Banner ES-FA-9AA Instruction Manual Download Page 10

Periodic Checkout Procedure

The functioning of the Safety Module and the device(s) connected to it must be verified on a regular periodic basis to

ensure proper operation (see also the machine manufacturer’s recommendations).
1. With the machine running, cause the safety device to generate a STOP or "open-contact" state (e.g., actuate the E-

stop switch to open its contacts). Verify that the machine stops.

2. Reset or otherwise cause the safety device to reach an ON or "closed-contact" state. Verify that the machine does not

restart.

3. If using manual reset mode, close and then open the reset switch within 3 seconds. Verify that the machine can be

restarted by normal initiation.

4. If more than one safety device is series-connected to the Safety Module, run the above checkout procedure individually

for EACH device.

Repairs

Contact Banner Engineering for troubleshooting of this device. Do not attempt any repairs to this Banner device; it

contains no field-replaceable parts or components. If the device, device part, or device component is determined to

be defective by a Banner Applications Engineer, they will advise you of Banner's RMA (Return Merchandise Authorization)

procedure.

Important: If instructed to return the device, pack it with care. Damage that occurs in return shipping

is not covered by warranty.

CAUTION: Abuse of Module After Failure

If an internal fault has occurred and the Module will not reset, do not tap, strike, or otherwise

attempt to correct the fault by a physical impact to the housing. An internal relay may have

failed in such a manner that its replacement is required.

If the Module is not immediately replaced or repaired, multiple simultaneous failures may

accumulate such that the safety function can not be guaranteed.

Specifications

Power

General

Supply Voltage and Current

24 V dc ±10% (SELV-rated supply according to EN IEC 60950, NEC

Class 2)
24 V ac ±10% , 50/60 Hz (NEC Class 2-rated transformer)
Power consumption: approx. 2W/2VA

Overvoltage Category

Output relay contact voltage of 1 V to 150 V ac/dc: category III
Output relay contact voltage of 151 V to 250 V ac/dc: category III, if

appropriate overvoltage reduction is provided, as described in 

Overvoltage Category II and III Installations (EN 50178 and IEC

60664-1)

 on page 8.

Pollution Degree

2

Supply Protection Circuitry

Protected against transient voltages and reverse polarity

Indicators

3 green LED indicators: Power ON , K1 energized, K2 energized

Construction

Polycarbonate housing. Rated NEMA 1, IEC IP40; Terminals IP20

Mounting

Mounts to standard 35 mm DIN rail track. Safety Module must be

installed inside an enclosure rated NEMA 3 (IEC IP54), or better.

Vibration Resistance

10 to 55 Hz at 0.35 mm displacement per IEC 60068-2-6

Operating Conditions

0 °C to +50 °C (+32 °F to +122 °F)
90% at +50 °C maximum relative humidity (non-condensing)

Output Configuration

Output Configuration

ES-FA-9AA: 3 normally open (N.O.) output channels
ES-FA-11AA: 2 normally open (N.O.) output channels and 1 normally

closed (N.C.) auxiliary output

Contacts

AgNi, 5 

μ

m gold-plated

Each normally open output channel is a series connection of

contacts from two forced-guided (mechanically linked)

relays, K1-K2. The normally closed Aux. output channel of

the ES-FA-11AA is a parallel connection of contacts from

two forced-guided relays, K1-K2.

 

 

ES-FA-9AA and ES-FA-11AA E-Stop Safety Module

10

www.bannerengineering.com - Tel: +1-763-544-3164

P/N 60606 Rev. G

Summary of Contents for ES-FA-9AA

Page 1: ...and or hard guards to protect personnel from hazardous machinery Failure to install point of operation guards on hazardous machinery can result in a dangerous condition which could lead to serious inj...

Page 2: ...vel of risk of harm These safety related functions can prevent initiation or they can stop or remove a hazard The failure of a safety related function or its associated safety circuit usually results...

Page 3: ...turn to the closed contact armed position The switch must be a positive opening or direct opening type as described by IEC 60947 5 1 Standards ANSI NFPA 79 ANSI B11 19 IEC EN60204 1 and ISO 13850 spec...

Page 4: ...ble local standards and codes Lockout tagout procedures may be required Refer to OSHA 29CFR1910 147 ANSI Z244 1 ISO 14118 or the appropriate standard for controlling hazardous energy It is not possibl...

Page 5: ...rs associated with the operation of the machine to recognize and immediately correct such failures If you have any questions about your intended use please contact a Banner applications engineer Conne...

Page 6: ...rdous area Reset switches must also be out of reach from within the safeguarded space and must be protected against unauthorized or inadvertent operation for example through the use of rings or guards...

Page 7: ...Interfacing MSCs Warning MSC Monitor Contacts or Jumper A2 A1 S34 S33 S21 S11 S12 S22 dc common V ES FA 9AA 24V ac dc Auto Reset Manual Reset A2 No Connection Reset A1 S34 S11 S33 MSC1 MSC2 MSC3 S22...

Page 8: ...evice A transformer with isolated windings A distribution system with multiple branch circuits capable of diverting energy of surges A capacitance capable of absorbing energy of surges A resistance or...

Page 9: ...sed contact state e g arm the E stop switch to close its contacts Automatic reset Ch1 K1 and Ch2 K2 indicators should come ON and the safety output contacts should close Manual reset From an open cond...

Page 10: ...the Module is not immediately replaced or repaired multiple simultaneous failures may accumulate such that the safety function can not be guaranteed Specifications Power General Supply Voltage and Cur...

Page 11: ...VA 2 000 000 cycles at 250 VA 5 000 000 cycles at 125 VA Output Response Time 25 milliseconds typical Note Transient suppression is recommended when switching inductive loads Install suppressors acro...

Page 12: ...CULAR PURPOSE AND WHETHER ARISING UNDER COURSE OF PERFORMANCE COURSE OF DEALING OR TRADE USAGE This Warranty is exclusive and limited to repair or at the discretion of Banner Engineering Corp replacem...

Reviews: