![B&R Industrial Automation GmbH Power Panel 65 User Manual Download Page 74](http://html1.mh-extra.com/html/bandr-industrial-automation-gmbh/power-panel-65/power-panel-65_user-manual_3075569074.webp)
Interface modules • 4PP065.IF23-1
74
Power Panel 65 User's manual V2.21
3.5.5 RS232 (IF1) or RS485/RS422 (IF2) interface
Interface
Pinout
IF1
IF2
Pin
RS232
RS485
RS422
1
Tx+/Rx+
Tx+
2
RxD
3
TxD
4
Rx+
5
GND
6
Rx-
7
RTS
8
CTS
RS232 or RS485/RS422 interface
5
1
9
6
9-pin male DSUB connector
9
Tx-/Rx-
Tx-
Information:
The IF1 and IF2 interfaces can be used simultaneously when wired appropriately.
3.5.6 CAN bus interface (IF3)
Interface
Pinout
Pin
CAN bus
1
CAN_H
CAN high
2
CAN⊥
CAN ground
3
CAN_L
CAN low
4
SHLD
Shield
CAN bus interface
1
2
3
4
4-pin male multipoint connector
3.5.7 Terminating resistors
Two switches are located on the back of the interface module that can be used to switch on a terminating resistor
for IF2 (RS485/RS422) and IF3 (CAN bus).
OFF
ON
OFF
ON
IF2 (RS485/RS422)
IF3 (CAN bus)
Interface
Switch position
Description
ON
Terminating resistor enabled (150 Ω)
IF2 (RS485/RS422)
OFF
Terminating resistor disabled
ON
Terminating resistor enabled (120 Ω)
IF3 (CAN bus)
OFF
Terminating resistor disabled