4 / 26
0006081537_201311
ENGLISH
TBG 85 PN V
TBG 80 LX PN V
hEATING CAPACITY
MAX kW
850
800
MIN kW
170
130
OPERATION
Modulating / Progressive two stage burner
NOx EMISSIONS
mg/kWh
< 120 (Class II according to
EN 676)
< 80 (Class III according to
EN 676)
FAN MOTOR
kW
1.1
r.p.m.
2820
ABSORBEd ELECTRICAL POWER*
kW
1.20
line FUSE
230 V
6 A
IGNITION TRANSFORMER
26 kV - 40 mA - 230/240 V - 50/60 hz
VOLTAGE
1N ~ 230 V + 10% - 15% - 50/60 hz
PROTECTION RATING
IP 44
FLAME dETECTOR
IONISATION PROBE
NOISE**
dBA
73
AMBIENT TEMPERATURE OF OPERATION
MAX
° C
40
MIN
° C
- 10
WEIGhT
kg
80
Natural Gas (G 20)
FLOW RATE
MAX
m³n/h
85.5
80.5
MIN
m³n/h
17
13.1
PRESSURE
MAX
mbar
360
500
STANdARd ACCESSORIES
TBG 85 PN V
TBG 80 LX PN V
BURNER COUPLING FLANGE
2
INSULATING GASKET
1
STUd BOLTS
No. 4 M 12
hEXAGONAL NUTS
No. 4 M 12
FLAT WAShERS
No. 4 Ø 12
*) Total absorption at start with ignition transformer on and fan motor supplied at 50 hz.
**) Sound pressure level measured in the laboratory of the manufacturer with burner running on test boiler, at maximum rated heating capacity.
teCHniCaL anD funCtionaL sPeCifiCations
• Two-stage progressive/modulating output operation.
• Gas adjustment through the proportional working valve
controlled pneumatically.
• Combustion head with partial recycling of exhaust gases at
low NOx emissions (TBG 85 PN-V Class II), (TBG 80 LX PN-V
Class III).
• high fan output, low electrical absorption, low noise.
• Ambidextrous hinge opening for easy access to the combustion
head when burner is installed.
• Airflow adjustment with linear opening gate driven by an electric
servomotor.
• Adjustment of the number of revolutions of the fan when the
requests by the burner vary through a frequency converter
to obtain a noticeable reduction in noise and electricity
consumption.
• Closing of air gate in pause.
• Control panel prepared for connection by plugs/sockets
(supplied) with 4 and 7 poles.
• Control panel with protection rating IP55.
• Sliding coupling flange to the generator, to adapt the
protuberance of the head to various types of heating generators.
• Gas train exit possibility at the top or at the bottom.
TECHNICAL SPECIFICATIONS
Summary of Contents for TBG 80 LX PN V
Page 2: ......
Page 26: ...24 26 0006081537_201311 ENGLISH MINIMUM IONISATION CURRENT 3 μA OPTIONAL WIRING DIAGRAM ...
Page 28: ...26 26 0006081537_201311 ENGLISH ...
Page 54: ...26 26 0006081537_201311 ESPAÑOL ...
Page 80: ...26 26 0006081537_201311 FRANÇAIS ...
Page 104: ...24 26 0006081537_201311 TÜRKÇE ASGARİ İYONİZASYON AKIMI 3 µA TALEP ÜZERİNE ELEKTRİK ŞEMASI ...
Page 106: ...26 26 0006081537_201311 TÜRKÇE ...
Page 132: ...26 26 0006081537_201311 PYCCKИИ ...
Page 156: ...24 26 0006081537_201311 中 文 最小电离电流3μA 如果有需求 电气图 ...
Page 158: ...26 26 0006081537_201311 中 文 ...
Page 159: ......