Commissioning
Power Panel C70 User's manual V1.30
85
Air circulation - Side view
Air outlet
>60 mm
>60 mm
>45 mm
Air intake
Information:
The specified air circulation clearance values are based on worst-case operation at the maximum spec-
ified ambient temperature (see "Temperature values" in chapter "Technical data").
If the specified air circulation clearance values cannot be observed, then the internal housing temper-
ature must be monitored by the user and appropriate measures taken if they are exceeded (see
perature monitoring" on page 15
).
4.1.4 Mounting orientations
Important!
Possible damage to device!
•
An ambient temperature that is too high can cause damage to the device or faulty behavior.
•
For the maximum permissible ambient temperature, see the technical data for the respective
device.
The following diagrams show the permissible mounting orientations of Power Panels. The operating temperature
limit values specified in the technical data apply taking into account the permissible mounting orientations.