Manual Documentation Number: ZXTx-IO-x-0712m
15
Follow the steps below to install the cable gland:
1. Insert the Non-tapered end of the Body (D) through the conduit knock-out on the I/O module enclosure.
2. Place the Gasket around the body on the outside of the enclosure.
3. Thread the Hex Nut onto the Body from the inside of the enclosure.
4.
Insert the cable through the Cable gland into the enclosure
. Ensure you leave enough slack in the cable to reach the
terminal blocks.
5. Place the Cable Nut onto the cable being careful to position the threaded side so that it can be attached to the Cable Body.
6. Tighten the Cable Nut. This will cause the tapered end of the Cable Body to compress, ensuring a water-tight seal.
3.5.2 Conduit Installation
Unused conduit openings: Class 1 Division 2 installation requires a UL Recognized plug (UL
Category Code QCRV2) be used when a conduit opening is not being used.
A conduit hub is supplied with the Zlinx Xtreme I/O module where conduit installation is preferred to route the cables. It
is
suited to connect ½” or 3/8” conduit fittings and
consists of a Body, Nut, and Gasket suitable for IP67 rating. It is used to
secure threaded half inch rigid service entrance conduit.
Figure 3-4
½ inch Threaded Conduit Hub with dimensions
1. Insert the treaded end of the body into the conduit knock-out from the outside of the enclosure. The
rubber gasket should be on the outside of the enclosure.
2. Thread the Nut onto the conduit body from inside the enclosure.
3. ½ Inch, rigid, threaded conduit can be attached to the threaded hub.
3.5.3 IP67 Membrane Cable Gland
NOTE: the Cable Glands cannot be used for Class 1 Division 2 applications. Please see the Quick
Start Guide for UL Class 1 Division 2 installation instructions.
The membrane cable gland can be used to plug an unused hole in the enclosure or to route a cable.
Figure 3-5
IP67 Membrane Gland
Stuff the cable gland into the knock-out hole with the narrow end toward the inside of the I/ Module enclosure. The enclosure
wall will fit into the indentation between the inside and outside portions of the gland.