18
97654 v.7
MOUNTING AND CONNECTING THE
IDASH,
CONTINUED
To start an Advanced B-Bus
Network:
1.
If you ONLY have HW Rev 1
iDash 1.8’s
A.
Connect the
In-Cab
Terminator
to the
iDash
6-pin port.
See
Figure 2-11,
Step A.
Only one
In-Cab
Terminator
is required.
B.
Connect the
Y-Cable
to
the
In-Cab Terminator
and
the second
iDash 1.8.
See
Figure 2-11, Step B.
For each additional
iDash
1.8,
a
Y-Cable
is used.
C.
Connect the
Starter
Cable
to the
Y-Cable.
See
Figure 2-11, Step C
.
2.
If you have ONLY HW Rev 2
iDash 1.8’s:
A.
Connect the
Y-Cable
to
the
iDash 6-pin port
of
the first and second
iDash
1.8
(
Without
the
In-Cab
Terminator
).
See
Figure 2-11, Step B.
B.
Connect the
Starter
Cable
to the
Y-Cable.
See
Figure 2-11, Step C
.
C.
Remove extra
Jumper
Blocks
from the added iDash
2-Pin terminations.
See
Figure 2-12.
Only one Jumper
Block Terminator is required.
3.
If you have a HW Rev 1 AND
Rev 2 iDash 1.8’s
Follow either instructions for
Rev 1
OR
Rev 2,
but
only
use a single terminator
in-cab.
2.8 Checking B-Bus
Network Termination
Type
When using multiple iDash Gauges
and/or Banks Modules it is very
important that there be
ONLY one
(1) termination in-cab.
Otherwise
your iDash 1.8 may have trouble
communicating to other devices on the
network.
Check which iDash 1.8 Hardware
Revision you have.
Look behind the
iDash 1.8 as shown in
Figure 2-12
& Figure 2-13
to visually confirm
the
Jumper Block Termination
.
Alternatively you can check the
“
Hardware Rev:
” in the “
System
Information
” menu, as shown in
Figure 2-14.
If you have
Hardware Revision
1,
you
must use
the
In-Cab
Terminator.
If you have
Hardware Revision 2,
you
will have
the
pre-installed Jumper
Block Termination.
DO NOT
use the
In-Cab Terminator
for
HW Rev 2 iDash 1.8.
2-Pin
Termination
Jumper
Block
Figure 2-11