Banner L-GAGE LTF12 Instruction Manual Download Page 23

June 22, 2023

LTF Time Of Flight Laser Distance Sensor With IO-Link Instruction Manual

 

 

23

Remote Input

: Not available 

Default

: 50 mm 

Mode

The Mode option sets the output to the desired mode. 

 

Navigate:MENU

 › 

Dx_OUT

 › 

Mode

 

Remote Input

: Available 

Default

: Wnd 

 mode 

The following table describes the sensor modes. 

Mode 

Description 

Alarm 

Alarm Mode:

 The Discrete Output is Off while a target is detected by the sensor at any distance.

When a loss of signal occurs, the Discrete Output is On. 

This mode has no associated thresholds. 

Health 

Health Mode:

 The Discrete Output is On while a target is detected by the sensor at any distance.

When a loss of signal occurs, the Discrete Output is Off. 

This mode has no associated thresholds. 

 

Switch

 

Switch Mode:

 The Discrete Output is On while a target is detected nearer than the switch point threshold.

When a target is detected farther than the switch point threshold or the signal is lost, the Discrete Output is Off. 

  

Switch

 

Switch Mode:

 The Discrete Output is Off while a target is detected nearer than the switch point threshold.

When a target is detected farther than the switch point threshold or the signal is lost, the Discrete Output is On. 

Wnd 

 

Window Mode:

 The Discrete Output is On while a target is detected between the SPt1 and SPt2 thresholds. (Default)

When a target is detected outside the SPt1 and SPt2 thresholds or the signal is lost, the Discrete Output is Off. 

Wnd 

 

Window Mode:

 The Discrete Output is Off while a target is detected between the SPt1 and SPt2 thresholds.

When a target is detected outside the SPt1 and SPt2 thresholds or the signal is lost, the Discrete Output is On. 

PFM

 

 The discrete is pulsed at a frequency between 100 Hz and 600 Hz and is scaled proportional to the sensor's 
D2_OUT Measurement span. Targets outside of the measurement span or a loss of signal pulse at 50 Hz. 

 

Remote Input Instructions

Access the setup mode.

Action 

Result 

Double-pulse the remote input. 

 

T

T

T

 

"REMOTE SETUP

" displays. 

1. 

View the current mode.

2. 

© Banner Engineering Corp.

Summary of Contents for L-GAGE LTF12

Page 1: ...LTF Time of Flight Laser Distance Sensor with IO Link Instruction Manual Original Instructions p n 195393 Rev I June 22 2023 Banner Engineering Corp All rights reserved...

Page 2: ...witch Point Two 21 TEACH Switch Point 21 Adjust Switch Point 22 Mode 23 Switch Point Reference SPtRef 24 Switch Point TEACH Offset 25 Switch Point Hysteresis 25 Timer 26 Polarity 27 Input Menu INPUT 2...

Page 3: ...3 Accessories 45 Cordsets 45 Brackets 46 RSD1 Remote Display 46 Banner Engineering Corp Limited Warranty 47 47...

Page 4: ...Blank page 4...

Page 5: ...in personnel safety applications A device failure or malfunction can cause either an energized on or de energized off output condition Models Family Connector Q Rotatable M12 Euro QD QP PVC M12 Euro...

Page 6: ...surement Buttons and Icons Use the sensor buttons Down Up Enter and Escape to program the sensor and to access sensor information Down and Up Buttons Press Down and Up to Access the Quick Menu from Ru...

Page 7: ...y Information CAUTION Return defective units to the manufacturer Use of controls or adjustments or performance of procedures other than those specified herein may result in hazardous radiation exposur...

Page 8: ...e ade quate protection under reasonably foreseeable conditions of operation including the use of optical instruments for intrabeam viewing FDA CDRH warning label Class 2 Class 2 Laser Safety Notes Low...

Page 9: ...hol and cotton swabs or water and a soft cloth Mount the Device Wiring Diagrams IO Link Models shield 12 30 V DC D1_Out IO Link D2_Out Input User configurable PNP NPN setting bu 3 bn 1 wh 2 bk 4 gy 5...

Page 10: ...stems 5 Pin Male Threaded and 5 Pin Female Quick Disconnect M12 Cordset with Shield Double Ended Model Length L1 Style Pinout Male Pinout Female MQDEC3 503SS 0 91 m 2 99 ft Female Straight Male Straig...

