Banner ES-FA-9AA Instruction Manual Download Page 7

NOTE: The minimum time required for the Module to be in a STOP or OFF condition is 250 ms. This “recovery time” (OFF-

state) is required for the internal circuitry of the Safety Module to normalize, allowing a reliable reset to occur. A lockout

occurs if the Module is cycled too quickly. To clear the lockout, the Module must be recycled, meeting the minimum OFF

time requirements.

Wiring

24V ac/dc

MSC1

E-Stop
Switch

E-Stop
Switch

Reset

MSC3

MSC2

See WARNING

Below

MSC
Monitor
Contacts
or 
Jumper

A2

A1

S34

S33

S21

S11

S12

S22

dc common

+V

ES-FA-9AA

24V ac/dc

Auto Reset

Manual Reset

A2

(No Connection)

A1

S34

S11

S33

MSC1 MSC2 MSC3

S22

S12

S21

dc common

+V

ES-FA-9AA

Figure 4. Dual-Channel E-Stop Applications

24V ac/dc

MSC1 MSC3

MSC2

See Interfacing MSCs

Warning

MSC
Monitor
Contacts
or 
Jumper

A2

A1

S34

S33

S21

S11

S12

S22

dc common

+V

ES-FA-9AA

24V ac/dc

Auto Reset

Manual Reset

A2

(No Connection)

Reset

A1

S34

S11

S33

MSC1 MSC2 MSC3

S22

S12

S21

dc common

+V

ES-FA-9AA

E-Stop
Switch

E-Stop
Switch

Figure 5. Single-Channel E-Stop Applications

Connection to the Machine to be Controlled

The machine hookup diagram shows a generic connection of the Safety Module's redundant output circuits to the master

stop control elements (MSCs). An MSC is defined as an electrically powered device, external to the Safety Module, which

stops the machinery being controlled by immediately removing electrical power to the machine and (when necessary) by

applying braking to dangerous motion. This stopping action is accomplished by removing power to the actuator of either

MSC.

ES-FA-9AA and ES-FA-11AA E-Stop Safety Module

 

 

P/N 60606 Rev. G

www.bannerengineering.com - Tel: +1-763-544-3164

7

Summary of Contents for ES-FA-9AA

Page 1: ...and or hard guards to protect personnel from hazardous machinery Failure to install point of operation guards on hazardous machinery can result in a dangerous condition which could lead to serious inj...

Page 2: ...vel of risk of harm These safety related functions can prevent initiation or they can stop or remove a hazard The failure of a safety related function or its associated safety circuit usually results...

Page 3: ...turn to the closed contact armed position The switch must be a positive opening or direct opening type as described by IEC 60947 5 1 Standards ANSI NFPA 79 ANSI B11 19 IEC EN60204 1 and ISO 13850 spec...

Page 4: ...ble local standards and codes Lockout tagout procedures may be required Refer to OSHA 29CFR1910 147 ANSI Z244 1 ISO 14118 or the appropriate standard for controlling hazardous energy It is not possibl...

Page 5: ...rs associated with the operation of the machine to recognize and immediately correct such failures If you have any questions about your intended use please contact a Banner applications engineer Conne...

Page 6: ...rdous area Reset switches must also be out of reach from within the safeguarded space and must be protected against unauthorized or inadvertent operation for example through the use of rings or guards...

Page 7: ...Interfacing MSCs Warning MSC Monitor Contacts or Jumper A2 A1 S34 S33 S21 S11 S12 S22 dc common V ES FA 9AA 24V ac dc Auto Reset Manual Reset A2 No Connection Reset A1 S34 S11 S33 MSC1 MSC2 MSC3 S22...

Page 8: ...evice A transformer with isolated windings A distribution system with multiple branch circuits capable of diverting energy of surges A capacitance capable of absorbing energy of surges A resistance or...

Page 9: ...sed contact state e g arm the E stop switch to close its contacts Automatic reset Ch1 K1 and Ch2 K2 indicators should come ON and the safety output contacts should close Manual reset From an open cond...

Page 10: ...the Module is not immediately replaced or repaired multiple simultaneous failures may accumulate such that the safety function can not be guaranteed Specifications Power General Supply Voltage and Cur...

Page 11: ...VA 2 000 000 cycles at 250 VA 5 000 000 cycles at 125 VA Output Response Time 25 milliseconds typical Note Transient suppression is recommended when switching inductive loads Install suppressors acro...

Page 12: ...CULAR PURPOSE AND WHETHER ARISING UNDER COURSE OF PERFORMANCE COURSE OF DEALING OR TRADE USAGE This Warranty is exclusive and limited to repair or at the discretion of Banner Engineering Corp replacem...

Reviews: