OPERATING RANGE
2
4
6
8
0
10
12
14
hPa (mbar)
0002929510
100 200 300 400 500 600 700 800 900 1000 1100
kW
1200 1300 1400 1500 1600
16
1700 1800 1900 2000
18
TBG 80LX P
TBG 80LX MC
TBG 110LX P
TBG 110LX MC
TBG 140LX P
TBG 140LX MC
TBG 200LX P
TBG 200LX MC
0002929471
18
16
14
12
10
8
6
4
2
0
450 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700
KW
2800 2900 3000 3100 3200 3300 3400 3500 3600
hPa / mbar
TBG 360 LX ME
TBG 360 LX MC
TBG 260 LX ME
TBG 260 LX MC
IMPORTANT
MINIMUM PROPANE THERMAL POWER TBG 80 LX = 200 kW
MINIMUM PROPANE THERMAL POWER TBG 260 = 500 kW
MINIMUM PROPANE THERMAL POWER TBG 360 = 600 kW
IMPORTANT
The operating ranges are obtained from test boilers corresponding to Standard EN676 and are indicative of the burner-boiler combination.
For correct working of the burner, the size of the combustion chamber must correspond to current regulations; if not the manufacturers
must be consulted.
DANGER / ATTENTION
During the ignition and adjustment phase, check that the maximum and minimum outputs at which the burner is adjusted are within the
working range in order to avoid damage to the system.
9 / 38
0006160254_202106
ENGLISH