Page 11: ...aded M12 Cordsets with Shield Single Ended Model Length Style Dimensions Pinout Female MQDEC2 506RA 2 m 6 56 ft Right Angle 32 Typ 1 26 30 Typ 1 18 14 5 0 57 M12 x 1 MQDEC2 515RA 5 m 16 4 ft MQDEC2 53...

Page 12: ...Blank page 12...

Page 13: ...he buttons for security preventing unauthorized or accidental programming changes See Remote Input on page 14 for more information Accessing the menus from Run Mode Access Quick Menu Access Sensor Men...

Page 14: ...bled by default Activate remote input using the buttons to navigate to the Input Type menu option The remote input provides limited programming options and is Active Low by default For Active Low conn...

Page 15: ...ing D2SPt1 TchSPt1 D2 with measurement value then to TchSPt2 D2 Teaching D2SPt2 TchSPt2 D2 with measurement value then back to Run mode 1x 3x Teaching D1D2SPt1 TchSPt1 D1 and D2 with measurement value...

Page 16: ...ed except for the unlock function Button Instructions To lock or unlock the sensor using the buttons press and hold Down and Escape simultaneously for 3 seconds Remote Input Instructions Access the se...

Page 17: ...OUT AdjSPt1 D1_OUT AdjSPt2 Hyst Auto D1_OUT Hyst Hyst Auto D2_OUT Hyst Mode Health Mode Alarm Mode Swtch Mode Swtch Mode Wnd Mode Wnd D1_OUT Mode SPtRef Object SPtRef Backgrnd D1_OUT SPtRef in SPt mod...

Page 18: ...esired 3 Access the TEACH mode Action Result Single pulse the remote input T RMT TCH and the current switch point val ue displays 1 Present the target Action Result Present the switch point one target...

Page 19: ...range Parameters LTF12 LTF24 Window Size Minimum 10 mm 10 mm Window Size Maximum 11950 mm 23950 mm Range 50 mm to 12000 mm 50 mm to 24000 mm Default Window Size 20 mm 20 mm Remote Input Available Act...

Page 20: ...ulse 10 mm 2 pulses 20 mm 3 pulses 100 mm 4 pulses 500 mm 5 pulses 2000 mm 6 pulses 11950 mm for the LTF12 23950 mm for the LTF24 The new value flashes and the sensor returns to Run mode Present the t...

Page 21: ...utput when the sensor is in Window mode The value is adjustable with the sensor s range It is required to be maintain the minimum window size be tween switch points This menu is not available when the...

Page 22: ...taught TEACH Accepted The new value is shown on the second line of the display and flashes before it is saved and the sensor returns to Dx_OUT Tch SPt TEACH Not Accepted FAIL and a warning message di...

Page 23: ...signal is lost the Discrete Output is Off Switch Switch Mode The Discrete Output is Off while a target is detected nearer than the switch point threshold When a target is detected farther than the sw...

Page 24: ...using the Offset menu that appears only after selecting Custom Switch Point Reference In Object or Background the distance between the taught surface and the switching threshold varies depending on m...

Page 25: ...lue applied at each threshold is automatically calculated and set based on target distance and measurement repeatability with a 10 mm minimum setting By default the hysteresis is applied away from the...

Page 26: ...timers On Off Delays and On Off One Shot timers can be programmed between 1 to 9999 ms a value of 0 disables the delay timer The following figure defines how the delays timers affect the output behavi...

Page 27: ...ote Input Not available Default PNP Input Menu INPUT Use this menu to view or change the Multi function input type Input Menu map or or Go Back to Parent Menu Select Menu Item Press to Save Setting Pr...

Page 28: ...Low The remote input detects low 0 V inputs and high to low transitions Default High The remote input detects high V inputs and low to high transitions Measure Menu MEASURE Use this menu to view or ch...

Page 29: ...splay units Display orientation Sleep mode settings Display Menu Map MENU DISPLAY or or Go Back to Parent Menu Select Menu Item Press to Save Setting DISPLAY Sleep DISPLAY Units Sleep 1min Sleep Disab...

Page 30: ...0 Off 0 the face of the sensor or the maximum range depending on the zero setting SetZero Sets the current distance as its new zero reference location This process is independent of teaching ana log...

