ELECTRICAL CONNECTIONS
• It is advisable to make all connections with flexible electric wire.
• Observe applicable national and European Standards (e.g. EN
60335-1/EN 50165) regarding electrical safety.
• Connect the devices, without option N or N1, to the power supply
respecting the phase-neutral polarity of the mains.
• Carefully check the cables before commissioning.
• Incorrect wiring can damage the equipment and jeopardise system
safety.
• Makes sure the equipment earth terminal, the metal burner casing
and electrical system earthing are connected properly.
• Avoid laying the detection cable along with the power cables or
ignition cables.
• Use a shorter and straight ignition cable and lay it far from other
conductors to minimise radio interferences (maximum length less
than 2 m and isolation voltage > 25 kV).
• This equipment has internal fuses, however, it must be protected
by means of at least one fuse on the line connection.
• Electrical lines must be kept away from hot parts.
• The burner installation is allowed only in environments with
pollution degree 2 as indicated in annex M of the EN 60335-
1:2008-07 regulation.
• Make sure that the electric line to which the unit will be connected
has frequency and voltage ratings suitable for the burner.
• The three-phase or single-phase power supply line must have
a switch with fuses. The standards also require a switch on the
burner's power line located outside the boiler room where it can be
accessed easily.
• The main line, the relevant switch with fuses and the possible
limiter must be suitable to support the maximum current absorbed
by the burner.
• The mains supply connection requires an omnipolar switch with a
contact opening gap equal to or greater than 3 mm in accordance
with current safety regulations.
• Refer to the wiring diagram for electrical connections (line and
thermostats).
• Unsheathe the external insulating cover of the power cable to the
necessary extent for the connection, thus avoiding the wire from
coming into contact with metal parts.
Summary of Contents for GI 350 DSPG
Page 2: ......
Page 39: ...ITALIANO 37 40 0006080098_201803 SCHEMI ELETTRICI...
Page 40: ...ITALIANO 38 40 0006080098_201803...
Page 41: ...ITALIANO 39 40 0006080098_201803...
Page 79: ...ENGLISH 37 40 0006080098_201803 WIRING DIAGRAMS...
Page 80: ...ENGLISH 38 40 0006080098_201803...
Page 81: ...ENGLISH 39 40 0006080098_201803...
Page 83: ......