SUPPLY LINE
The figure below shows the gas supply line block diagram.
The gas train is certified in compliance with EN 676 Standard and
supplied separately from the burner.
DANGER / ATTENTION
Install a manual shut-off valve and a vibration-proof joint
upstream of the gas valve, according to the layout shown in
the block diagram.
GAS TRAIN BLOCK DIAGRAM
M
M
12
10
9
14
11
13
8
4
7
6
5
3
2
1
0002910950N2
TO BE CARRIED OUT BY THE INSTALLER
GAS TRAIN SUPPLIED BY THE MANUFACTURER
1
Manual shut-off valve
2
Vibration-proof joint
3
Gas filter
4
Minimum gas pressure switch and for controlling gas leaks
5
Safety valve
6
Pressure regulator
7
Valve seal control device (mandatory for burners with maximum rated
heating capacity higher than 1200kW)
8
Working valve
9
Air regulation servomotor
10
Air regulation damper
11
Air pressure switch
12
Combustion head
13
Gas throttle valve
14
Gas regulation servomotor
14 / 34
0006081328_202202
ENGLISH
Summary of Contents for TBG 80 LX ME
Page 2: ......
Page 32: ...SCHEMI ELETTRICI TBG 80 360LX ME TBG 80 360 ME 30 34 0006081328_202202 ITALIANO...
Page 33: ...TBG 80 360LX ME TBG 80 360 ME 31 34 0006081328_202202 ITALIANO...
Page 34: ...TBG 80 360LX ME TBG 80 360 ME I1 I2 BA I4 I3 32 34 0006081328_202202 ITALIANO...
Page 36: ...34 34 0006081328_202202 ITALIANO...
Page 66: ...WIRING DIAGRAMS TBG 80 360LX ME TBG 80 360 ME 30 34 0006081328_202202 ENGLISH...
Page 67: ...TBG 80 360LX ME TBG 80 360 ME 31 34 0006081328_202202 ENGLISH...
Page 68: ...TBG 80 360LX ME TBG 80 360 ME I1 I2 BA I4 I3 32 34 0006081328_202202 ENGLISH...
Page 70: ...34 34 0006081328_202202 ENGLISH...
Page 71: ......