnd
Press the up button to manually select a constant hysteresis value between 2 mm and 12000 mm.
Navigate
:
MENU
›
D_OUT
›
Hyst
Remote Input
: Not available
Default
: Auto
Timer
The Timer option sets the delays and timers. On/Off Delays and On/Off One-Shot timers can be programmed between 1 to
9999 ms (a value of 0 disables the delay/timer). The following figure defines how the delays/timers affect the output behavior.
Navigate:
MENU
›
Dx_OUT
›
Timer
Remote Input
: not available
Default
: 0 ms for all timers
Delays/Timers
Output
OFF Delay
ON Delay
Time
OFF 1-Shot
ON 1-Shot
ON
OFF
D
D
D
D
D
D
D
D
(D = 1 - 9999 ms)
Some combinations of delays/timers are not allowed. The programming menu automatically disables invalid combinations of delays/timers. The following ta-
ble shows the allowable combinations of delays/timers.
Off Delay
Off One-Shot Timer
On Delay
On One-Shot Timer
Off Delay
(OffDly)
OK
OK
OK
N/A
Continued on page 27
© Banner Engineering Corp.