Banner ES-FA-9AA Instruction Manual Download Page 6

Connection of Safety Switches

The Safety Module may be used to monitor safety interlocking

switches that determine the position of a guard or gate. To

achieve Category 4 operation per ISO 13849-1 (EN 954-1),

two positive-opening safety switches must operate

concurrently when the guard or gate is opened.

The Safety Module verifies concurrent opening of two contacts

– one from each safety switch. Reset of the Safety Module is

not possible if one switch fails to open or if a short circuit

between the safety interlocking switches occurs.

S12

S22

S11 S21

Safety Gate or Guard with  
end-of-travel stops and two  
individually mounted 
Safety Interlocking Switches

OPEN

Figure 3. Wiring using contacts from two safety switches

Connection of Reset Switch

The reset circuit switch can be any mechanical switch, such as a normally open momentary switch, or a two-position key

switch. The reset switch must be capable of reliably switching 8 to 12 V dc at 10 to 15 milliamps. As shown in the hookup

drawings, the reset switch connects between Safety Module terminals S33 and S11.

The reset switch must be located outside of – and not be accessible from – the area of dangerous motion, and must be

positioned so that any area of dangerous motion may be observed by the switch operator during the reset procedure. See

warning below.

WARNING: Reset Switch Location

All reset switches must be accessible only from outside, and in full view of, the hazardous

area. Reset switches must also be out of reach from within the safeguarded space, and must

be protected against unauthorized or inadvertent operation (for example, through the use of

rings or guards). If any areas are not visible from the reset switch(es), additional means of

safeguarding must be provided. Failure to do so may result in serious bodily injury or death.

Automatic Reset Mode

The Safety Module may be configured (via hookup) for automatic reset. If no MSC contacts are monitored, install a jumper

between terminals S33 and S34. The Safety Module will reset (and its outputs energize) as soon as the switch returns to

its armed (closed-contact) position.

Automatic reset is useful for some automated processes. However, if automatic reset is used, it is necessary to provide a

means of preventing resumption of hazardous machine motion, until an alternate reset procedure is performed. The

alternate procedure must include a reset/restart switch, located outside the area of dangerous motion, which is positioned

so that any area of dangerous motion may be observed by the switch operator during the reset procedure. See Warning

below.

WARNING: Reset Routine Required

U.S. and international standards require that a reset routine be performed after clearing the cause of a

stop condition (for example, arming an E-stop button, closing an interlocked guard, etc.). Allowing the

machine to restart without actuating the normal start command/device can create an unsafe

condition which may result in serious injury or death.

 

 

ES-FA-9AA and ES-FA-11AA E-Stop Safety Module

6

www.bannerengineering.com - Tel: +1-763-544-3164

P/N 60606 Rev. G

Summary of Contents for ES-FA-9AA

Page 1: ...and or hard guards to protect personnel from hazardous machinery Failure to install point of operation guards on hazardous machinery can result in a dangerous condition which could lead to serious inj...

Page 2: ...vel of risk of harm These safety related functions can prevent initiation or they can stop or remove a hazard The failure of a safety related function or its associated safety circuit usually results...

Page 3: ...turn to the closed contact armed position The switch must be a positive opening or direct opening type as described by IEC 60947 5 1 Standards ANSI NFPA 79 ANSI B11 19 IEC EN60204 1 and ISO 13850 spec...

Page 4: ...ble local standards and codes Lockout tagout procedures may be required Refer to OSHA 29CFR1910 147 ANSI Z244 1 ISO 14118 or the appropriate standard for controlling hazardous energy It is not possibl...

Page 5: ...rs associated with the operation of the machine to recognize and immediately correct such failures If you have any questions about your intended use please contact a Banner applications engineer Conne...

Page 6: ...rdous area Reset switches must also be out of reach from within the safeguarded space and must be protected against unauthorized or inadvertent operation for example through the use of rings or guards...

Page 7: ...Interfacing MSCs Warning MSC Monitor Contacts or Jumper A2 A1 S34 S33 S21 S11 S12 S22 dc common V ES FA 9AA 24V ac dc Auto Reset Manual Reset A2 No Connection Reset A1 S34 S11 S33 MSC1 MSC2 MSC3 S22...

Page 8: ...evice A transformer with isolated windings A distribution system with multiple branch circuits capable of diverting energy of surges A capacitance capable of absorbing energy of surges A resistance or...

Page 9: ...sed contact state e g arm the E stop switch to close its contacts Automatic reset Ch1 K1 and Ch2 K2 indicators should come ON and the safety output contacts should close Manual reset From an open cond...

Page 10: ...the Module is not immediately replaced or repaired multiple simultaneous failures may accumulate such that the safety function can not be guaranteed Specifications Power General Supply Voltage and Cur...

Page 11: ...VA 2 000 000 cycles at 250 VA 5 000 000 cycles at 125 VA Output Response Time 25 milliseconds typical Note Transient suppression is recommended when switching inductive loads Install suppressors acro...

Page 12: ...CULAR PURPOSE AND WHETHER ARISING UNDER COURSE OF PERFORMANCE COURSE OF DEALING OR TRADE USAGE This Warranty is exclusive and limited to repair or at the discretion of Banner Engineering Corp replacem...

Reviews: