SPECIFICATIONS FOR PROPANE USE
•
Operating costs approximate assessment;
- 1 m3 of liquid gas in gaseous stage has a lower heating capaci-
ty, of nearly 25.6 kWh.
-
To obtain 1 cu.m of gas, about 2 kg of liquid gas are needed,
i.e. about 4 litres of liquid gas.
•
Safety provisions
• Liquid propane gas (L.P.G.) in the gaseous form has a greater spe-
cifi c weight than air (specifi c weight relative to air = 1.56 for propa-
ne), which means it does not disperse in air like natural gas, which
has a lower specifi c weight than air (specifi c weight of natural gas
relative to air = 0.60), but precipitates and spreads out at ground
level (as if it were a liquid). Summing up the concepts we deem
most relevant fi r the use of LPG
•
Liquefi ed petroleum gas (L.P.G.) burners and/or boilers may be
used only in premises located above ground level and certifi ed
toward free spaces. Installations using liquid gas are not allowed in
underground or semi-underground premises.
• Rooms where liquid gas is used must have ventilation inlets without
closing devices, located on external walls, in compliance with the
local exiting rules.
•
Carrying out the propane gas system to ensure
correct, safe operation.
Natural gasifi cation from sets of cylinders or a tank can be used only
in low power systems. Gas supply capacity on the basis of tank size
and minimum outdoor temperature are shown in the table below, as
an approximate indication only.
Minimum
tempera-
ture
- 15 °C
- 10 °C
- 5 °C
- 0 °C
+ 5 °C
Tank 990 l. 1.6 Kg/h
2.5 Kg/h
3.5 Kg/h
8 Kg/h
10 Kg/h
Tank
3000 l.
2.5 Kg/h
4.5 Kg/h
6.5 Kg/h
9 Kg/h
12 Kg/h
Tank
5000 l.
4 Kg/h
6.5 Kg/h
11.5 Kg/h
16 Kg/h
21 Kg/h
•
Burner;
The burner must be ordered specifi cally for use with liquid gas
(L.P.G.) so that it is equipped with gas valves of suffi cient dimen-
sions to ensure correct ignition and gradual adjustment. We provide
valves with size suitable for a supply pressure starting from approx.
300 mm mbar. You suggest checking the burner gas pressure by
using a pressure gauge.
DANGER / ATTENTION
The maximum and minimum power (kW) of the burner refers
to natural gas which is more or less the same as with propane.
•
Combustion control
To keep consumption down and mainly to prevent serious problems,
regulate the combustion using the specifi c instruments. It is absolu-
tely essential to check that the percentage of carbon monoxide (CO)
does not exceed the maximum permitted value by the local existing
regulation (use a combustion analyser or other similar instrument).
ENGLISH
29 / 44
0006160281_202007
Summary of Contents for TBG 450LX ME
Page 2: ......
Page 34: ...SCHEMI ELETTRICI ITALIANO 32 44 0006160281_202007...
Page 35: ...ITALIANO 33 44 0006160281_202007...
Page 36: ...ITALIANO 34 44 0006160281_202007...
Page 37: ...BA BP I1 I2 I3 I4 ITALIANO 35 44 0006160281_202007...
Page 38: ...ITALIANO 36 44 0006160281_202007...
Page 39: ...ITALIANO 37 44 0006160281_202007...
Page 40: ...ITALIANO 38 44 0006160281_202007...
Page 41: ...ITALIANO 39 44 0006160281_202007...
Page 42: ...ITALIANO 40 44 0006160281_202007...
Page 43: ...BA BP I1 I2 I3 I4 ITALIANO 41 44 0006160281_202007...
Page 44: ...ITALIANO 42 44 0006160281_202007...
Page 45: ...ITALIANO 43 44 0006160281_202007...
Page 78: ...WIRING DIAGRAMS ENGLISH 32 44 0006160281_202007...
Page 79: ...ENGLISH 33 44 0006160281_202007...
Page 80: ...ENGLISH 34 44 0006160281_202007...
Page 81: ...BA BP I1 I2 I3 I4 ENGLISH 35 44 0006160281_202007...
Page 82: ...ENGLISH 36 44 0006160281_202007...
Page 83: ...ENGLISH 37 44 0006160281_202007...
Page 84: ...ENGLISH 38 44 0006160281_202007...
Page 85: ...ENGLISH 39 44 0006160281_202007...
Page 86: ...ENGLISH 40 44 0006160281_202007...
Page 87: ...BA BP I1 I2 I3 I4 ENGLISH 41 44 0006160281_202007...
Page 88: ...ENGLISH 42 44 0006160281_202007...
Page 89: ...ENGLISH 43 44 0006160281_202007...
Page 91: ......