![baltur BTL 3 User Instruction Manual Download Page 46](http://html1.mh-extra.com/html/baltur/btl-3/btl-3_user-instruction-manual_4057246046.webp)
MALFUNCTION CAUSE DIAGNOSTICS AND LOCK
In the event of a burner lock-out, the red light on the reset button will be fixed.
Keeping it pressed in for more than 3 seconds, the diagnostics procedure is activated (red light with quick flashes). The table below indi
-
cates the meaning of the lock-out or failure according to the number of red flashes.
Holding the reset button down for at least 3 seconds, the diagnostics function will be interrupted (for further details see technical sheet
7614).
The diagram below indicates the operations that are necessary to activate diagnostics functions.
EK
> 3 s
Flashing
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
EK
> 3 s
O
CI
40
0
EK
< 3 s
71
30
z04e
/060
2
Reset
On
Operating position
PC interface/
diagnostic analyser
Colour code table
Diagnostics
Operating position
Operating position
Visual indication
AL to terminal
10
Possible causes
2 blinks
●●
On
No flame at the end of the safe ignition time<TSA>
- Faulty or soiled fuel valves
- Faulty or soiled flame detector
- Poor adjustment of burner, no fuel
- No ignition Faulty ignition transformer
3 blinks
●●●
On
Available
4 blinks
●●●●
On
Extraneous light during the ignition phase
5 blinks
●●●●●
On
Available
6 blinks
●●●●●●
On
Available
7 blinks
●●●●●●●
On
Lack of flame signal during normal operation, ignition repeated (ignition is repeated
max. 3 times)
- Fuel valves' failure or earthing not correct
- Poor adjustment of burner
8 blinks
●●●●●●●●
On
Fuel preheating time failure
9 blinks
●●●●●●●●●
On
Available
10 blinks
●●●●●●●●●●
On
Wiring problems or damage inside the device
•
Under fault conditions the device remains deactivated. The burner is off.
•
The «AL» alarm signal is on terminal 10 that is under voltage. To reactivate the device and start a new cycle, press the reset button for
1 sec. (< 3 sec).
ENGLISH
18 / 26
0006080735_201409
Summary of Contents for BTL 3
Page 2: ......
Page 26: ...SCHEMI ELETTRICI ITALIANO 24 26 0006080735_201409...
Page 27: ...ITALIANO 25 26 0006080735_201409...
Page 52: ...WIRING DIAGRAMS ENGLISH 24 26 0006080735_201409...
Page 53: ...ENGLISH 25 26 0006080735_201409...
Page 55: ......