Device description • Power Panel C70 - 10.1" display
62
Power Panel C70 User's manual V1.30
Model number
4PPC70.101G-22W
4PPC70.101G-22B
4PPC70.101N-22W
4PPC70.101N-22B
Interfaces
Interface IF1
Fieldbus
POWERLINK V2 managing or controlled node
Type
Type 4
4)
Variant
1x RJ45 shielded
Line length
Max. 100 m between 2 nodes (segment length)
Max. transfer rate
100 Mbit/s
Transfer
Physical layer
100BASE-TX
Half-duplex
Yes
Full-duplex
POWERLINK mode: No / Ethernet mode: Yes
Autonegotiation
Yes
Auto-MDI / MDIX
Yes
Interface IF2
Type
Ethernet
Variant
1x RJ45 shielded
Line length
Max. 100 m between 2 nodes (segment length)
Max. transfer rate
10/100 Mbit/s
Transfer
Physical layer
10BASE-T/100BASE-TX
Half-duplex
Yes
Full-duplex
Yes
Autonegotiation
Yes
Auto-MDI / MDIX
Yes
Interface IF3
Type
USB 2.0
Variant
Type A
Current-carrying capacity
0.49 A
Interface IF4
Type
USB 2.0
Variant
Type A
Current-carrying capacity
≥Rev. E0: 0.20 A
<Rev. E0: 0.10 A
Interface IF5
Fieldbus
X2X Link master
Interface IF6
Type
CAN bus
Variant
3 pins of the 6-pin multipoint connector
Max. distance
1000 m
Max. transfer rate
Bus length ≤25 m
1 Mbit/s
Bus length ≤60 m
500 kbit/s
Bus length ≤200 m
250 kbit/s
Bus length ≤1000 m
50 kbit/s
Terminating resistor
5)
Hardware revision ≥ G0: Integrated, can be switched on using software
Hardware revision < G0: Must be wired externally
Interface IF8
Type
RS232
Variant
3 pins of the 6-pin multipoint connector
Max. distance
900 m
Transfer rate
Max. 115.2 kbit/s
Electrical properties
Nominal voltage
24 VDC -15% / +20%
Max. power consumption
6)
14.5 W
Reverse polarity protection
Yes
Electrical isolation
IF1, IF2 and IF5 with each other, with other interfaces and with the base device
Operating conditions
Permissible mounting orientations
Standard mounting orientation
Vertical
Tilt
±25°
Rotation
In 90° increments (portrait/landscape)
Installation elevation above sea level
0 to 2000 m
No limitation
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529
Front: IP65, Back: IP20
Ambient conditions
Temperature
Operation
0 to 50°C
Storage
-20 to 70°C
Transport
-20 to 70°C
Relative humidity
See temperature/humidity diagram.
Table 25: Power Panel C70 - 10.1" variants, 1x CAN bus and 1x RS232 - Technical data