Page 31: ...nce 8000 0 4000 12000 mm 0 V Display Reference 8000 0 4000 12000 mm 8000 0 4000 12000 mm mm 0 0 8000 4000 4000 mm 0 8000 4000 4000 mm Zero Far Shift Off Zero Far 8000 0 4000 12000 View The View option...

Page 32: ...del part number P N serial number S N and firmware version Version information Select one of these options to view specific information for your sensor This information is read only Navigate MENU INFO...

Page 33: ...Discrete Output Settings LTF12 LTF24 Adjust Switch Point One 50 mm 50 mm Adjust Switch Point Two 12000 mm 24000 mm Mode Wnd Wnd Hyst Auto Auto Polarity PNP PNP Timer 0 ms for all timers 0 ms for all t...

Page 34: ...Blank page 34...

Page 35: ...ors con figure one sensor to be the master and one to be the slave In this mode the sensors alternate taking measurements and the response speed triples Sync Master Slave Chapter 4 Configure the first...

Page 36: ...Blank page 36...

Page 37: ...e remote input T RMT TCH and the current measurement value dis play 1 Present the target Action Result Present the switch point one target RMT TCH and the target s measurement value dis play 2 TEACH t...

Page 38: ...eaching displays while the sensor is being taught TEACH Accepted The new value displays on the second line of the dis play flashes and the sensor returns to Run mode TEACH Not Accepted FAIL flashes th...

Page 39: ...Flight Laser Distance Sensor With IO Link Instruction Manual 39 Chapter Contents Sensor Menu Full Map 40 Troubleshooting 41 Specifications 41 Accessories 45 Banner Engineering Corp Limited Warranty 47...

Page 40: ...OUT AdjSPt1 D2_OUT AdjSPt2 DISPLAY Sleep DISPLAY Units DISPLAY View INFO Version INFO Model INFO P N INFO S N RESET No RESET Yes Zero Far Zero Near DISPLAY Zero Shift SetZero Shift Off DISPLAY Shift D...

Page 41: ...e is valid The Analog Output cannot be used to measure distances inside the NEAR measur ing range Power LED is flashing green The sensor input is set to laser enable and the input is not active See In...

Page 42: ...ons 20 C to 55 C 4 F to 131 F 90 at 55 C maximum relative humidity non condensing Shock MIL STD 202G Method 213B Condition I 100G 6x along X Y and Z axes 18 shocks with device operating Advanced Capab...

Page 43: ...rd 0 2 0 08 4 0 16 6 0 24 8 0 31 10 0 39 12 0 47 14 0 55 LTF24 Models Speed Slow 256 ms 1 Repeatability in mm inches 2 0 08 0 0 4 0 16 6 0 24 8 0 31 10 0 39 12 0 47 14 0 55 16 0 63 18 0 71 20 0 79 Dis...

Page 44: ...0 31 10 0 39 12 0 47 14 0 55 16 0 63 18 0 71 20 0 79 Distance in m ft 18 Gray Card 90 White Card 6 Black Card Speed Fast 1 5 ms 1 Repeatability in mm inches 2 0 08 0 0 4 0 16 6 0 24 8 0 31 10 0 39 12...

Page 45: ...5 23 m 75 44 ft MQDEC2 5100 30 5 m 100 ft MQDEC2 506RA 2 m 6 56 ft Right Angle 32 Typ 1 26 30 Typ 1 18 14 5 0 57 M12 x 1 MQDEC2 515RA 5 m 16 4 ft MQDEC2 530RA 9 m 29 5 ft MQDEC2 550RA 15 m 49 2 ft MQD...

Page 46: ...rn 12 gauge stainless steel 45 85 134 6X 3 5 2X 4 5 4 5 SMBAMSLTFIP Includes the mounting plate and two protective windows 90 plus degree rotation Window frames are black anodized aluminum mounting pl...

Page 47: ...Y INCIDENTAL CONSEQUENTIAL OR SPECIAL DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE THE PRODUCT WHETHER ARISING IN CONTRACT OR WARRANTY STATUTE TORT STRICT LIABILITY NE...

Page 48: ...LinkedIn Twitter Facebook 2023 All rights reserved www bannerengineering com...

Page 49: ...Mouser Electronics Authorized Distributor Click to View Pricing Inventory Delivery Lifecycle Information Banner Engineering SMBLTFL SMBLTFU...

Reviews: