7 / 20
0006081159_201209
ENGLISH
SIPHON FEED SYSTEM WITH FEED FROM THE TOP OF THE TANK
SUCTION FEED SYSTEM
GRAVITY FEED SYSTEM
H Height difference between minimum tank level and pump axis.
L Total length of pipeline, including vertical length. Subtract 0.25 m for every elbow or gate
valve.
NOTE: Comply with the regulations in force for any components missing in the pipelines.
Dimension P = 3.5 m. (max.)
1 Tank
2 Feeding pipe
3 Wire-net filter
4 Pump
5 Degasifier
PUMP AXIS
PUMP AXIS
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
PUMP AXIS
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
7 Return pipe
10 Foot valve
H metres
Length total metres
Ø i = 10 mm
Øi.= 12 mm
1
20
30
2
25
35
3
30
40
4
35
45
H
metres
Length total metres
Ø = 10mm
Øi. 12 mm
0.5
15
27
1
12
23
1.5
9
19
2
7
15
2.5
4
10
3
-
7
3.5
-
-
H metres
Length total metres
Ø i = 10 mm
Øi.= 12 mm
1
20
30
2
25
35
3
30
40
4
35
45
6 Suction pipe
7 Burner return pipe
8 Automatic shut-off device with burner off
9 One-way valve
7 Return pipe
8 Automatic shut-off device with burner off
9 One-way valve
10 Foot valve
Summary of Contents for Minicomist 11
Page 2: ......
Page 19: ...17 20 0006081159_201209 ENGLISH WIRING DIAGRAM ...
Page 20: ...18 20 0006081159_201209 ENGLISH ...
Page 22: ...20 20 0006081159_201209 ENGLISH ...
Page 39: ...17 20 0006081159_201209 TÜRKÇE ELEKTRIK ŞEMASI ...
Page 40: ...18 20 0006081159_201209 TÜRKÇE ...
Page 42: ...20 20 0006081159_201209 TÜRKÇE ...
Page 43: ......