OPERATING THE EVEREST 214S
After switching on the supply voltage, the device starts a test routine in which all LEDs and the digital display are activated (LEDs test).
After ≈1 second the software version is displayed for a short time.
Then the display jumps to menu level 0 (measured value display).
Power
Power supply
galvanic isolated
Signal
processing
Display
CONTROLS
See diagram of operating menu at the end of document
Rotary / push switch: t/-
Menu level 0 = Selection of display of input 1 or input 2
Menu level 1 = selection setting of the limit value for relays 1 to 4
Menu level 2 to 6 = set /-
Rotary / push switch: pressing
Selection of submenus 1 to 6
If the control button is not pressed within 15 s, the system automatically switches back to the measured value display (menu 0).
LIMIT RELAY 1 to 4
Yellow LED lights up = relay pulled in = contact is closed
LIMIT VALUE
Setting from 2 to 100%
relative to the selected mA- or MIN- or MAX range
The threshold value cannot be set smaller than or equal to the currently set hysteresis.
Default setting: A1 = 80%, A2 = 60%, A3 = 40%, A4 = 20%
DELAY
Adjustable from 0.1 to 9.9 s
Exceeding, or falling below, the limit value --> after set delay the relay switches
Default setting: 0.1 s
RE
10-02-2022
M-232.04-EN-AB
232-04
/4
4 limit value relays
EVEREST 214-S