DP0005a

FAULT CONTACT

The contact is always closed when measurement functions correctly.
The fault contact opens in the event of a fault in the connected sensor.
The type of fault is indicated at the display (TR: receiver fault, TT: emitter fault). If measured turbidity is significantly greater than the maximum
measuring range of the sensor, fault message TT (emitter fault) is displayed.

All contacts are always open in the event of a fault!

RESET TO DEFAULT SETTINGS

Switch power supply on!
Within 3 seconds (i.e. during the test routine), press and hold the rotary/pushbutton selector for approximately 5 seconds:

The display counts up: 1, 2, 3, 4... 99 ST (ST = default values are loaded).
All settings are returned to their default values (factory settings).

SWITCHING SUPPLY POWER ON (TEST ROUTINE)

After supply power has been switched on, the device starts a test routine during which all LEDs and the digital display are activated (LED test).

After about 5 seconds, the evaluation units software version is briefly displayed.
The display is then “limit value display”.

INSTALLING A MEASURING CELL IN A PIPING SYSTEM (IN-LINE)

Installation of in-line measuring cell

The Measuring cells (TURBISWITCH GA1, GA5, GA11) can be installed in main lines as well as in bypass lines.

Emitter

Receiver

Horizontal installation (top view)

Flow direction

Installation in bypass line (top view)

Flow direction

Emitter

Receiver

Flow direction

Flow direction

Emitter

Receiver

Emitter

Flow direction

Vertical installation

Installation with trap

Emitter

Receiver

Measurable turbidity values depend on the process medium and the nominal diameter of the piping.
Minimum acquirable turbidity in the LOW range begins at roughly 50...100FAU.
Maximum detectable turbidity in the HIGH range: approx. 3000...10000FAU (corresponds to approx. 10...30g/l SiO₂).

Maximum detectable turbidity in the MEDIUM range: 10% of the HIGH range.
Maximum detectable turbidity in the LOW range: 1% of the HIGH range.

TUR

19-08-2021

M-410.03-EN-AA

410-03

/3

Turbidity Limit Value

Evaluation Unit

TURBISWITCH GS5

22, Rue de la Voie des Bans · Z.I. de la gare · 95100 ARGENTEUIL

Tel

Fax

+33 (0)1 30 25 83 20

+33 (0)1 34 10 16 05

Web

E-mail

www.bamo.eu

[email protected]

INTERNATIONAL

Summary of Contents for TURBISWITCH GS5

Page 1: ...OMAT series TT GS TR GS and CP1 at the evaluation unit TURBISWITCH GS5 is not possible TECHNICAL DATA Supply power 100 240V AC 50 60Hz TURBISWITCH GS5 G or 10 30V DC and 12 24V AC TURBISWITCH GS5 D Po...

Page 2: ...shed by simply turning the rotary pushbutton selector The selected hysteresis value is automatically skipped in this case 100 in the LOW range is followed by 0 in the MEDIUM range 100 in the MEDIUM ra...

Page 3: ...iefly displayed The display is then limit value display INSTALLING A MEASURING CELL IN A PIPING SYSTEM IN LINE Installation of in line measuring cell The Measuring cells TURBISWITCH GA1 GA5 GA11 can b...

Page 4: ...TURBISWITCH CP2 and CP5 transducers are designed as hanging probes or for use with an extension tube It can be installed in slurry tanks basins or open wells The probe should be installed so that it c...

Page 5: ...eiver TT HDR and TR HDR or TT HDR5 and TR HDR5 Emitter Receiver IR Light TT HDR Emitter TURBISWITCH GS5 TR HDR Receiver 10 to 30 V DC 100 to 240 V AC L N Fuse 16 14 8 2 6 1 3 4 OC V RX V Limit value L...

Page 6: ...13 15 Switching logic with increased reliability The contacts open when one of the following events occur Contact 9 11 opens when the limit value is exceeded Contact 9 12 opens when measurements are b...

Page 7: ...NG THE THRESHOLD LIMIT VALUE AND COMMISSIONING Adjustment takes place after installation and electrical connection If problems arise see Troubleshooting All steps must be carried out in chronological...

Page 8: ...is so high that no light is reaching the receiver HDR5 emitter blinks red Defective emitter Replace the emitter TR appears on the display The receiver has malfunctioned or it is not connected Check t...

Page 9: ...mescale remover The side of the glass disc marked with a dot must be installed that it faces the medium Check the seals O rings for damage and replace them if necessary before start up The frequency o...

Reviews: