Installation
Electrical Installation
23
Machine
Max Amps Breaker
Wire Size
Max Amps Breaker
Wire Size
HP-65, 3ph
8
15
14ga / 2.5mm
4
15
14ga / 2.5mm
HP-65, 1ph
13.6
15
14ga / 2.5mm
HP-125, 3ph
32
40
8ga / 10mm
16
20
10ga / 4mm
208-230V
380-460V
Note: For single phase operation (SP-40, 60
and 100 only), connect input power to R
and S, leaving the T terminal open.
Note: Do not use phase adders (roto-phase)
on inverter driven equipment!
Note: Wire sizes shown are for copper,
THHN, 90 conductor per NEC article 310
(USA).
The machine should be connected to an
individual branch circuit not shared with
lighting or other equipment.
Because this is a vibrating machine, the use
of SO cable or similar, with a twist-lock
plug, to connect the machine to main power
is recommended. A shielded liquid tight or
approved flexible conduit with proper
conductor of correct size installed in
accordance with National Electric Code
(USA) or other applicable codes is also
acceptable. The connection must be made
by a qualified electrician using the wiring
diagram provided with the machine. See
the Electrical Connection data Chart for
correct wire sizes.
For personal safety and for proper
operation, the machine must be grounded
in accordance with state and local codes
and in the USA in accordance with the
National Electric Code, article 250-96.
The ground connection must be to a proven
earth ground, not to conduit or water pipes.
Do not connect the ground to the neutral
(N) leg at the terminal strip (if so equipped).
If a DELTA supply system is used, the high
leg should be connected to T, since control
voltage is derived from R and S.
Insure that the control transformer taps are
connected in accordance with the incoming
line voltage. Verify connections as shown
on the schematic with each machine.
Power connection points
inside this panel
Power wire
feedthrough
Al Cu CONDUCTORS ONLY
PE
R S T
Summary of Contents for HP series