TECHNICAL SPECIFICATIONS
MODEL
TBML 1600 ME
Maximum natural gas thermal power
kW
16000
Minimum natural gas thermal power
kW
2340
¹) natural gas emissions
mg/kWh
Class 2
Natural gas operation
Electronic modulation
Natural gas maximum flow rate
Stm³/h
1693
Natural gas minimum flow rate
Stm³/h
248
Natural gas minimum pressure
hPa (mbar)
150
Natural gas maximum pressure
hPa (mbar)
500
Diesel fuel maximum flow rate
kg/h
1349
Diesel fuel minimum flow rate
kg/h
337
Maximum diesel fuel thermal power
kW
16000
Minimum diesel fuel thermal power
kW
4000
50hz pump motor
kW
5.5
³) diesel emissions
mg/kWh
Class 2
Diesel viscosity
6 cst/20°C - 1,5° E - 20° C
Diesel operation
Electronic modulation
50hz fan motor
kW
30
50 hz ignition transformer
2x5kV - 30mA - 230V
50Hz three-phase electrical data
3L 400V - 63A - 38,29kW
50Hz single-phase electrical data
1N 230V - 1,96A - 0,454kW
Protection rating
IP54
Control box
BT 335
Flame detection
Light sensor
operating ambient air temperature
°C
-15 ÷ +40
Sound pressure**
dBA
93
Sound power***
dBA
108
Weight with packaging
kg
850
Weight without packaging
kg
800
Calorific power below reference conditions 15° C, 1013 hPa (mbar):
Natural gas: Hi = 9,45 kWh/Stm³ = 34,02 MJ/Stm³
Lower calorific power:
Diesel fuel: Hi = 11.86 kWh/kg = 42.70 Mj/kg
Minimum gas pressure, depending on the type of gas train used for obtaining max. flow rate with null pressure in the combustion chamber.
The measurements have been carried out in accordance with EN 15036 - 1 standard.
** The acoustic pressure measured with burner operating at maximum rated thermal output refers to the manufacturer's laboratory environment
conditions and cannot be compared to measurements carried out in different locations. Measurement accuracy σ = +/- 1.5 dB(A).
*** Acoustic pressure was obtained characterizing the manufacturer's laboratory with a sample source; this measurement has a class 2 accuracy
(engineering class) with a standard deviation of 1.5 dB(A).
ACOUSTIC SHROUD
If it is necessary to reduce the sound pressure level, install a suitable acoustic shroud. (see technical price list and contact the dealer) ).
STANDARD ACCESSORIES
MODEL
TBML 1600 ME
Burner coupling flange gasket
1
Stud bolts
N°8 M20
Hexagon nuts
N°8 M20
Flat washers
N°8 Ø20
Hoses
No.2 - 1" 1/2" x 1500
Filter
1" 1/2
6 / 40
0006160375_202305
ENGLISH
Summary of Contents for TBML 1600 ME
Page 2: ......
Page 37: ...SCHEMI ELETTRICI TBML 1200ME 1600ME 2000ME BT 335 35 40 0006160375_202305 ITALIANO ...
Page 38: ...TBML 1200ME 1600ME 2000ME BT 335 36 40 0006160375_202305 ITALIANO ...
Page 39: ...TBML 1200ME 1600ME 2000ME BT 335 37 40 0006160375_202305 ITALIANO ...
Page 40: ...TBML 1200ME 1600ME 2000ME BT 335 38 40 0006160375_202305 ITALIANO ...
Page 41: ...BA I1 I2 I3 I4 TBML 1200ME 1600ME 2000ME BT 335 39 40 0006160375_202305 ITALIANO ...
Page 77: ...WIRING DIAGRAMS TBML 1200ME 1600ME 2000ME BT 335 35 40 0006160375_202305 ENGLISH ...
Page 78: ...TBML 1200ME 1600ME 2000ME BT 335 36 40 0006160375_202305 ENGLISH ...
Page 79: ...TBML 1200ME 1600ME 2000ME BT 335 37 40 0006160375_202305 ENGLISH ...
Page 80: ...TBML 1200ME 1600ME 2000ME BT 335 38 40 0006160375_202305 ENGLISH ...
Page 81: ...BA I1 I2 I3 I4 TBML 1200ME 1600ME 2000ME BT 335 39 40 0006160375_202305 ENGLISH ...
Page 83: ......